Motor starter vs contactor: using a starter as one

Motors and motor starters Published 8 min read

Short answer

A motor starter is a contactor with an overload relay added: the relay's normally closed contact opens the coil circuit on sustained overcurrent. A starter works wherever a contactor is called for, provided three checks pass — horsepower rating at the supply voltage, coil voltage, and the overload setting against the motor's nameplate full-load current. A NEMA Size 1 covers a 3 HP motor.

On this page
  1. What a contactor is, and what the starter adds
  2. NEMA 1 on the nameplate means two different things
  3. NEMA size: the horsepower decision
  4. The overload relay: where it sits, and how many elements it has
  5. Three-wire control and the seal-in contact
  6. Using a starter as a contactor: three checks and a worked example
  7. Reading a dropout: heat trip or control logic
  8. Variants that need a second look
  9. Questions asked

Yes — a starter can stand in wherever a plan calls for a plain contactor. A motor starter is a contactor with an overload relay added: the relay's normally closed contact sits in series with the coil and opens it on sustained overcurrent, dropping the power contacts. Take the overload relay off and the device is a contactor again. Three checks decide whether your starter fills the contactor position: horsepower rating at your supply voltage, coil voltage, and overload setting against the motor's nameplate full-load current. A NEMA Size 1 starter covers a 3 HP motor at any common three-phase industrial voltage.

What a contactor is, and what the starter adds #

A contactor is an electrically operated switch. A solenoid coil pulls the power contacts in; a spring drops them out when the coil de-energizes. Nothing in that box watches current: a bare contactor will hold a motor at 150% of full-load current until the insulation, not the switch, gives up.

A magnetic motor starter is the same contactor plus an overload relay, and the relay is the whole difference. Its current elements sit in the motor power path and carry motor current. Its normally closed control contact sits in the coil circuit. Current above the setting, held long enough, heats the elements to the trip point; the contact opens, the coil de-energizes, and the power contacts drop out. Because the protection acts through the control circuit, a starter with the overload contact missing or jumpered out runs as a plain contactor while everyone believes otherwise.

Starters also carry horsepower ratings, because the contact set is built to close onto locked-rotor inrush and carry full-load current continuously. The common bare contactor in packaged equipment is the definite-purpose type: contacts and solenoid, no overloads, and usually no provision for a start/stop station.

NEMA 1 on the nameplate means two different things #

The marking can describe the contactor or the box it ships in. NEMA size 1 is a rating class that fixes the current and horsepower the contacts handle. Type 1 is an enclosure designation: general-purpose, indoor, with no protection against water or dust. The two are independent — read the size marking on the contactor body or the starter nameplate, and read the enclosure type separately before choosing where the unit mounts.

Horsepower ratings also depend on running voltage and phase: a rating quoted at 460 V says nothing about 230 V, and the 200/208 V column is not the 230 V column. Confirm both from the nameplate or the manufacturer's data sheet.

NEMA size: the horsepower decision #

NEMA rates each starter size in horsepower at named voltages. One documented Size 2 listing carries 45 A continuous, 10 HP at 200 V AC, and 25 HP at 460 V and 575 V AC. One size down, a Size 1 covers a 3 HP motor at any of those voltages with margin. Decision for a 3 HP load: the Size 1 goes in.

Oversized contactors are not electrically wrong for a small motor — a contact set does not suffer from being underloaded. They cost you panel space and lug fit, not protection, and the overload still gets set to the motor's nameplate current, never to the contactor's frame rating.

The overload relay: where it sits, and how many elements it has #

The relay does two jobs in two different circuits. Its heating or sensing elements are in series with the motor conductors; its normally closed contact is in series with the coil. That split is why the overload protects the motor but trips through the control wiring.

Count the elements. Older three-phase starters carried two, monitoring the A and C phases and leaving B unwatched. Current production carries three and watches every phase. On a balanced motor the two-element design still catches most overloads; where the phase currents differ by design — a rotary phase converter's generated leg is the classic case — a two-element relay can sit on the two quiet phases while the hot one cooks. Use a three-element overload there, or clamp each leg under load and confirm the monitored phases carry the highest currents.

Three-wire control and the seal-in contact #

A starter ships with everything a three-wire station needs: the coil, the normally closed overload contact in series with it, and a normally open auxiliary contact to parallel with the momentary start button. When the contactor closes, that auxiliary seals the circuit through itself; the stop button (normally closed, in series) or an overload trip breaks it.

A definite-purpose contactor has no such auxiliary, so a momentary start button cannot hold it in without an added auxiliary block or an interposing relay. If your scheme commands the contactor from a maintained switch or a relay contact, the seal-in path is unused and the auxiliary stays spare.

Using a starter as a contactor: three checks and a worked example #

Before any of this, lock out the disconnect, test for absence of voltage at the starter's line terminals with a meter rated for that voltage class, and replace the covers before re-energizing — NFPA 70E, 2024 edition, sets the requirements for that sequence, and they come before every check below that opens the enclosure.

Check What passes Where to read it
Horsepower rating At your supply voltage, meets or exceeds the motor horsepower Starter nameplate or size marking, manufacturer data sheet
Coil voltage Equals the control supply you will wire Coil label or coil face
Overload trip setting Set to the motor nameplate full-load current, within the code cap Adjustment dial or heater-element table on the overload relay
Overload elements Three elements on unbalanced loads Count the elements on the overload block
Seal-in contact Present for three-wire (start/stop) control Auxiliary contact block beside the coil

Worked example: a 3 HP, three-phase, 230 V, 60 Hz motor with a nameplate full-load current of 9.6 A and a service factor of 1.15, controlled at 120 V AC.

Size: a Size 1 starter covers 3 HP at 230 V with margin, so the size check passes.

Coil: the coil label reads 120 V AC and the control supply is 120 V AC, so the coil check passes. If the label read 24 V or 480 V, the fix is the correct coil from the manufacturer's coil table before anything else is wired.

Overload: NFPA 70, the National Electrical Code, 2023 edition, covers motor circuits in Article 430, and 430.32 bases overload protection on the motor nameplate full-load current — not on the code tables — capped at 125% of that current for a motor marked with a service factor of at least 1.15 or a temperature rise of 40 °C or less, and at 115% for others. For this motor, 9.6 A × 1.25 = 12.0 A. Set the dial to 9.6 A; if the dial stops fall at 9 A and 10 A, choose 10 A, still inside the 12.0 A cap. Confirm the requirement with the local authority having jurisdiction and the motor and starter documentation.

Cross-check the 9.6 A against NEC Table 430.250, which lists 9.6 A for a 3 HP, 230 V, three-phase motor; that table is the one you size conductors and branch-circuit protection from, while the nameplate stays the source for the overload. At 460 V the same motor nameplate reads 4.8 A, the dial goes to 4.8 A, and the cap becomes 4.8 A × 1.25 = 6.0 A.

Decision: the starter takes the contactor's position, and you keep the overload relay wired rather than unwiring it — that relay is the free protection the swap buys.

Reading a dropout: heat trip or control logic #

A starter that will not stay in is failing thermally or logically, and the timing tells you which before any instrument comes out.

Symptom Class Cause and first check
Trips after seconds to minutes of running; resets after a cooling pause Heat Overload trip from real overcurrent, or a setting below nameplate full-load current; clamp each phase and compare to the setting
Drops out the instant the start button is released Logic Seal-in auxiliary missing or unwired; verify the normally open auxiliary parallels the start button
Chatters, never seats Logic Coil voltage mismatch or sagging control supply; compare the coil label to the measured control voltage
Silent, no pull-in Logic Overload contact open or tripped, or no control voltage at the coil; check continuity across the overload contact with power off, then reset
Discolored lugs or insulation near the terminals Heat Loose termination, or current above the rating; torque to the marked value and re-measure
Motor runs hot, starter never trips Heat Two-element overload on the wrong phases, or setting too high; count elements and confirm the setting

Variants that need a second look #

A manual motor starter replaces the electromagnet with a lever and a mechanical latch, and its overload releases the latch. There is no coil to command, so it cannot serve a three-wire station, a timer, or a relay-driven scheme; that class is commonly used to about 1 HP single-phase and 10 HP three-phase.

A reversing starter is two mechanically interlocked three-phase contactors sold as one unit, sometimes with fewer overload elements than you would expect — count them before treating it as a single protected starter.

Some machine-tool starters tap loads off ahead of the overload section, with a coolant pump the usual one. Anything fed from such a tap gets no overload protection from that starter, and an overload trip anywhere in the string drops the one coil through the shared three-wire station.

Questions asked

Can I use a motor starter in place of a contactor in my schematic?

Yes, when three things pass: the horsepower rating at your supply voltage meets the load, the coil voltage matches the control supply, and the overload relay's normally closed contact stays in series with the coil with the trip current set to the motor's nameplate full-load current. The starter then adds thermal protection a bare contactor never had. Never jumper the overload contact closed to force a pull-in; find out why it is open instead.

Should the overload dial follow the nameplate amps or the code table value?

The nameplate. NFPA 70, 2023 edition, Article 430.32 sizes overload protection from the motor nameplate full-load current, while the table full-load currents (Table 430.250 for three-phase motors) are the values you size conductors and branch-circuit protection from. A 3 HP, 230 V motor shows 9.6 A in the table; if the nameplate agrees, set 9.6 A, and the cap for a 1.15 service-factor motor is 12.0 A.

Why does my older three-phase starter have only two overload heaters?

Older designs put elements in the A and C phases and left B unmonitored, which works on a balanced motor and goes blind when phase currents differ by design. That design should not be trusted on a load whose phase currents differ by design, such as one fed from a rotary phase converter: use a three-element overload there instead.

The contactor drops out the instant I release Start. Is it faulty?

No, that is missing seal-in, not a failed coil. A normally open auxiliary contact must sit in parallel with the momentary start button so the coil keeps its path after the button returns. Add an auxiliary block, or command the coil from a maintained switch or a relay contact instead, and the dropout disappears.

Is a manual motor starter a substitute for a magnetic one?

Not where anything remote commands the motor. A manual starter replaces the electromagnet with a lever and a mechanical latch, and its overload releases the latch — there is no coil for a pushbutton station, timer, or relay to energize. That class is commonly used up to about 1 HP single-phase and 10 HP three-phase, so it stays a local, hand-operated device.

Keep reading

  • How-to

    Wiring a three-phase coolant pump starter from a 120 V signal

    Run the machine's 120 V coolant output through the overload relay's normally closed contact to a contactor with a 120 VAC coil, and set the overload dial to the pump's nameplate full-load current — 1.8 A on a typical 1/2 HP three-phase pump, inside a 1.3–2.1 A adjustable range. Then bump-test rotation and swap any two motor leads if the pump runs backward.

    Motors and motor starters

  • How-to

    Fixing voltage drop on a long 277 V lighting feeder

    The drop budget on this feeder limits the loop to 0.40 Ω — 0.267 Ω per conductor — so size up the copper or split the load across the three phases of the wye system, which relaxes the limit sixfold. Raise the source only after the two-endpoint check, because a fixed boost that fixes full-load voltage also overvoltages the panel at light load.