Why residual current after a single-pole trip is not 40 A

Protection: breakers, fuses and SCCR Published 8 min read By Current Intel engineering team

Short answer

Neither 40 A nor 20 A follows from an open pole. The residual is the phasor sum of the currents the relay's CTs measure: equal to the neutral current on a four-wire feeder with line-to-neutral loads, zero on a three-wire motor circuit. A three-CT residual element reads that unbalance as earth-fault current; a core-balance or neutral-inclusive measurement does not, and a negative-sequence element is the right tool for the open pole.

On this page
  1. Is the relay really seeing 40 A with one phase out?
  2. What does the relay's residual current actually measure?
  3. Why does the same open pole read differently on two feeders?
  4. How do you calculate residual current from the event record?
  5. Will the earth-fault element trip on the unbalance?
  6. Which element detects an open pole without tripping on load unbalance?
  7. What do you check before changing any setting?
  8. What is the decision for each feeder type?
  9. Questions asked

No. After a downstream single-pole trip the 11 kV relay does not see 40 A, and it does not see 20 A with two poles open. Those figures come from adding unsigned current magnitudes and dividing by three. The relay's earth-fault quantity is the phasor sum of the currents its CTs actually measure, so the value is set by the return path and the CT arrangement: on a four-wire feeder with equal line-to-neutral loads it equals the neutral current, and on a three-wire motor circuit it is zero. This article shows the arithmetic for both cases and gives the decision for each measurement arrangement.

Is the relay really seeing 40 A with one phase out? #

No. The 40 A figure comes from adding two unsigned current magnitudes and dividing by three, but the relay's earth-fault quantity is a phasor sum with no division in it, so the guessed figure is not a residual current at all. The 20 A guess for two poles out repeats the same move with one magnitude over three. The division habit belongs to symmetrical components, where the zero-sequence current is I0 = (Ia + Ib + Ic) / 3, but the sum inside the brackets is a phasor sum, and the residual an earth-fault element acts on is three times I0.

The two guessed numbers are not random, though. For one specific pattern, with the open phase at zero and two equal currents 120 degrees apart, the positive-sequence magnitude works out to 40 A and the zero-sequence component to 20 A. Those are sequence components of that one load pattern, not the earth-fault quantity, and they move as soon as the load mix or the power factors move.

What does the relay's residual current actually measure? #

The residual is the phasor sum Ia + Ib + Ic of the phase currents at the measuring point, and a relay either calculates it from its three phase CTs or measures it with a single ring-type CT around all the conductors. Both methods are documented practice: the ABB application note on restricted earth-fault protection for the REF 542plus relay describes the earth-fault current as calculated from the three phase currents or separately measured by a ring-type CT.

The physics behind both methods is current continuity. The phasor sum of the currents crossing the CT boundary equals the current returning by any path outside that boundary, whether an earth path or a neutral conductor the CTs do not enclose. Watch the quantity name on the display as well: some elements pick up on the residual, some on I0, and the two differ by a factor of three, while negative-sequence current is a separate quantity that measures unbalance rather than return current.

Why does the same open pole read differently on two feeders? #

Because the return path decides the sum: on a four-wire feeder the missing phase's current returns in the neutral, so the phase-CT residual equals that neutral current, while on a three-wire motor circuit the two surviving line currents are equal and opposite and add to zero. A four-wire 11 kV feeder gets its neutral from the grounded wye secondary of the 33/11 kV transformer. When the downstream device opens one pole, the single-phase loads on the two live phases keep drawing current and return it through that neutral; with equal currents at equal power factor the neutral current equals one phase current, and at different power factors the angle between the surviving currents changes and so does the sum. The loading this puts on the transformer itself is a separate problem, covered in unbalanced loading on a delta-wye transformer with one open phase.

A three-phase motor is a three-wire load. With one line open, the source drives a single series path through the windings, so the two surviving line currents are equal and opposite and their sum is zero. The unbalance is real, the motor heats, and its own negative-sequence or thermal protection often trips it, but that unbalance lives in the negative sequence, not the residual.

How do you calculate residual current from the event record? #

Read the three phase currents as phasors from the relay's event record and add them with their angles; the sum is what the residual element saw, and the worked example below shows the arithmetic for both feeder types. Hypothetical example with every input stated: an 11 kV feeder at 50 Hz, equal single-phase line-to-neutral loads drawing 60 A per phase at equal power factor before the event, the downstream device opening phase A only, and the loads on B and C holding their pre-event current. The record then shows Ia at zero, Ib = 60 A at -120 degrees, Ic = 60 A at +120 degrees.

For two equal phasors the sum's magnitude is 2 x I x cos(half the angle between them), so:

  • Four-wire case, 120 degrees apart: 2 x 60 A x cos 60 degrees = 2 x 60 A x 0.5 = 60 A of residual, matched by 60 A returning in the neutral.
  • Motor case, 180 degrees apart: 2 x 60 A x cos 90 degrees = 2 x 60 A x 0 = 0 A of residual.
  • Motor negative sequence: I2 = I / root 3, so 60 A / 1.732 = 34.6 A.

The full picture for both feeders, with the sequence formulas I1 = (Ia + a x Ib + a2 x Ic) / 3 and I2 = (Ia + a2 x Ib + a x Ic) / 3 and a the 120-degree operator:

Quantity Four-wire feeder, phase A open Three-wire motor feeder, phase A open
Ia 0 A 0 A
Ib 60 A at -120 degrees 60 A at 0 degrees
Ic 60 A at +120 degrees 60 A at 180 degrees
Residual Ia + Ib + Ic 60 A 0 A
Zero sequence I0 20 A 0 A
Positive sequence I1 40 A 34.6 A
Negative sequence I2 20 A 34.6 A
Neutral current 60 A none

The residual row is the only one the earth-fault element acts on, and neither guessed figure appears in it: one feeder shows the full neutral-return current, the other shows nothing.

Will the earth-fault element trip on the unbalance? #

With a plain three-CT residual connection, yes: the element cannot tell load unbalance from an earth fault, because both arrive as the same phasor sum, so tripping then depends only on pickup and delay. The three measurement arrangements answer differently:

Earth-fault measurement Sees open-pole load unbalance? Reading in the four-wire example
Residual calculated from three phase CTs, neutral not summed Yes, unbalance and earth fault arrive as the same phasor sum 60 A
Residual from phase CTs with the neutral CT summed in No, the neutral return cancels in the sum 0 A
Ring-type core-balance CT around all conductors No, only current leaving the enclosed group is measured 0 A

The core-balance row is the clean one: with no earth return, the net current crossing the CT aperture is zero whatever the phase currents do, the working principle behind what a zero-sequence CT does in ground fault protection. The first row is the one that trips plant: a sensitive residual element picks up on load unbalance alone, the mechanism behind why a 51N earth-fault setting trips without a fault. The same unbalance is what limits how sensitive a nondirectional residual element can be set on four-wire feeders with phase-to-neutral load.

Which element detects an open pole without tripping on load unbalance? #

Give the open-pole duty to a negative-sequence overcurrent element, the 46 or 50Q/51Q function, because it responds to unequal phase currents while a neutral-inclusive or core-balance earth-fault measurement stays at zero for pure load unbalance. Its formula is I2 = (Ia + a2 x Ib + a x Ic) / 3, and it lands at the 34.6 A the table shows for the motor case. A residual element cannot do this job on a three-wire motor circuit, where the open pole produces no residual at all.

Set the negative-sequence pickup above the feeder's normal load unbalance and coordinate it with the earth-fault element and the downstream devices. The coordination procedure for distribution feeders is set out in a downloadable paper on negative-sequence overcurrent element application and coordination.

What do you check before changing any setting? #

Change nothing until the event record, the CT wiring and the conductor routing have been checked, because a residual that appears under balanced load points to reversed polarity or a swapped phase input, not to an earth fault. Any step that opens the relay panel or a CT terminal block begins with the circuit de-energized, locked out and tested for absence of voltage, wearing the arc-rated clothing and gloves NFPA 70E, 2024 edition calls for on the task; confirm the procedure with your electrical safety program and the authority having jurisdiction.

Then work the list:

  • Pull the event record: the operated element, the quantity it displayed (residual or I0), pickup, delay, and the phase currents with angles at the moment of trip.
  • Verify CT ratio, polarity and phase assignment against the wiring diagram; on four-wire feeders confirm whether a neutral CT exists and whether its secondary is summed with the phases.
  • On a core-balance CT, confirm every phase and neutral conductor of that circuit passes through the window and nothing else does.
  • Prove the residual sits within CT error of zero under balanced load, before and after any change, then finish with a secondary-injection test of the element per the relay manual.

What is the decision for each feeder type? #

Four-wire feeder with a three-CT residual: bring the neutral CT into the sum or move to a core-balance CT, set any residual-only element above the worst neutral current, and give the open pole to a negative-sequence element; three-wire feeder: keep the earth-fault element and add the negative-sequence element. Case by case:

  • Three-CT residual on a four-wire feeder: the open pole is presented as earth-fault current. Include the neutral CT in the sum or change to a core-balance CT; where neither is possible, set the residual pickup above the worst-case neutral current with added delay and accept reduced earth-fault sensitivity.
  • Neutral-inclusive or core-balance measurement on a four-wire feeder: the unbalance is invisible, so the earth-fault settings stay exactly as they are.
  • Three-wire feeder: the residual holds at zero for any load unbalance, so the earth-fault element is secure; put the open-pole detection on a coordinated negative-sequence element.

In every case the number you write down comes from the event record's phasors, never from dividing the load current by three.

Questions asked

Is the earth-fault pickup written in I0 or in residual amps?

Relay manuals differ. Some elements pick up on the zero-sequence component I0, others on the residual, which is three times I0, so the same physical setting reads three times smaller in I0. Before comparing a pickup with event-record values, put both in the same quantity as the element definition in the manual states.

Does an earth fault also drive the negative-sequence element?

Yes. Every unbalanced fault produces negative-sequence current alongside zero-sequence current, so the two elements overlap and must be coordinated: the negative-sequence element should back up the earth-fault element and the downstream protection, not race them. Distribution-feeder coordination cases are worked through in the negative-sequence paper linked in the body.

What does the residual read with two downstream poles open?

On the four-wire example it stays equal to the one remaining phase current, because that current still returns through the neutral, so it does not fall to a third of the load. On a three-wire motor circuit two open poles remove every current path, and the residual and the sequence quantities all collapse to zero.

Why does the metering show residual current on a healthy feeder?

Almost always a secondary-circuit error: one CT polarity reversed, two phase inputs swapped, or mixed CT ratios on one circuit. The signature is a residual that holds a fixed fraction of load current as the load changes. Correct the wiring, then confirm the calculated residual sits within CT accuracy of zero under balanced load, before and after any setting change.

Keep reading

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.

    Protection: breakers, fuses and SCCR

  • Comparison

    What current-only motor protection can and cannot detect

    Three per-phase current amplitudes support overload, phase loss, current unbalance, stalled acceleration and short-cycling protection, and nothing else. Undervoltage, ground fault, winding temperature and mechanical overloads such as high head pressure need their own inputs: a voltage measurement channel, a core-balance current transformer, and temperature or pressure sensors.

    Protection: breakers, fuses and SCCR

  • Explainer

    Why a 51N earth fault setting trips without a fault

    A residual 51N element set at 0.05 In with a 0.7 s delay trips without a fault when the residual connection reports more than that in normal operation: load unbalance, a CT circuit error, or a low-level earth fault. Read the event record, verify the CTs, measure the normal residual current, then set the pickup above it, 0.10 In first and 0.12–0.13 In if the measurement demands it, keeping the delay only where coordination supports it.

    Protection: breakers, fuses and SCCR