Explainer
Why power factor differs between circuits on the same bus
Short answer
Both readings can be correct. A shared 11 kV bus gives every circuit the same voltage, but each circuit's power factor pairs that voltage with its own current: a 0.85 feeder carries about 0.62 kvar per kW of active power, a 0.95 transformer branch about 0.33. Confirm each display is bound to its own current measurement before blaming the excitation controller.

On this page
- Power factor belongs to a circuit, not to the bus
- What each display value represents
- What the two readings mean in kW and kvar
- Compare the supervisory screen with the local device
- Configuration checks before touching the excitation controller
- What the excitation controller can and cannot move
- The decision
- Questions asked
A feeder reading 0.85 power factor and a station transformer reading 0.95 on the same 11 kV bus are not contradicting each other. Both can be correct at the same instant. The shared bus fixes exactly one thing: the voltage. Power factor is computed from a pair — one circuit's own current against a voltage reference — so every branch on the bus carries its own ratio of reactive to active power. The feeder's number describes the grid exchange at that connection; the transformer's number describes the station auxiliary load it supplies. This article explains why two honest power factors differ legitimately on one bus, how to confirm that each display is bound to its own current measurement, and where a real fault would hide before anyone touches the excitation controller.
Power factor belongs to a circuit, not to the bus #
Apparent power combines active and reactive power as S = sqrt(P² + Q²), all three in the same units — on a plant scale kVA, kW and kvar — and power factor is the ratio P/S. For a balanced, substantially sinusoidal circuit the reactive-to-active ratio follows directly: |Q/P| = sqrt(1/PF² − 1). The phase angle between a branch's current and the shared voltage is the arccosine of its power factor, so the feeder here runs at about 31.8 degrees and the transformer branch at about 18.2 degrees.
A meter computes that ratio from one current and one voltage. The bus guarantees the voltage is common; it says nothing about the current. Each branch's current transformer sees only its own conductor, and what that conductor carries sets the angle: the outgoing feeder carries the grid exchange, the station transformer carries the auxiliary load, the generator carries whatever its excitation controller regulates. A bus itself has no power factor; a metering point does. Different branches at one voltage, at one instant, with different angles — different power factors, both honest.
What each display value represents #
Trace every displayed value back to its physical measurement pair before interpreting it. Read the circuit name beside the value, follow it through the monitoring system's tag list to the current transformer feeding it, and note which voltage transformer supplies the reference. The metering side matters: a station transformer measured on the high-voltage side includes the transformer's own magnetizing vars and losses in the reading; measured on the low-voltage side, the reading is the station load's power factor alone.
| Display | Measurement pair | What the value reflects |
|---|---|---|
| Outgoing feeder | Feeder current transformer, bus voltage transformer | Net active and reactive exchange with the grid at that connection |
| Station transformer | Transformer circuit current transformer, bus or low-voltage voltage transformer | Auxiliary load mix, plus transformer vars if metered on the high-voltage side |
| Generator, if displayed | Generator current transformer, terminal voltage transformer | The boundary the excitation controller regulates |
Each motor, drive and lighting panel in the station service contributes its own share of active and reactive power, so the transformer branch's ratio is set by that load mix — the branch's own power factor, the same quantity you pick when choosing a power factor for a motor current calculation. Neither branch display is the generator terminal power factor, and neither has to match the other.
What the two readings mean in kW and kvar #
Assume a balanced three-phase, sinusoidal circuit — the condition most bus metering is built for — and treat every megawatt figure below as an example input, not a measurement.
Feeder at 0.85: 1 / 0.85² = 1 / 0.7225 = 1.3841; 1.3841 − 1 = 0.3841; sqrt(0.3841) = 0.62. The feeder carries about 0.62 kvar for every kilowatt of active power.
Transformer branch at 0.95: 1 / 0.95² = 1 / 0.9025 = 1.1080; 1.1080 − 1 = 0.1080; sqrt(0.1080) = 0.33. That branch carries about 0.33 kvar per kilowatt.
To attach magnitudes, invent inputs, because a plant's overall rating is not a measurement of either branch. If the feeder exports 10 MW at 0.85, its apparent power is 10 MW / 0.85 = 11.765 MVA, and Q = sqrt((11.765 MVA)² − (10 MW)²) = sqrt(138.4 − 100) MVA² = 6.20 Mvar. If the station transformer carries 2 MW at 0.95, S = 2 MW / 0.95 = 2.105 MVA and Q = sqrt((2.105 MVA)² − (2 MW)²) = sqrt(4.431 − 4) MVA² = 0.66 Mvar. One bus, two branches, 6.20 Mvar and 0.66 Mvar at the same time — both meters right. The conversion rests only on the definition of power factor; check any real branch against its own measured active and reactive powers, not against this example.
The ratios say nothing about direction: the feeder's figure could be lagging import, lagging export or leading in either direction. Read the signed active and reactive powers and the device's direction convention before interpreting. And when drives or rectifiers sit in the branch, current distortion separates total power factor from displacement power factor — the split examined in why total power factor differs with vector vs scalar kVA.
Compare the supervisory screen with the local device #
Before calling either number a fault, separate a display-binding problem from an electrical one. Where a supervisory screen shows the values, read the same circuit on the local device at the same load and compare power factor, active power and reactive power together.
- If the screen and the device agree, the values are electrical facts about the branch; continue with the measurement checks below.
- If they disagree, suspect the tag association, scaling or communication interpretation first: a correctly communicating tag can still be bound to the wrong feeder, and a right circuit label can carry a stale or wrongly decoded value.
- Comparing two instruments on one circuit is a different fault again; the per-phase method in why two power factor meters disagree per phase covers that case.
Devices built and declared to IEC 61557-12, 2022 edition, report the same defined quantities: the standard specifies requirements for stationary power metering and monitoring devices and lists the electrical quantities such a device may measure. A power factor from two compliant devices is therefore the same defined quantity; which quantity and accuracy class a specific model declares is stated in its documentation. Confirm against the manual rather than assuming.
Configuration checks before touching the excitation controller #
If a branch's numbers look implausible — direction contradicting a known operating condition, magnitudes off against a portable analyzer, a power factor barely moving while load swings — work the measurement chain in this order.
- Ratios: compare the configured current and voltage transformer ratios with the installed nameplates. A uniform ratio error scales active and reactive power together and can leave the power factor looking plausible while every magnitude is wrong. A metering current transformer carries a class and burden rating — for example 0.3 B0.5, where 0.3 is the permitted percent ratio error and B0.5 is a 0.5 ohm secondary burden — and that accuracy affects magnitude, not the angle.
- Polarity and reference direction: a reversed current circuit flips the signs of active and reactive power, so direction and lead or lag interpretation go wrong while magnitudes look right. Verify against a known load flow.
- Phase pairing: a voltage lead landed on the wrong phase scrambles the measured angle and distorts the power factor with plausible magnitudes. Check against the drawings and the device's phasor display where it has one.
- Displayed quantity: confirm whether the value shown is total or displacement power factor before comparing it with any calculation.
De-energize and verify absence of voltage before opening any metering panel, terminal compartment or current transformer circuit — NFPA 70E, 2024 edition, covers electrical safe work practices and requires de-energizing and verification before work where feasible — and an energized current transformer secondary must never be opened. Confirm the applicable requirements with the authority having jurisdiction and the plant's switching procedures.
What the excitation controller can and cannot move #
In power factor mode the automatic voltage regulator holds the power factor at its own feedback measurement, and the control documentation states which boundary that is: generator terminals or the grid connection point. Excitation changes the machine's reactive exchange and shifts the bus voltage slightly; each branch's reactive flow responds to that voltage a little. It cannot pull two branches to one number. The feeder's power factor follows the grid exchange at its connection; the transformer branch's follows the station load. Trim excitation to hit its own target — the tariff boundary or the machine's reactive limit — not to close the gap between two displays that are both telling the truth.
The decision #
- Both displays trace to their own current measurement against the bus voltage, and the supervisory screen matches the local devices: both power factors are correct; there is nothing to fix on the bus.
- The screen disagrees with the local device: correct the tag mapping, scaling or communication interpretation; the measurement wiring and the excitation stay untouched.
- A branch's numbers contradict a known operating condition: work through ratios, polarity, phase pairing and the displayed quantity, then correct the confirmed error through the plant's approved maintenance process.
- Distorted load in the branch: compare total with total and displacement with displacement before calling a difference a fault.
- Excitation: set it for the boundary it regulates. The gap between the feeder and transformer readings is the plant's own reactive geography, not an error.
Questions asked
Does a feeder reading of 0.85 tell you whether the circuit is leading or lagging?
No. 0.85 is a magnitude only. Whether the circuit is leading or lagging comes from the sign of the reactive power and the device's direction convention: many devices print a lead or lag flag beside the number, or treat positive reactive power as lagging. Read the signed active and reactive values alongside the ratio, and check the convention in that device's manual before comparing readings from two different devices.
Which power factor figure matters for a utility power factor penalty?
The one the tariff is written on: the power factor at the utility metering point on the grid connection, computed from that meter's own signed active and reactive energy. Branch displays inside the plant, including the station transformer, do not enter the bill. When a penalty arrives, reconcile the utility meter's figures first, then trace internal branches if the numbers still do not add up.
What reading would actually indicate a metering fault rather than two honest power factors?
Treat a value as suspect when it breaks physics or arithmetic: a magnitude above 1.00 is impossible for any circuit; active and reactive power must combine to the displayed apparent power as the square root of the sum of their squares; and a reading that holds still while the load moves is probably a stale or wrongly mapped tag. All three point at the measurement chain, not at the excitation controller.
Can I average the feeder and transformer power factors into one number for the bus?
No single bus power factor exists to average toward. A ratio has no meaning outside its own apparent power base, so averaging the two displays produces a number that describes nothing. If you want one figure for a boundary, add the signed active power and the signed reactive power of the circuits at that boundary first and compute the ratio from the totals.
