How-to
How many 480 V fixtures on a 30 A three-pole breaker
Short answer
Fifteen 2.4 A fixtures fit on a 30 A three-pole 480 V breaker: five each on A-B, B-C and C-A draw 20.8 A per line, under the 24 A continuous-load limit, because a three-pole breaker's pole ratings never add.
On this page
- Does a three-pole breaker give me three times the lighting capacity?
- Is the fixture current the nameplate value or lamp watts divided by voltage?
- How much of the rating can the lighting bank use continuously?
- Why does each line carry √3 times one pair's current?
- How many fixtures fit on the breaker?
- How do I land the fixtures on the contactor and keep it balanced?
- What should I measure after the bank warms up?
- Questions asked
Fifteen fixtures. Put five 2.4 A metal halide fixtures on each line pair — A-B, B-C and C-A — at the three-pole contactor fed by the breaker, and every line carries 20.8 A against the continuous-load allowance for its pole, about 13 percent of headroom. The trap is the breaker itself: a three-pole frame is not three times the capacity, because each pole is a separate limit on one line. The line-to-line groups form a delta bank, so line current is √3 times one pair's current — not the pair current, and not the arithmetic sum of two pairs. This walkthrough sizes the circuit, schedules the groups and verifies the result with a clamp meter.
Does a three-pole breaker give me three times the lighting capacity? #
No — a three-pole breaker is three separate limits, one per line, never 90 A of capacity; the fixture count is set by the current in the busiest line, and that current flows through one breaker pole, one contactor pole and one conductor. The three poles open together, and each one senses only its own line. What the three-pole arrangement buys you is not extra amperes but the ability to spread single-phase loads across three line pairs: one pair loaded to the continuous allowance carries ten fixtures, while three balanced pairs carry fifteen on the same per-line allowance.
Is the fixture current the nameplate value or lamp watts divided by voltage? #
Use the nameplate input current, not the 2.08 A quotient: a metal halide ballast draws more than lamp watts divided by voltage because of ballast losses, power factor and its starting characteristic. The 2.08 A figure assumes the lamp consumes exactly 1000 W at unity power factor with no losses in the ballast, which no real fixture achieves. The fixture or ballast documentation states the input current at 480 V, and that value is what sizes the circuit. Warm-up draws current above the run value for the first minutes after ignition, which matters for tripping but not for the steady-state count.
How much of the rating can the lighting bank use continuously? #
24 A per line: NFPA 70, the National Electrical Code, 2023 edition, defines a continuous load as one at its maximum current for three hours or more, and Article 210.20(A) requires the branch-circuit overcurrent device to be rated at not less than 125 percent of that load. A metal halide bank that runs through a shift or all night meets the three-hour definition, so treat it as continuous: 30 A × 0.80 = 24 A per line. Article 210.19(A)(1) applies the same 125 percent to the branch conductors, so the wire and its terminations must carry it too, and the breaker must also be adequate for the available fault current at the panel. An exception permits a device listed and marked for operation at 100 percent of its rating, which raises the ceiling to the device's full rating under its listing conditions. Confirm this requirement, and any local amendments, with the authority having jurisdiction and the equipment documentation.
Why does each line carry √3 times one pair's current? #
Because every line serves two fixture groups whose currents sit 120 electrical degrees apart, so the conductor carries their phasor difference — and two equal branch currents displaced 120° combine to √3, about 1.732, times one branch current. Five fixtures on a pair draw 12 A in that branch. Line A carries the currents of the A-B group and the C-A group together; displaced by a third of a cycle, they do not add arithmetically, and because the second group is attached, the line does not carry one branch's current alone either. The magnitude works out to √3 × 12 A = 20.8 A. The three groups behave as a delta-connected bank even though every fixture is a single-phase load — this says nothing about how the source transformer is wound internally.
How many fixtures fit on the breaker? #
Five per pair: N = floor(limit ÷ 4.16 A) = floor(5.77) = 5, so 15 fixtures total, drawing 20.8 A in each of the three lines. The steps, with every input stated:
- Set the per-line limit for a continuous lighting load as derived above: breaker rating × 0.80.
- Read the fixture input current from the nameplate.
- Convert to a per-line figure: one fixture on every pair means √3 times the nameplate current, 4.16 A in each line, so N fixtures per pair give N × 4.16 A per line.
- Solve for the maximum: N = floor(5.77) = 5 fixtures per pair.
- Check the next count up: six per pair gives 6 × 4.16 A = 24.9 A per line, over the limit on a standard-rated breaker.
- Total and schedule: five on each of the three pairs = 15 fixtures, 20.8 A per line, 3.2 A of margin.
Decision: 15 fixtures on this breaker at 80 percent loading. The count is an estimate to be checked against the governing code edition and the installed equipment's documentation.
How do I land the fixtures on the contactor and keep it balanced? #
Five across A-B, five across B-C and five across C-A, landed on the contactor's output terminals so each pole switches one line, with the 120 V coil circuit kept separate. The control side is the same arrangement as wiring a three-phase coolant pump starter from a 120 V signal: the coil gets its own overcurrent protection and conductor, and it does not change the fixture math. Verify the contactor's continuous current rating covers the line current, since its poles see exactly what the breaker poles see. Before anyone opens the panel, the contactor cover or a fixture terminal box to make these connections, open the feeder, lock it out and test for absence of voltage — NFPA 70E, 2024 edition, sets the lockout and verification practice. Equal counts per pair are what make the single √3 formula valid; if the count will not divide by three, work out the busiest line from its two attached branches or measure it after warm-up instead of using the balanced formula.
What should I measure after the bank warms up? #
Clamp each of the three lines after the lamps finish warm-up and compare the highest single reading — not the average — against the per-line limit: balanced groups read close to 20.8 A on every line. Metal halide lamps take several minutes to stabilize, so wait until the currents stop rising before recording. Then:
- Clamp lines A, B and C at the contactor output and record all three readings.
- Compare the highest reading with the per-line limit.
- Measure line-to-line voltage at the contactor output and at the farthest fixture under full load — the approach is the same as fixing voltage drop on a long 277 V lighting feeder, checking that the far-end voltage stays inside the fixture's rated range.
- If one line reads meaningfully higher than the others, clamp the individual pairs to find the group that is off: unequal counts, a lamp that has failed or is cycling, or a ballast drawing differently.
- If the breaker trips only at energization, capture the start with an instrument that records transient current and compare it with the breaker's trip curve, or split the bank across two contactor steps so the groups do not start together.
Questions asked
Can a breaker rated for 100 percent loading add a sixth fixture per pair?
Yes, when the breaker is listed and marked for operation at 100 percent of its rating and its termination conditions are met, the per-line ceiling rises to the device's full rating. Six per pair then draws 24.9 A per line, so 18 fixtures fit on the same schedule. Re-check the contactor's continuous rating and the conductor ampacity at that higher current before adopting it.
How do I size the circuit when the pairs cannot be equal?
Compute each line from its two attached branch currents: line current = √(I1² + I2² + I1 × I2), which holds when the branches have similar power factor. With six fixtures on one pair (14.4 A) and four on the adjacent pair (9.6 A), the shared line carries √(207 + 92 + 138) = 20.9 A, still under the limit.
Does the 120 V control circuit change the fixture count?
No. The control circuit feeds only the contactor coil, so it takes its own overcurrent protection and its own conductor sizing. Verify the coil really is a 120 V coil before wiring it, keep control wiring separated from the power conductors as the code requires, and the fixture count stays exactly as calculated.
Does the same math work for 480 V LED fixtures?
Only the current figure changes. The √3 relation comes from connecting single-phase loads across three line pairs, not from the lamp type, so divide the per-line limit by √3 times the driver's rated input current and round down. For example, a driver rated 1.4 A gives nine per pair, or 27 fixtures, because ten per pair would reach 24.2 A.