Troubleshooting
Why a VFD ignores the analog speed reference from the controller
Short answer
A speed-reference voltage never starts a drive, and it sets speed only when the drive's reference-source setting selects that analog input. A varying signal with a stopped motor is a missing run command; a motor that climbs to the same frequency at every command is a drive still running from its keypad or preset reference; a top speed about 3% low after both paths work is analog gain. Split the fault into those three cases and fix each in turn.
On this page
- Two separate command paths into the drive
- Read the symptom before touching a parameter
- Measure the signal where the drive sees it
- Case 1: no start — the run command is missing
- Case 2: one frequency at every command — the analog input is not the selected reference
- Case 3: speed follows but tops out low — the analog gain, worked out
- Before you close the panel
- Questions asked
You can prove the reference signal is alive and still have a drive that ignores it, because a drive takes two separate commands: a run command to start and a frequency reference to set speed. A voltage that changes with your speed command is the reference only — it never starts anything, and it sets speed only while the setting that selects the reference points at that analog input. That splits the complaint into three cases with three different fixes. No start with a good signal means the run command never reached the drive. A start that always climbs to the same frequency means the analog input is not the selected reference. A motor that follows every command but tops out about 3% short is analog scaling, and the correction belongs in the drive's analog gain, not in the wiring. Work the three cases in order.
Two separate command paths into the drive #
Every drive that accepts an external speed command needs a run command and a frequency reference, and each has its own setting. The run command is a digital input — a dry contact closed between an input terminal and its common — and the command-source setting decides whether that input or the keypad starts the drive. The frequency reference is the analog signal, in the industry-standard forms 0-10 V dc, ±10 V dc, 0-20 mA and 4-20 mA, and the reference-source setting decides whether the drive follows that signal or a keypad value, a preset or a stored maximum. Selecting terminal control answers the first question only. The classic trap: terminal control set, voltage seen changing at the terminals, job declared done — while the drive sits ready to run, displaying a reference it will never use because the reference source still points at the keypad.
Read the symptom before touching a parameter #
The motor's behavior tells you which path is broken, and one measurement decides it.
| What the motor does | Path at fault | Deciding check |
|---|---|---|
| Voltage at the drive changes with the command, motor stays stopped | Run-command path, or an active inhibit | Drive's digital-input status display while the contact closes |
| Motor starts, then climbs to the same frequency at every command | Reference source still on keypad or preset | Drive's displayed reference frequency while you sweep the signal |
| Motor follows commands but tops out short of the commanded maximum | Analog gain or span scaling | Input voltage against displayed reference at maximum command |
| Speed sags at a fixed command under load | Not a control fault — load or current limit | Motor current against the drive's overload margin |
For the last row, the number you need is an honest motor current, and measuring VFD and soft starter current with the right meter is how you get one from a drive output.
Measure the signal where the drive sees it #
Control terminals share an enclosure with mains parts, so before you open any cover or move any wire: lock out the drive's supply, wait the DC-bus discharge time the drive manual states, and verify absence of voltage at the terminals you will touch. NFPA 70E, 2024 edition, covers this kind of energized work as safety-related work practices — confirm the rules that apply to you with the authority having jurisdiction and the drive documentation.
Then, with control power on and the drive stopped, measure DC volts between the voltage analog input terminal and the drive's documented analog common, at the drive's control terminals, using a digital multimeter on its DC volts range while the controller sweeps the command. A healthy loop tracks the command from near zero to the top of the span. A reading at the controller proves the controller alone; the drive-end reading proves the wiring, the common and the drive's selector together. Check the input's hardware voltage/current selector — a jumper or switch on many drives — because a current-loop setting on a voltage signal reads wrong and scales wrong. If the controller reports an output while the drive terminals see nothing at any command, the analog channel itself has failed, and detecting a failed analog input channel and reporting it is a discipline of its own.
Case 1: no start — the run command is missing #
A varying reference with a stopped motor is not a reference fault; the drive is waiting for its run command. Close a relay contact from a controller output between a spare digital input and that input's common, set the command source to terminal control, and trust only the drive's own digital-input status display: operate the contact and watch the drive register the input, because a relay that clicks or an output LED on the controller proves nothing at the drive.
Match the wiring to the run mode the drive expects: a maintained contact suits two-wire run/stop, a momentary command suits three-wire start/stop, and the two are not interchangeable. Check for an active inhibit as well — a tripped fault or an open enable or safety input holds the drive stopped whatever the reference does.
Decision: the motor stays stopped until a verified digital-input transition reaches the drive. The analog signal plays no part in starting it, and no gain, selector or reference change will start it either.
Case 2: one frequency at every command — the analog input is not the selected reference #
Once the motor starts, the run-command path is proven. A motor that climbs to the same frequency at every command is following a reference that is not yours. Sweep the signal bottom to top and watch the drive's displayed reference or commanded frequency: if the display sits still, the reference-source setting still points at the keypad, a preset or a stored maximum, and the drive is ignoring the wire exactly as the symptom says. Select the voltage analog input as the reference source, confirm the hardware voltage/current selector agrees, and check reference priority, because jog, preset speeds, step references and comms references outrank the analog input on many drives.
Decision: the fix is confirmed when the drive's own reference display tracks your sweep from near zero to full scale — from that moment the motor follows the controller.
Case 3: speed follows but tops out low — the analog gain, worked out #
Example inputs: a controller whose documented analog output tops out at 9.8 V dc instead of the nominal 10 V; a drive input scaled 0-10 V for 0-50 Hz; a command that should give full speed; a measured output frequency of 48.5 Hz.
Ideal scaling gives 9.8 V ÷ 10 V × 50 Hz = 49.0 Hz, so the 0.2 V shortfall at the top of the span is worth 1.0 Hz. The measured shortfall is bigger: 50.0 − 48.5 = 1.5 Hz, or 3.0% of the span, which means the drive's input reads the signal low beyond the controller's shortfall — about 9.7 V registered where 9.8 V is applied. One correction absorbs both errors: raise the analog input gain by the measured ratio, 50.0 ÷ 48.5 = 1.0309. Set the gain in the drive's analog input group (the manual calls it gain, calibration or input span) from 100.0% to 103.1%, staying inside the gain range the manual documents, then verify: 48.5 Hz × 1.031 = 50.0 Hz at maximum command, with about half the span reading about half the reference at the midpoint.
Decision: apply the measured ratio and re-measure at full and half command. A small residual at full speed is normal tolerance in an analog chain. What gain cannot fix is a command that reaches full scale without giving the spindle speed the work needs — that is a motor or transmission-ratio problem, and the correction belongs in the gearing, sheaves or motor selection.
Before you close the panel #
- De-energize and verify absence of voltage before moving any control wire or connector.
- Run the motor once from the keypad before blaming the control wiring; a keypad run that works isolates the fault to the command paths.
- Record the parameter set you start from — command source, reference source, input selector, gain, minimum and maximum reference, ramps — before you edit anything.
- Enter the motor's own nameplate data: power, voltage, current, frequency and rated speed. Never load a parameter set borrowed from a high-speed spindle application: a maximum-output-frequency setting above the motor's nameplate frequency takes an ordinary motor past its mechanical speed limit and past what its self-cooling survives, and long runs well below base speed need a cooling check of their own.
- Run the analog signal as twisted shielded pair, shield landed per the drive manual, kept apart from power conductors; most stubborn wrong-speed complaints that survive the checks above turn out to be noise or a shared common on that cable.
Questions asked
Can I use a 4-20 mA signal instead of a voltage reference?
Yes, if the drive's analog input supports current and the controller offers it. Move the input's selector to current and rescale the input's span parameters for the current range. A current loop has a live zero, so a broken wire reads as no signal instead of as full speed, and it rides through long cable runs and noisy panels better than a voltage signal. The run command still needs its own digital input either way.
The drive displays a frequency but the motor is stopped. Is that a fault?
Usually not. Many drives show the reference and the run status separately, so the reference display can follow your signal while the drive waits for a run command. Read it as a diagnostic: a reference display that tracks your sweep proves the analog input is selected and receiving the signal, which leaves the missing run command as the fault to fix.
How accurate should an analog speed reference be?
Expect a few percent of span from the combined errors of the controller's output and the drive's input, and take the drive manual's stated analog input accuracy as the figure that matters. Correct steady offset and gain with the input's calibration settings, as in the worked example above. After calibration, a residual under 1% at full speed is normal; an error that grows with temperature or time points at failing hardware rather than scaling.
Can the controller's analog output damage the drive's input?
Not while the signal stays inside the span the drive documents. Damage comes from going outside it: reversed polarity, a voltage above the documented maximum, or a signal returned to the wrong common so the input sees a loop offset. Check the documented input range in both manuals before first connection, and never tie two signal sources to one input.