Selection guide
Selecting overload and jam protection for a reversible motor
Short answer
Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.
On this page
- Two jobs, two devices
- What the overload relay is set from
- Why wattage cannot set the overload
- Setting the jam relay that acts as the clutch
- Reset delay, auto reset and the cycle timer
- Wiring, interlocks and reversing
- Selection table
- Worked example: 240 V motor, nameplate FLA 4.0 A
- Verification before handover
- Questions asked
A reversible 240 V, 500 W motor that has to trip like an electronic clutch needs two devices, not one clever overload. Set a standard bimetallic or electronic overload relay from the motor's nameplate full-load current (FLA) to protect the windings from accumulated heat, and add a current-sensing jam, shock-load or electronic-shear-pin relay to make the fast trip the machine wants. That second relay carries the adjustable reset delay, set so the cycle timer always removes the run command before a reset can reissue motion. Set nothing from the wattage: 500 W ÷ 240 V = 2.08 A only in the ideal case of unity power factor and perfect efficiency, roughly half of what a real 500 W output motor draws.
Two jobs, two devices #
In motor language, an overload is one specific thing: thermal protection of the winding, with the relay operating on the accumulated heating effect of current, approximately current squared integrated over time (I²t). Doubling the current quadruples the resistive heating rate. An overload trip stops further heating, but the stored heat stays in the windings, and the relay's auto reset recloses its contact when its own element cools — elapsed time, not a winding temperature measurement.
The behavior you want — stall or shock load, a fast control reaction, then a delayed retry — is jam or shock-load detection. The product categories that do it are current-sensing relays, jam relays, shock-load relays and electronic shear pin relays; full motor protection relays carry the same function as a load-jam element (the SEL-710 documents load-jam protection that trips the motor quickly on stall). These devices typically provide a start bypass, an adjustable trip delay, an adjustable or latched reset, and an isolated contact for the control circuit.
The decision: keep both. The overload protects the motor. The jam relay is the electronic clutch.
What the overload relay is set from #
NFPA 70, the National Electrical Code (2023 edition), governs motor circuits in Article 430. Its full-load-current tables are the basis for conductor sizing and branch-circuit short-circuit and ground-fault protection, but overload elements are set from the motor nameplate full-load current; the table value and the nameplate value are not interchangeable. The Code caps the setting at 125 percent of nameplate full-load current for motors marked with a service factor of 1.15 or greater, or a temperature rise not over 40 °C, and 115 percent for other motors.
On a 1.15-service-factor motor, put the dial at the nameplate FLA and treat the 125 percent figure as a ceiling for nuisance-trip headroom, not as a target. Confirm the requirement with the local authority having jurisdiction and with the motor and relay documentation.
Why wattage cannot set the overload #
The 500 W and 240 V on the job sheet do not determine the setting. If 500 W were single-phase electrical input at unity power factor, I = P / V = 500 W / 240 V = 2.08 A — a labeled ideal case only. A 500 W mechanical-output single-phase motor draws I = Pout / (V × PF × η); with power factor 0.75 and efficiency 0.70, I = 500 / (240 × 0.75 × 0.70) = 500 / 126 = 3.97 ≈ 4.0 A, nearly double.
Set an overload to 2.1 A on that motor and it nuisance-trips on every start; raise it until it runs and you have abandoned the nameplate basis the Code uses. Read rated current, voltage, frequency and duty from the nameplate.
Setting the jam relay that acts as the clutch #
Measure current through complete healthy cycles in both directions with a clamp or recording meter: the acceleration peak and its duration, the loaded running current, and the worst repeatable process peak. Then establish the jam current — a stalled rotor slows, slip rises, and the motor pulls toward locked-rotor current, several times nameplate FLA, well above anything healthy.
Set the trip threshold between those two measurements with margin on both sides: at least 20 percent above the worst normal process peak, and no more than half the jammed-mechanism current. Set the start bypass just longer than the measured acceleration, so inrush does not trip the relay but a jam that persists after the machine should be moving does. Keep the trip delay short enough that the jam is cleared before the mechanism or the motor suffers, and prove it with the test in the verification section.
Reset delay, auto reset and the cycle timer #
The reset delay is the coordination point: it must be longer than the worst-case time the cycle timer takes to remove the run command after a trip. Measure that drop-out time and set the reset delay to at least twice it. Auto reset with the run command still present restarts the motor by itself the moment the delay expires; NFPA 79, the Electrical Standard for Industrial Machinery (2024 edition), covers the electrical equipment of machines, including the control circuits that govern restarting, so where unexpected motion could injure, latch the fault and require a deliberate restart.
A thermal overload trip is a different case. Even after the relay's contact resets, the motor must cool to an acceptable condition before a restart; a delay is not a temperature measurement, and no timer setting proves the windings are ready.
Wiring, interlocks and reversing #
Lock out the supply, de-energize and test for absence of voltage before opening the starter panel or the motor terminal box for any of this work. Use the relays' isolated control contacts to interrupt the contactor coil circuit, and never switch motor current through a sensor output that is not rated for it. Forward and reverse contactors need electrical and mechanical interlocking so the two directions cannot energize together; compact reversing contactors have matching clip-on bimetallic overload relays, the 193-K series for 100-K and 104-K miniature contactors among them.
Reversing to clear a jam stacks a forward stall and a reverse acceleration with little cooling between them, and it hammers contactors, couplings and gearing. Check the permitted number of starts and reversals against the motor manufacturer's data, and keep the reversal logic in the machine-control chain where the risk assessment can see it.
Selection table #
Settings shown are the worked example's, for a 240 V motor with nameplate FLA 4.0 A.
| Function | Device | Set from | Example setting | Response |
|---|---|---|---|---|
| Winding thermal protection | Bimetallic or electronic overload relay | Nameplate FLA; 125% ceiling at SF 1.15 or 40 °C rise, 115% otherwise | Dial at 4.0 A | I²t trip; reset follows relay cooling, not the cycle |
| Electronic clutch | Current-sensing jam, shock-load or electronic shear pin relay | Measured healthy-cycle peak versus jam current | Threshold 8.0 A, trip delay 0.5 s, start bypass 2.0 s | Drops the run command about 0.5 s after the bypass expires |
| Restart coordination | Reset delay on the jam relay | Measured cycle-timer drop-out time | 10 s against a 5 s drop-out | Motor restarts only after the timer removed the run command |
| Directional protection | Forward and reverse contactors with electrical and mechanical interlocks | Control-circuit design | Interlocked coils and actuator blocks | No simultaneous opposing commands |
Worked example: 240 V motor, nameplate FLA 4.0 A #
Illustrative inputs, a hypothetical machine with these values: single-phase 240 V motor, nameplate FLA 4.0 A, service factor 1.15. Measured healthy cycle: 12 A for 1.5 s accelerating, 4.2 A loaded running, worst normal process peak 6.5 A for 0.8 s. Jammed-mechanism current 19 A sustained. Cycle timer removes the run command within 5 s of the trip.
- Overload relay: dial at 4.0 A, the nameplate FLA, inside the 4.0 A × 1.25 = 5.0 A ceiling. The 12 A start is 3.0× the setting for 1.5 s, which a Class 10 overload characteristic rides through easily; verify on the relay's published trip curve.
- Jam relay: threshold 8.0 A, which is 1.23× the 6.5 A process peak and 0.42× the 19 A jam current. Start bypass 2.0 s, covering the 1.5 s acceleration; trip delay 0.5 s, so the run command drops about half a second after the bypass window, at 19 A — 4.75× the overload setting, where the thermal device takes far longer.
- Reset delay: 2 × 5 s = 10 s, so the timer has dropped the run command long before the relay recloses.
The decision for this machine: overload at 4.0 A, jam relay at 8.0 A with a 2.0 s bypass and 0.5 s trip delay, 10 s reset delay, interlocked reversing contactors, and a latched restart if the machine can hurt someone.
Verification before handover #
- Run the worst normal cycle in both directions and record current against time: no trip anywhere in the cycle.
- Prove the jam response with a controlled method approved for the machine, not a destructive hard stall, and hold the initiating command during the test to expose exactly what the auto reset does.
- Confirm the jam trip removes the active run command, the timer cancels the pending restart, both interlocks block simultaneous direction commands, and the reversing sequence follows the design.
- Test loss and restoration of control power, then record the final settings on the panel documentation.
Questions asked
Can I set the overload from the motor's 500 W rating?
No. 500 W divided by 240 V is 2.08 A only at unity power factor and 100 percent efficiency, and only if 500 W is electrical input. A 500 W mechanical-output motor with, for example, 0.75 power factor and 0.70 efficiency draws 500 / (240 × 0.75 × 0.70) = about 4.0 A, nearly double. An overload set to 2.1 A on that motor nuisance-trips on every start, so use the nameplate full-load current.
Why not let the thermal overload relay act as the clutch?
An overload relay models winding heating and integrates squared current over time, so it trips after heat accumulates and resets when its own element cools, on no schedule you control. A current-sensing jam or shock relay measures current magnitude, trips on a threshold within a fraction of a second, and gives you the adjustable reset delay you need to coordinate with the cycle timer.
How do I set the jam relay threshold and its delays?
Measure a complete healthy cycle in both directions, then find the jammed-mechanism current. Set the threshold at least 20 percent above the worst normal process peak and no more than half the jam current. Set the start bypass just longer than the measured acceleration time, and keep the trip delay short enough that the jam is cleared before the motor or mechanism is damaged.
How long should the adjustable reset delay be?
Longer than the worst-case time the cycle timer needs to remove the run command. Measure that drop-out time — for example 5 s — and set the reset delay to at least twice it, 10 s in that case. If the run command is still present when the delay expires, the motor restarts by itself, so latch the fault and demand a deliberate restart wherever motion could injure.
Is auto reset acceptable on a reversing motor?
Only where an uncommanded restart cannot injure anyone or damage the machine, and only with the cycle timer proven to drop the run command before the delay expires. Otherwise latch the trip and restart from a deliberate action. Remember that reversing to clear a jam stacks two heating events with little cooling between them, and it wears contactors, couplings and gearing.
Do the NEC full-load-current tables set the overload?
No. The Article 430 tables in NFPA 70, the National Electrical Code (2023 edition), feed conductor sizing and branch-circuit short-circuit and ground-fault protection. Overload elements are set from the motor nameplate full-load current, capped at 125 percent of it for service factor 1.15 or greater, or a 40 °C temperature-rise marking, and 115 percent otherwise. Confirm the limit with your authority having jurisdiction.