Why contactor failure data depends on the exact duty, not the frame
Short answer
Failure modes, electrical life and a dangerous-failure fraction are properties of one contactor catalog number under stated load, duty and protection; a frame carries none of them. Use the coordination table row for the tested combination, apply the claim only up to its published prospective current, and request the manufacturer's reliability data for the exact part; where no dangerous-failure fraction is published, none may be substituted.

On this page
A request for a contactor's failure modes and percentage of dangerous failure has no database answer at the generic level: those numbers attach to one catalog number, tested under stated load, duty, protection and environment, and a frame size carries none of them. An overtest - a 100 kA test circuit behind a 65 kA published claim - is margin the manufacturer kept for its own verification, not coverage that transfers to other ratings. The same rule governs electrical life and safety data. This article separates what each document actually describes, works the overtest example with its arithmetic, and ends with what to do when the dangerous-failure fraction does not exist.
What each rating actually describes #
IEC 60947-4-1, the product standard for electromechanical contactors and starters (the 2023 edition also covers motor protective switching devices), defines the utilization categories that set how hard every switching operation hits the contacts: AC-1 for resistive loads, AC-2 for slip-ring motors, AC-3 for starting and switching off running squirrel-cage motors, AC-4 for plugging and jogging. Each category applies different making and breaking currents, so one contactor carries several currents and several endurance numbers at once: a rated carrying current for the closed contacts, an electrical-life curve per category, and a mechanical-endurance count for no-load operations. What the AC-1 rating of a contactor covers for a resistive load is set out in What a contactor's AC-1 rating means for a single-phase load. Where a code question rides on a category or a rating, confirm the requirement with your authority having jurisdiction and the contactor's documentation.
Short-circuit coordination is a tested combination #
A contactor never clears a fault alone. IEC 60947-4-1 verifies short-circuit coordination on a combination - the contactor, its overload relay and a named short-circuit protective device - tested at a stated prospective current. Type 1 requires the combination to cause no danger to persons or the installation, accepting that the contactor itself may be unusable afterwards; Type 2 additionally requires the starter to be fit for continued service after the fault clears. The manufacturer's coordination tables list the tested combinations row by row, catalog number by catalog number, each with its maximum prospective current - not frame by frame. That is the same which-rating-governs question raised by an MCC's rating versus its bucket breakers', covered in MCC short-circuit rating vs bucket breaker ratings. A claim travels only with its listed rows.
Reading a 100 kA test circuit behind a 65 kA claim #
The inputs are illustrative figures for the overtest case: a test-laboratory prospective short-circuit current of 100 kA, and a published coordination rating of 65 kA for the listed combinations. The question is what the gap between them lets you apply.
The rule: the published value is the ceiling the manufacturer stands behind for the listed rows; the test only has to meet or exceed it, and how far above the claim the testing runs is the manufacturer's own choice.
The arithmetic: margin 100 kA - 65 kA = 35 kA; test-to-claim ratio 100 / 65 = 1.54; headroom above the claim 35 / 65 x 100% = 54%, rounded.
The result: the test circuit ran at roughly 1.5 times the published rating.
The decision: apply the claim where the prospective current at the starter is at or below the claimed value and the exact combination appears in the table. Above the claim, or for a combination the table does not list, the test margin buys nothing - select a combination the table lists for that fault level. And the margin never extends the rating to other catalog numbers in the same frame; coverage comes from listed rows, not frame membership.
Where failure-mode and dangerous-failure data live #
Typical contactor failure modes - welded or eroded main contacts, coil or insulation damage, terminal overheating, failure to pick up or drop out - are investigation categories, not probabilities for a given model. A dangerous-failure fraction is a different kind of number: it belongs to a defined safety function, with failures classified as dangerous detected or undetected and diagnostic coverage stated, in the framework IEC/EN 62061 uses to define safety integrity levels.
Some manufacturers do that analysis and publish results per device; one major supplier publishes functional-safety and reliability data covering its motor-starting and protection range. Others state plainly that the number does not exist: the published support note for Rockwell Automation's Bulletin 100S, 104S and 700 safety contactors and relays says some of its figures come from an FMEA and that no dangerous-failure fraction or FMEDA is on record for that line. That is an answer from the source that holds the data, not a gap to fill with a generic percentage.
What endurance tests prove #
Electrical endurance tests run a stated number of make and break operations under stated load conditions against defined acceptance criteria; mechanical endurance tests count no-load operations. Run-to-destruction testing exists, and it can show which mechanism limits the device - contact erosion, welding, coil failure - but a run-to-failure result describes the tested conditions, not a field failure rate or a service interval. Environmental, vibration and EMC stresses are separate test dimensions with their own levels. Before quoting any figure, ask for the test standard, the load and voltage, the operation rate, the acceptance criteria, and whether the number is typical or a guaranteed limit. Uneven duty also shows up in the hardware itself: the unbalanced heating that burns one pole first is its own diagnosis, covered in Why only one contactor pole burns on a small motor.
The decision #
For fault coordination: find the row for the exact catalog number with its named protective device and apply it only up to the published prospective current; the frame and the test margin add nothing. For life: read the electrical-life curve at your utilization category and actual operation rate, and treat a mechanical-endurance figure as irrelevant to contact wear. For a safety function: request the FMEDA and dangerous-failure data for the exact part and revision through the manufacturer's technical or safety channel; where the manufacturer publishes none, record the fraction as unavailable and keep generic figures out of the calculation - qualify the function another way or select a device whose published data covers it.
Before opening any starter to read contact damage or a coil, de-energize, lock out and verify absence of voltage following NFPA 70E, the 2024 edition, which covers safe work practices around energized electrical equipment; confirm those requirements with your authority having jurisdiction and the equipment documentation.
Questions asked
Can I interpolate a coordination claim between tested prospective-current values?
No. Coordination is verified at the prospective-current values the tests were run at, so a point between two tested rows is not established by the two results together. Choose a combination whose published row meets or exceeds the fault current calculated for the installation, and confirm the calculation method against the governing standard and the manufacturer's data.
What is the difference between electrical and mechanical endurance on a contactor datasheet?
Mechanical endurance counts no-load operations of the operating mechanism and is stated in millions of operations for most industrial contactors; electrical endurance counts operations while making and breaking load current and is always lower, because every operation erodes the contacts. Read the electrical-life curve at the utilization category and operation rate your application runs, not at the headline number on the front page.
If the manufacturer publishes no dangerous-failure fraction, can I use an industry survey figure instead?
No. A dangerous-failure fraction assumes specific failure modes, detection and diagnostic coverage for one device in one function; a survey figure built from other devices makes the calculation unverifiable. Record that the data does not exist for the catalog number, then either obtain an FMEDA for that part through the manufacturer's safety channel or design the function so it does not depend on that fraction.