Short answer

The nameplate works out to 20.8 kVA of apparent power. Fed from the single-phase shop service, that is about 87 A before converter and transformer losses, so the machine needs a rotary phase converter sized to its total demand plus a reverse-connected step-down transformer, unless tracing shows the internals run on 200 to 220 V. Verify loaded voltage balance before releasing the machine to production.

On this page
  1. Correct the nameplate math first
  2. Lock it out, then trace the input chain
  3. Worked example: supplying the lathe from single phase
  4. Choose the architecture on what the trace found
  5. Back-feeding the step-down transformer
  6. Commission under load, never at idle
  7. Grounding, labelling and the code check
  8. Questions asked

Your machine's nameplate works out to 20.8 kVA of apparent power. Pulled from the single-phase shop service, that same demand is about 87 A before the first converter or transformer loss is counted. So the job has a fixed order: lock the machine out and trace what its cabinet actually runs on, then either feed it three-phase at the service voltage from a rotary converter sized to the whole machine, or hang a reverse-connected step-down transformer on the converter output. The math, the sizing decisions and the loaded checks that close the job follow.

Correct the nameplate math first #

Multiplying the nameplate voltage by the nameplate current and calling the result 12 kW is wrong twice. It drops the root-three factor that three-phase apparent power carries, and it treats volt-amperes as watts. The nameplate states line-to-line voltage and line current, which define apparent power only; real power would need power factor and efficiency, and the label gives neither. Note also that the stated current is the maximum input rating, so the machine's everyday draw sits below it, which matters when you verify the installation, not when you size it. Size on kVA; the arithmetic is in the worked example below.

Lock it out, then trace the input chain #

Open that cabinet only after lockout at the machine disconnect and a verified absence of voltage: the machine transformer is energized from the line side, and drive DC bus capacitors hold charge after the disconnect opens. With the machine dead, record, in this order:

  1. The external nameplate, the disconnect rating, and the incoming conductor, fuse and contactor sizes.
  2. The machine transformer nameplate: every primary and secondary tap voltage, and the strap position actually connected.
  3. Each secondary branch and its input rating: spindle drive, servo drives, hydraulic power unit, coolant and lubrication pumps, control transformer.
  4. The machine schematic, with point-to-point confirmation anywhere the drawing is missing or contradicts the straps.

One lathe of this class, opened and documented, shows why this trace decides everything downstream:

Documented finding What it tells you
Input label matches the external nameplate, three-phase The configured machine input, not the voltage of each internal load
Machine transformer primary taps 575/480 V The input transformer accepts either high-voltage connection
Secondary taps 220/200 V Internal distribution voltage is set by strap position
Strapped 575 V in, 200 V out The machine ran internally on 200 V in that configuration
Manual lists auxiliary motors at 220 V The gap between motor rating and strapped secondary must be closed by the schematic before the service voltage is applied

Do not bypass or re-strap that transformer just because the motors are marked 220 V. Contactor coils, drive front ends and the control transformer have their own requirements, and the 200 V strapped secondary against 220 V motors is exactly the discrepancy the schematic must settle.

Worked example: supplying the lathe from single phase #

Inputs:

  • Line-to-line voltage: 600 V, from the machine nameplate.
  • Line current: 20 A, the nameplate maximum input rating.
  • Available source: 240 V, single phase, shop service.
  • Converter output: three phase, at the service voltage.

Rule in words: three-phase apparent power is root-three times the line-to-line voltage times the line current, divided by 1000 to get kVA. Current at any voltage is kVA times 1000 divided by that voltage, with root-three also in the denominator on a three-phase line.

Arithmetic, with the inputs above substituted:

S = √3 × V × I / 1000 = 20.78 kVA

Single-phase input from the shop:

I = S × 1000 / V = 86.6 A at the service voltage

Converter output side:

I = S × 1000 / (√3 × V) = 50.0 A per line

Both currents are ideal floors: converter and transformer losses, plus the imbalance of the manufactured leg, push the single-phase draw above 86.6 A.

Decisions from these numbers:

  • Size the rotary converter to the machine's total demand: at least 20.8 kVA, a 50 A three-phase output class. A CNC's electronic drives swing the load from idle to full within one program, so the largest-motor shortcut does not apply.
  • Plan a dedicated 100 A branch at the service voltage for the converter. 86.6 A ideal plus losses and imbalance leaves no margin in a 90 A circuit, and 100 A is the next standard size up. Final conductor and overcurrent sizing follows the converter's listed input rating under NFPA 70, the National Electrical Code (2023 edition), which governs branch circuits in the US; confirm the requirement with the local authority having jurisdiction.
  • At this current the run from the panel is a voltage-drop design item, not an afterthought; the method is the same as fixing voltage drop on a long 277 V lighting feeder, applied at roughly four times the current of a typical small branch.
  • After the first full-load cut, clamp the single-phase input and write the number down. The nameplate current is a maximum, so the measured current sets the machine's real operating point in your shop.

Choose the architecture on what the trace found #

  1. Internals rated 200 or 220 V, the common case for machines of this class: run the rotary converter's three-phase output straight into the machine, with the internal transformer bypassed or re-strapped exactly as the schematic allows. Do not generate the high voltage only to transform it back down; every conversion stage adds loss and one more thing to balance.
  2. Machine genuinely requires 575 V input: converter into a reverse-connected three-phase step-down transformer of the matching ratio, 30 kVA class, the next standard size above the demand calculated above.
  3. One variable-frequency drive as a whole-machine supply: no. A drive listed for one motor is not rated to feed a cabinet of drives, coils and its own machine transformer. Only written approval from the drive and machine manufacturers, with the input derating and output filtering they specify, makes that architecture defensible.
  4. Static phase converter: no for this machine. It drops its start circuit after spin-up and runs the load partially single-phase, and a spindle drive under varying load will fault on it.

On a motor-only installation you can sometimes size a rotary converter around the largest directly connected motor, because the other running motors help the generated leg. A CNC removes that help: its spindle and servo drives rectify the line instead of spinning on it. Size to total demand and let the loaded balance test below decide whether the choice holds.

Back-feeding the step-down transformer #

A step-down transformer run backwards is the practical way to obtain the high voltage, because the downward winding direction is the common one offered. Two behaviors govern the back-fed connection. Manufacturers advise that the reverse-connected output runs below the nameplate ratio, because winding compensation is designed for the forward direction; the nameplate voltage can land in the 570s on load, which is also the 575 V Canadian service voltage this machine class is built for, and the nameplate taps pull it back up. And the unit must be three-phase: a single-phase back-fed transformer has powered single-phase loads such as a tap disintegrator, but a lathe spindle needs all three lines.

Before buying any used unit, check its winding markings and connection diagram against the manufacturer's documentation; that documentation tells you whether the specific transformer may be reversed at all.

Commission under load, never at idle #

  1. Before energizing anything, confirm phase rotation against the machine's requirement, and confirm the bonding and grounding of the transformer's derived system per its nameplate and NFPA 70 (2023 edition).
  2. Energize the controls with no motion commanded, and verify each internal transformer secondary and control-supply input against its documented rating.
  3. Run the auxiliary loads, hydraulic unit, coolant and lubrication, one at a time, then together, recording all three phase-to-phase voltages at each step.
  4. Accelerate the spindle and take a heavy cut. Watch for drive undervoltage faults, clamp the single-phase input for peak current, and record it.
  5. After an hour of cycling, check the back-fed transformer's temperature; the acceptance logic is the same as evaluating dry-type transformer hot-spot temperature rise against its insulation class.
  6. Hold the loaded voltage spread at the machine to 1% unbalance, about 6 V phase-to-phase at this voltage. Unbalance is 100 times the largest deviation from the mean of the three phase-to-phase readings, divided by that mean. NEMA MG 1 (2021 edition), the US motor standard, treats 1% as the level motors are built for and requires derating above it; a wider spread under load is a converter balance or sizing problem, so fix it before the machine goes into production.

Grounding, labelling and the code check #

The transformer's high-voltage winding is a separately derived system: its system bonding jumper, grounding electrode connection and labelling follow the transformer nameplate and NFPA 70, the National Electrical Code (2023 edition), in US jurisdictions, and requirements differ by country and local amendment, so confirm them with the authority having jurisdiction and the equipment documentation. And that voltage is not exotic: it is the standard Canadian industrial utilization voltage at 60 Hz, which is why this machine exists and why the step-down unit you need is the common one to find.

Questions asked

Why is the nameplate volts times amps not 12 kW?

Two errors combine in that shortcut. Three-phase apparent power carries a root-three factor, so 600 V times 20 A is not the whole story, and volt-amperes are not watts: real power would need power factor and efficiency, which the label does not state. The correct figure is the square root of three times 600 V times 20 A divided by 1000, or about 20.8 kVA. Size the converter and transformer on that kVA number, not on a wattage guess.

Can I run the motors off a phase converter and rectify single-phase 240 V for the controls?

You can, but only after the trace inside the cabinet confirms what each branch actually needs. The control transformer, contactor coils and any drive front ends have their own voltage requirements, and the machine transformer's strap position sets the internal distribution voltage. Feed the converter's three-phase output into the machine as the schematic allows rather than splitting the supply, unless the documentation clearly supports separating the control power.

Will a step-up transformer to 480 V work instead?

No, if the machine genuinely requires its 575 V class input. A 480 V secondary leaves the spindle and drives well below the voltage the cabinet was built and strapped for, and undervoltage faults under load are the likely result. If the internal trace shows the machine runs on 200 or 220 V internally, the better answer is to feed the converter output straight in at the service voltage and skip generating the high voltage at all.

What voltage will a back-fed step-down transformer actually give?

Manufacturers advise that a reverse-connected step-down transformer delivers slightly below its nameplate ratio, because winding compensation is designed for the forward direction. On load, the output can land in the 570 V range, which sits close to the 575 V service voltage this machine class is built for, and the nameplate taps let you pull the voltage back up. Measure the loaded voltage at the machine before releasing it to production.

Can a 200 A shop service handle this machine?

On paper yes: the ideal single-phase draw is 86.6 A, and converter and transformer losses plus the imbalance of the manufactured leg push it somewhat higher, still well inside a 200 A service. But that is capacity, not a branch circuit. Plan a dedicated 100 A branch at the service voltage for the converter, sized finally on its listed input rating under NFPA 70, the National Electrical Code, 2023 edition, and confirmed with your local authority having jurisdiction.

Keep reading

  • How-to

    Fixing voltage drop on a long 277 V lighting feeder

    The drop budget on this feeder limits the loop to 0.40 Ω — 0.267 Ω per conductor — so size up the copper or split the load across the three phases of the wye system, which relaxes the limit sixfold. Raise the source only after the two-endpoint check, because a fixed boost that fixes full-load voltage also overvoltages the panel at light load.

    Power distribution and transformers

  • How-to

    Wiring a three-phase coolant pump starter from a 120 V signal

    Run the machine's 120 V coolant output through the overload relay's normally closed contact to a contactor with a 120 VAC coil, and set the overload dial to the pump's nameplate full-load current — 1.8 A on a typical 1/2 HP three-phase pump, inside a 1.3–2.1 A adjustable range. Then bump-test rotation and swap any two motor leads if the pump runs backward.

    Motors and motor starters

  • Explainer

    Evaluating dry-type transformer hot spot temperature rise

    A 128.2°C average winding rise proves only the average, not the hot spot: the resistance method and a point RTD measure different quantities, so the 219°C combination is invalid. The 202.6°C full-load reading is a 180.8°C local rise, which projects to 220.8°C at the 40°C rating ambient and exceeds the 180°C hot-spot rise a class 220 system allows. Decision: run the simultaneous full-voltage, full-load heat run.

    Power distribution and transformers