Why a pad-mount transformer tank gets hot between bushings
Short answer
A confirmed hot spot on the tank between secondary bushings is eddy-current and hysteresis heating in the steel hardware there, driven by thousands of amps in the bushing leads — not a sign the core ground failed. Verify the reading for emissivity error, then escalate with nameplate, load and scan data; never grind, weld or bond the pad on your own theory.

On this page
A hot spot on the tank right between the secondary bushings is not a mystery to park until it fails. That location sits in the strongest leakage field the transformer makes: the two secondary leads carry the full low-voltage current a few inches apart, and the alternating field between them drives eddy currents and hysteresis loss into any magnetic steel plate or insert sitting in that path. When the scan also shows paint peeled back from the steel there, you are looking at defect-level heating — not a camera artifact, and not evidence that the core ground failed. Work it in this order: prove the reading is real, leave the pad untouched, put load numbers behind the pattern, and get the manufacturer to identify the hardware in writing.
Where the heat comes from #
The plate between two bushing leads sits inside their field. Each lead carries a large alternating current, the fields of the two leads add between them, and that leakage flux passes through whatever steel is in the way. Magnetic carbon steel accepts the flux readily and then pays for it twice: eddy currents induced in the plate dissipate heat, and the magnetic domains reverse every half-cycle and add hysteresis loss. The heat lands exactly where the steel sits between the leads, which is exactly where the scan shows it.
Transformer designers plan for this. Eliminating hot spots and cutting eddy losses in bushing mounting plates is a stated design consideration for pad-mounted units, and the standard countermeasures are nonmagnetic material — stainless steel inserts or aluminum mounting plates — or flux shields that counteract the leakage field before it reaches the tank steel. The bushing itself insulates the current-carrying conductor from the tank; the hardware around it is what collects the loss, and tank walls and covers in high-current regions behave the same way. When a magnetic-steel pad or a plate added in the field sits between high-current bushings instead of the nonmagnetic insert the design intends, that pad becomes the heater.
Judging the tank says nothing about winding temperatures. Surface heating and winding hot-spot rise are separate evaluations with separate methods, and evaluating dry-type transformer hot spot temperature rise covers the rise calculation on that side of the machine.
Ruling the pad in or out as a core-ground point #
A threaded pad with holes between bushings invites a guess: core-ground point? Position cannot settle electrical function. A factory pad in that spot can be a mounting boss, a lifting fixture, a grounding feature or something else, and nothing about its location tells you which.
The unit is already case-grounded at the base pad, so safety does not wait on this answer. What matters is that you do not act on a guess. If the pad ties to the core, adding a second bond creates a second core-ground path, and an unintended second core ground can circulate current and generate its own heating — the exact problem under investigation, made worse. If the pad is a plain boss, a bond adds nothing except a connection someone later has to explain.
Get the function in writing. Send the manufacturer the complete nameplate and serial number with photographs of both pads — the one between the secondary bushings and its twin between the primary bushings — and ask what each pad is and which connection instruction applies. If they identify a pad as a grounding point, follow their specified method for that exact unit. Until the answer arrives, treat it as unknown hardware: no bond, no test jumper, no grinding.
Prove the hot spot before you report it #
An infrared camera infers surface temperature from emitted and reflected radiation, and a peeling-paint patch mixes surface types: painted steel reads close to its true temperature, while bare or shiny steel reads low and mirrors hotter objects nearby. Pin the reading down before it reaches a report.
- Repeat the scan from a second angle and position. If the hot area slides with the viewing angle, you are reading reflected radiation, not generated heat.
- Set the camera emissivity for the actual surface, and record the setting, the distance and the spot size with the scan.
- Compare like with like: same load, same ambient, same distance, and the same pad locations on a sister unit carrying similar load.
- Record what the pattern is centered on — the pad itself, a bushing gasket line, a connection, or a broad halo — and whether it swells with load.
- Confirm with a second method only where the documented procedure permits it, and never touch the tank or the pad to check by hand.
The scan runs with the unit energized and loaded, next to medium-voltage equipment. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers the shock and arc-flash protection requirements for work near energized equipment, including the boundary between people and exposed energized parts; confirm the requirement that applies to your site with the authority having jurisdiction and the equipment documentation. Stay outside the boundary on the unit's label for the whole scan — how those labels get their values at a transformer secondary is its own subject, covered in transformer secondary and switchboard line side arc flash labels.
| What you see | What it points to | Next step |
|---|---|---|
| Hot area shifts with viewing angle | Reflection or emissivity error | Correct the measurement and rescan before reporting |
| Confirmed heat centered on the pad | Loss heating in or around that hardware | Escalate with nameplate, load and scan data |
| Heat centered on a bushing gasket or connection | That component's own problem | Follow the manufacturer's inspection guidance for it |
| Same pattern on several sister units | Possible common design or installation issue | Report all serial numbers and matching scans together |
Working the numbers for a 997 kVA, 7200/277 V unit showing 300 °F #
Inputs, with their sources:
- 997 kVA, single phase — the nameplate rating of the reported field case.
- 7,200 V primary and 277 V secondary — the nameplate voltages of that case.
- 300 °F — the field-reported infrared reading between the secondary bushings; a reported symptom until the checks above confirm it.
- Half load — an example assumption for the part-load check, stated as such.
The rules, in words: for a single-phase transformer, full-load apparent power divided by voltage gives the line current, I = S/V. Temperature converts between the scales as °C = (°F - 32) × 5/9. Stray loss in steel carrying leakage flux rises roughly with the square of the current producing the flux.
The arithmetic:
- Secondary full-load current: 997,000 VA ÷ 277 V = 3,599 A, about 3,600 A in each secondary lead.
- Primary full-load current: 997,000 VA ÷ 7,200 V = 138.5 A, about 138 A.
- Ratio: 3,599 A ÷ 138.5 A = 26.
- Temperature: (300 - 32) × 5/9 = 268 × 5/9 = 148.9 °C, about 149 °C.
- Part-load check: at half load, stray loss ≈ (0.5)² = 0.25 of the full-load value.
Result: each secondary lead carries about 3,600 A, twenty-six times the primary current, so the steel between them sees a field the primary-side pair never develops. If the twin pad between the primary bushings scans cool under the same conditions, that contrast is further evidence for a current-driven mechanism. The reported 300 °F is 149 °C, a surface temperature consistent with the peeled paint: that coating has already run past its limit.
Decision: a confirmed 149 °C between the secondary bushings is defect-level heating in the hardware there. Escalate now — do not wait for oil or winding indications to catch up, and do not repair the plate in the field. If the scan was taken well below rated load, rescan near rated load first, because at half load the loss is about four times smaller and a part-load scan understates the condition. These currents are nameplate estimates; the heating at any moment follows the real load current through the leads.
What to send, and what to never touch #
The escalation package fits in one submission:
- Complete nameplate and serial number, plus photographs of both pads.
- The verified scan record: load current, ambient, emissivity setting, distance, spot size, timestamp.
- The sister-unit comparison under similar load.
- Two direct questions: what the pad is, and what surface temperature the manufacturer accepts on it.
The numeric limit belongs to the manufacturer, not to a table you pick: the working threshold here comes from the observed damage, peeled paint, and their written acceptance criterion replaces it once issued.
Never grind, weld, cut, insulate, relocate or paint over the pad to test a theory, and never attach a trial bond. Any of those changes the bonding or the magnetic circuit at the exact spot where the heating is, which can create a new loss, mask the original condition, or leave the equipment outside its documentation. The only acceptable correction is the manufacturer's written instruction for the exact serial number, performed by qualified personnel, with the unit de-energized, grounded and verified dead before anyone opens anything.
When the answer comes back: if the manufacturer confirms the installation correct and the temperatures within their criteria, keep those criteria in the file and return the unit to your normal infrared cycle. If they identify a defect or an incorrect part, perform only that written instruction, then rescan under comparable load and confirm the spot is gone or inside their criteria.
The decision, case by case #
- Reading confirmed and the pad unidentified: eddy-current and hysteresis heating in the hardware between the bushings is the working diagnosis. Escalate with the full package and keep hands off the pad.
- Reading not reproducible from a second angle: emissivity or reflection artifact. Fix the camera setup and rescan; nothing is wrong with the transformer yet.
- The pad turns out to be a core-ground point: follow the manufacturer's bonding instruction only, and add no second bond of your own.
- The pad is structural and the heating is within their criteria: document the criteria and monitor on the normal scan schedule.
- The same pattern shows on several sister units: report every serial number together, as a possible common design or installation issue.
Questions asked
Can the tank run this hot while the oil and windings are fine?
Stray-flux heating is localized in the steel near the high-current leads, so oil and winding temperatures can stay within their design limits while a small patch of tank runs far hotter — a normal oil indication does not clear the tank. Judge the tank on its own evidence: a confirmed reading near 149 °C with peeling paint is defect-level for that hardware, and it goes to the manufacturer either way.
Why would the factory use stainless or aluminum there instead of steel?
Nonmagnetic material is the standard design answer for hardware sitting in a bushing lead's leakage field. Stainless steel and aluminum carry essentially no hysteresis loss and support far less eddy-current heating than magnetic carbon steel in the same alternating field, so designers specify them for bushing mounting plates, inserts and flux shields where the currents are large. A magnetic-steel pad in that spot collects the heat instead.
Should I bond the mystery pad to the ground grid to be safe?
No. The tank is already grounded at the base pad, so a second bond adds no safety. If the upper pad connects to the core, your bond creates a second core-ground path, which can circulate current and generate its own heating in the core and tank. Leave it untouched, get the manufacturer's written identification against the exact serial number, and follow only their bonding instruction.
Does the hot spot change with load?
It should. Stray-flux loss in the steel follows the bushing current squared, so at half load you see roughly a quarter of the full-load heating and at rated load the full amount. Scan near rated load for a fair severity check and record the load at scan time; the manufacturer will ask for it, and a spot that swings with load supports the eddy-current diagnosis.