Current IntelPower LibraryShop main store

Selection guide

Choosing flexible wire for large motor leads and starters

Wiring, grounding and bonding Published 6 min read

Short answer

Yes, but not welding cable. Replace stiff 7-strand #2 AWG with 19-strand building wire of the same type, or use dual-rated DLO carrying an RHH/RHW-2 print line (105 strands at 4 AWG, 273 at 1/0) or SIS/XHHW-2 Class H wire (133 strands from 8 AWG up). Size from the 75 C column at the lugs, and keep tight bends away from every termination.

On this page
  1. The conductors that bend and stay listed
  2. What the code requires before flexibility matters
  3. Stranding buys bend radius, not ampacity
  4. Terminating fine strands without a callback
  5. Inside the enclosure: flexible busbar
  6. What to order, by case
  7. Questions asked

Skip the welding cable. For rigid #1, #2 and #3 AWG motor leads on 480 V three-phase systems, three listed conductors bend where THHN or MTW will not: building wire with finer stranding, such as 19-strand #2 AWG in place of the usual 7-strand; diesel locomotive (DLO) cable that also carries an RHH/RHW-2 print line, with 105 strands at 4 AWG and 273 at 1/0 AWG; and dual-rated SIS/XHHW-2 wire stranded to ASTM B173 Class H, with 133 strands from 8 AWG up and 259 at larger sizes. Inside the enclosure, laminated flexible busbar handles right angles no cable should be forced into. Every one of those choices still has to pass the same two gates: a listing the installation recognizes under the National Electrical Code, and terminations the lug maker rates for that stranding.

The conductors that bend and stay listed #

Conductor Documented stranding Best use Non-negotiable condition
Building wire, finer stranding 19 strands in place of the usual 7 in #2 AWG Raceway runs from starter to motor terminal box Same THHN, THWN-2 or MTW print line the spec calls for
DLO cable, dual rated 105 strands at 4 AWG, 273 at 1/0 AWG, thermoset jacket Short leads and tight terminal boxes Jacket must print RHH/RHW-2
SIS/XHHW-2 133 strands from 8 AWG, 259 at larger gauges, ASTM B173 Class H Internal starter and panel wiring XHHW-2 side covers raceway and building-wire use
Laminated flexible busbar Flat copper strips instead of strands Right-angle links between fixed points in a panel Insulated, supported, ends drilled for direct bolting
Welding cable Not applicable None of these jobs No Article 310 building-wire listing

For the field run, the quiet win is ordering the same building wire with the finer stranding: the print line does not change, so nothing in the specification changes except how the conductor bends at the box.

Manufacturer technical literature places DLO in general wiring under Article 310 of the NEC on the strength of its RHH/RHW-2 listing, with a thermoset jacket rated 90 C wet or dry. That permission lives on the print line of the cable you actually buy; the letters DLO alone on the jacket are not a building-wire designation, so verify the marking before the reel leaves the rack.

On SIS/XHHW-2, the SIS side is the switchboard and panel wiring type, and the XHHW-2 side is accepted in raceways and general building-wire applications, which is exactly what a dual rating is for. Welding cable has neither designation, which ends the discussion on a 480 V motor circuit.

What the code requires before flexibility matters #

  • NFPA 70, the National Electrical Code, 2023 edition, Article 310 governs conductors installed in raceways and cable assemblies, which is where your motor leads live.
  • Section 430.12 governs motor terminal boxes; their construction and bending space decide whether a stiff #1 to #3 AWG conductor can be landed properly at all.
  • Section 430.22 sets branch-circuit conductors for a continuous-duty motor at not less than 125 percent of full-load current; Table 430.250 supplies the full-load current and Table 310.16 supplies the ampacity.
  • Section 110.14(C) caps the ampacity you may use at the temperature rating of the termination, regardless of what the insulation is rated.

Confirm the adopted edition and any local amendments with the authority having jurisdiction, and follow the motor and starter documentation for what the terminals accept.

Stranding buys bend radius, not ampacity #

A published DLO ampacity chart can list 2 AWG at 170 A because the insulation is rated 90 C wet or dry. That number is not usable at a 75 C lug: under 110.14(C) the 75 C column of Table 310.16 governs there, where 2 AWG copper is 115 A. Commit to the rule: fine stranding buys bend radius, and the ampacity comes from the listed type, the table and the termination. The 90 C column is the starting point for derating calculations only, such as high ambient or grouped conductors, and the derated result still cannot exceed the termination limit.

Worked example: 75 HP, 460 V motor lead #

Illustrative inputs: 75 HP, 460 V, three-phase, continuous duty; copper conductors; three current-carrying conductors in one raceway; 30 C ambient; lugs rated 75 C.

  1. Full-load current, Table 430.250: 96 A.
  2. Required ampacity, Section 430.22: 1.25 x 96 A = 120 A.
  3. Table 310.16, 75 C column, copper: 2 AWG = 115 A. Since 115 A < 120 A, the downsize the DLO chart suggests fails.
  4. 1 AWG = 130 A, and 130 A >= 120 A, so the conductor is 1 AWG.

Decision: order that 1 AWG in the finer building-wire stranding for the raceway run. If only the final drop into the terminal box is tight, 1/0 AWG DLO with the RHH/RHW-2 print line also passes with margin: 150 A at 75 C against the same 120 A requirement. This is a worked estimate against the tables named; confirm it against the governing code edition and the equipment documentation before building. The same look-ups settle small circuits too, and the walk-through in NEC motor branch circuit #14 AWG with a 20 A breaker shows the method at low amperages.

Terminating fine strands without a callback #

Open nothing energized: lock out the feeder and test for absence of voltage at the starter and the motor terminal box before a lug comes off.

  • Match the connector to the construction. Inner bunches of rope-lay cable can slide out of a connector never listed for them, and a tight bend close to the barrel plus vibration and heating-cooling cycles is the classic recipe for a loose joint. Use a connector whose listing names flexible stranding.
  • Keep the tightest bend several conductor diameters back from the barrel, and clamp the cable so bending loads land on the support, not on the termination.
  • Crimp with the connector manufacturer's tool, die and pass sequence; a field-devised method is not a termination.
  • Two-hole lugs also resist rotation under vibration, and the trade-offs are laid out in NEMA 2-hole versus 4-hole lug selection for power terminations.
  • The 75 C termination limit follows every flexible cable, and sizing Type W conductors for 75 C lug terminations shows the same method applied to portable cable.
  • Thermographically check the new joints after the first week of load cycles.

Inside the enclosure: flexible busbar #

When the link between two fixed points inside a panel needs a sharp right angle or a compound twist, laminated copper strip takes it without springback, and the ends can be drilled for direct bolting, which removes the fine-strand lug question entirely. Insulate it, support it, and hold the spacings that UL 508A, the industrial control panel standard, calls for. It is an internal link material, not a feeder or a motor lead. And when the enclosure itself is the problem, upsizing the conduit or cabinet beyond the code minimum removes the bends that make large conductors hard to land in the first place.

What to order, by case #

  • Long conduit run from starter to motor: building wire in the finer stranding, at the size the calculation gives.
  • Tight motor terminal box, or a short final drop: DLO that prints RHH/RHW-2 on the jacket, sized from the 75 C column.
  • Wiring inside the starter or panel: SIS/XHHW-2 with Class H stranding.
  • A right angle inside the panel that no conductor survives: laminated flexible busbar with drilled ends.
  • Welding cable: not on a motor circuit. Where it turns up on one, replace it with a listed conductor.

Questions asked

Can I use welding cable for 480 V three-phase motor leads?

No. Welding cable carries no building-wire type designation recognized for the raceway installations that NFPA 70, the National Electrical Code, treats in Article 310, and its rope-lay stranding falls outside what standard compression lugs are listed for. Where it is already installed on a motor circuit, the fix is replacement with a listed conductor, not relabeling. DLO that prints RHH/RHW-2 on the jacket is the flexible conductor that does carry a recognized designation.

Does fine stranding increase ampacity so I can use a smaller wire?

No. Ampacity comes from the listed type's table and the termination temperature rating, not from strand count. A published DLO chart listing 2 AWG at 170 A reflects a 90 C insulation rating under that chart's own conditions; at 75 C lugs the 75 C column governs and 2 AWG copper is 115 A. The 90 C rating is the starting point for derating, for example high ambient, and the derated value still may not exceed what the terminations allow.

Will 19-strand #2 AWG land in the same lugs as 7-strand wire?

In principle yes. Nineteen-strand #2 AWG is a standard concentric building-wire construction at the same 2 AWG cross-sectional area, so AWG-keyed lugs and dies fit it as they fit the 7-strand product, with the same crimp practice. Read the lug listing sheet once, as with any conductor change, because that listing names the constructions the connector was tested with, and it is the acceptance that counts.

How do I stop fine-stranded lugs from loosening in a vibrating starter enclosure?

Use a connector whose listing covers flexible stranding, keep the tightest bend several conductor diameters back from the barrel, and clamp the cable so vibration and thermal cycling load the support rather than the lug. Some shops tin or braze large fine-stranded ends; a listed connector made for the strand class is the documented route. After the first week of load cycles, scan the joints and compare them against the crimp practice above.

When is flexible busbar better than any cable inside the panel?

When the route between two fixed points needs a sharp right angle or a compound twist that no conductor should be forced into. Laminated copper strip takes those bends without springback, and drilling the ends for direct bolting removes the fine-strand lug question entirely. Insulate it, support it, and hold the spacings the panel standard calls for. It is for short internal links, not for feeders or motor leads in raceway.

Keep reading

  • Troubleshooting

    Diagnosing 200 A currents on equipment grounding conductors

    Hundreds of amperes on equipment grounding conductors between a substation and its MCCs, with like phases grouped in cable tray, is magnetically induced circulating current, not a ground fault. Clamp all circuit conductors of one feeder: a residual near zero proves induction, and the fix is regrouping each parallel set A-B-C.

    Wiring, grounding and bonding

  • How-to

    Installing a robust PROFIBUS DP network inside an MCC

    Run the bus at or below 1.5 Mbit/s, keep the cable against the bonded backplane, clamp the shield to bonded metalwork at every MCC entry, and terminate only the two electrical ends of the segment: a slower rate widens timing margins but cannot fix poor bonding or missing termination.

    Wiring, grounding and bonding

  • Troubleshooting

    Why motors burn up with no overload trips on 480 V

    Crystallized insulation several feet back from motor terminals is the signature of high-resistance terminations cooking the leads from I²R heat, while unbalanced voltage adds negative-sequence heating that current-magnitude overload heaters never see. Record all three line-to-line voltages and all three phase currents under load, verify the transformer grounding, and measure insulation resistance on every failed branch before any restart. Welded contacts and ruptured starters are consequences of closing onto failed motors, not a separate mystery.

    Motors and motor starters