Selection guide
What plugging duty does to reversing contactor sizing
Short answer
Plugging (reverse-current braking) is AC-4 duty: the reversing contactors make roughly locked-rotor current while the motor still spins forward, so you must select them from the manufacturer's AC-4 plugging ratings, not the horsepower label. Work through a 25 hp, 460 V mixer example, then set the manual motor starter overload from the motor nameplate current.

On this page
Size the reversing contactors from the manufacturer's AC-4 (plugging) ratings at your voltage, and set the manual motor starter overload from the motor nameplate full-load current. Horsepower labels, informal oversizing multipliers, and "a starter big enough for 40 hp" do not test what plugging actually asks of the contacts. Here is what plugging does electrically, how IEC and NEMA data differ, and a worked example for a 25 hp, 460 V mixer.
Why plugging is the hardest duty on the contacts #
During plugging, the stop command energizes the reverse contactor while the rotor still spins forward. The stator field reverses, the torque reverses, and the motor brakes. Until the zero-speed switch removes reverse voltage, the circuit carries current close to the motor's locked-rotor current, because the counter-voltage now adds to the supply instead of opposing it. For a NEMA design B squirrel-cage motor that means roughly six to eight times full-load current, flowing through a contactor that was not designed to make that current every cycle.
The make is the punishing event, not just the current: the contacts close on an asymmetric peak with high arc energy, and at zero speed they must interrupt current in a circuit whose impedance is lower than a normal running circuit. Every plugging stop repeats that make-and-break. A contactor rated only for ordinary starting will erode contacts and weld poles in short order under repeated plugging.
IEC 60947-4-1 and UL 60947-4-1 define the utilization categories that describe this. AC-3 covers squirrel-cage starting and running; AC-4 covers squirrel-cage starting, plugging, and inching. Don't read AC-3 as "normal duty" and AC-4 as "heavy duty" marketing labels: they are different test conditions, and AC-4 testing is the one that resembles plugging. IEC contactor selection for mixed duty is based on the percentage that plugging and inching operations represent of the total duty cycle against the AC-3 and AC-4 ratings, so the published AC-4 rated operational current at your supply voltage is the number to size against.
The zero-speed switch defines when the duty ends. It must detect zero speed and drop the reverse contactor before the motor accelerates backward, otherwise the system becomes an uncontrolled reverse start that holds plugging current indefinitely. Prove the interlocks (mechanical and electrical between the two contactors), the zero-speed trip point, and the stop logic before you blame component ratings for a failure. Two reversing contactors with interlocks are the standard arrangement for this, as covered in why reversing a three-phase motor needs two contactors, and a weak contactor coil or interlock problem produces symptoms that look like duty failures, as covered in why a motor starter coil has voltage but won't pull in.
Three ways people size this, and which one is right #
| Approach | What it tests | Where it fails in plugging service |
|---|---|---|
| Horsepower label only | Contactor capacity under the conditions the data sheet states | A 40 hp AC-3 rating says nothing about AC-4 make current or operations per hour |
| Informal multiplier | Nothing | No documented multiplier exists for plugging; oversizing doesn't prove thermal endurance or coordination |
| Manufacturer AC-4 table at your voltage | Make and break capability under the actual plugging duty, against your motor's locked-rotor current and operations per hour | Requires real motor nameplate data and the exact model's AC-4 table; that is the work |
Use the third approach. Compare the old and replacement devices on their published ratings, not on frame size or nominal horsepower: an IEC manual motor starter matched to the original BOM can differ in thermal range, magnetic trip range, and coordination data from the NEMA device it replaced, even when both claim the same motor size. If the switching frequency is high or the AC-4 rating of any candidate is marginal for the duty cycle, the documented IEC method is to apply the duty-cycle percentage between the AC-3 and AC-4 ratings from the manufacturer's application data.
Sizing the contactors and MMS for a 25 hp mixer #
This example works the mixer case: 25 hp, 460 V, three phase, plugging to stop about once per hour, zero-speed switch terminating the reverse interval. Confirm your own machine's stop count from operation records before sizing; the once-per-hour figure here is the assumed cycle rate.
Inputs and where they come from. Horsepower from the motor: 25 hp, three phase, at the supply voltage stated above. Full-load current from the NEC motor tables: NFPA 70 (National Electrical Code, 2023 edition), Table 430.250 lists 34 A for a 25 hp, 460 V, three-phase motor. That table value is an estimate for sizing; the nameplate full-load current governs the actual overload setting per NEC 430.6. Locked-rotor current: estimate seven times full-load current as a design B midpoint and verify against the nameplate code letter and the motor data sheet.
The rule in words. Both the forward and the reverse contactor must have a published AC-4 rated operational current at 460 V that exceeds the motor's plugging current, with endurance (permitted operations) covering your plugging stops per hour over the contactor's service life. The manual motor starter's thermal element must be settable to the nameplate full-load current, and its magnetic element must sit above the peak plugging current without tripping on every stop.
The arithmetic.
- Full-load current (table estimate): 34 A.
- Plugging current, estimated at seven times full-load current: 7 × 34 A = 238 A.
- Both contactors see this: the reverse contactor makes it when the stop command fires, and the forward contactor must be able to break it if the interlock or stop logic opens it mid-braking. Neither contactor can be sized smaller than the other.
- MMS thermal setting: nameplate full-load current. If the nameplate reads 32 A, the thermal element adjusts to cover 32 A; the 34 A table value is only the sizing cross-check.
- MMS magnetic element: must be above the 238 A plugging peak, and low enough to clear a genuine short circuit. Check that 238 A sits inside the starter's magnetic adjustment range; if the locked-rotor estimate from the nameplate code letter comes out higher, say nine times 34 A = 306 A, the magnetic range must still contain it.
The result and the decision. Select contactors whose AC-4 table entry at the supply voltage is rated for at least 238 A (verify against the actual code letter before ordering) and whose AC-4 endurance covers the operations-per-hour of the mixer duty, both contactors sized identically with mechanical plus electrical interlocks. Select a manual motor starter whose thermal range covers the nameplate current and whose magnetic range contains the plugging peak, with published Type 1 (and Type 2 where the process needs it) coordination with those contactors. If no candidate meets the AC-4 endurance at the actual stop rate, the documented options are a larger AC-4-rated contactor or the manufacturer's duty-cycle method between AC-3 and AC-4 ratings — not an informal multiplier.
The result is an estimate until checked against the motor data sheet, the contactor's own AC-4 table, and the governing code edition with your authority having jurisdiction.
What a field failure is telling you #
Soot around the manual motor starter and both contactors proves an energetic fault occurred, not which device failed first. A single failing device can coat its neighbors; several visibly damaged components can mean one fault cascaded through all of them. Before changing any rating, identify damage on each device and reconstruct the event: contact erosion or welds point to switching duty beyond the rating; starter damage or nuisance trips point to thermal range, magnetic range, or coordination; damage across all three devices points to a fault current, a wiring error, or a sequence problem. Also check control voltage during pickup and sealing-in, because a contactor that chatters makes and breaks plugging current repeatedly and destroys itself under a rating that would otherwise hold. A contactor that repeatedly interrupts high current on one pole, as covered in why only one contactor pole burns on a small motor, shows the same physics as plugging concentrated on the weakest contact.
One safety note: de-energize the mixer circuit, lock out, and test for absence of voltage with a proven instrument before opening the panel or inspecting any of these components.
Set the protection functions independently of the contactor duty #
Overload protection and contactor duty rating answer different questions. The manual motor starter protects the motor; it must be selected and set from the nameplate current and the protection scheme, including its adjustable range and its coordination data with the contactors. The contactors make and break the plugging current; they are selected from AC-4 data. The panel-cover disconnect requirement that often drives the choice of a manual motor starter does not change either selection. Never use the contactor's horsepower rating as evidence that the protective functions are correct, and never let a protective device's presence stand in for an AC-4 endurance check.
If the mixer's stopping logic cannot change — as is often the case where a machine must stop within a set distance for safety — the contactors, the starter, the interlocks, and the zero-speed switch all have to be proven as one system against that fixed duty. Sizing is the first step; proving the delivered duty cycle is the one that keeps the replacement from failing the same way.
Questions asked
Why can't I just pick a contactor one size up from the horsepower table for plugging?
The horsepower label describes AC-3 duty: making a stopped motor and interrupting running current. Plugging is AC-4 duty: the contactor closes into reverse voltage while the rotor still spins forward, so the make current approaches locked-rotor current and the contacts must break current at near-zero speed with high arc energy. A horsepower guess doesn't test either of those limits; the manufacturer's AC-4 table, expressed as rated operational current at your voltage, does.
Does the manual motor starter need a special plugging rating too?
The starter's thermal element is set from the motor nameplate full-load current, and its magnetic element must be above the peak plugging current, so check that the plugging current estimate stays inside the magnetic adjustment range. What the starter never does is make or break the plugging current: the contactors do that. Compare the old and replacement starters' thermal range, magnetic range, and published coordination with the contactors, because an IEC device rated to the same horsepower is not automatically the same device in those three respects.
What happens if the zero-speed switch fails to open the reverse contactor?
The motor accelerates in reverse at plugging current indefinitely, which is an uncontrolled reverse start, not a stop. That is a control fault, distinct from contact wear under correctly terminated plugging, but it loads the contactor the same way. The interlocks, the zero-speed switch, and the stop logic must be proven as part of the design, because the contactor ratings only cover the duty cycle the logic actually delivers.