Why the generator-side neutral grounding switch stays closed
Short answer
Close the generator-side neutral disconnect switch as the normal position and close the transformer-side switch only in the states where the generator breaker is open. Both neutral grounding resistors stay installed, and an interlock keeps at least one ground reference on the 13.8 kV bus and the machine in every operating state, including the delta 69 kV islanding case.

On this page
- Which neutral grounding switch should be closed on a 13.8 kV generator bus?
- What goes wrong when the transformer-side switch is the only one closed?
- How does each switch position behave in the four operating states?
- Why does the delta 69 kV winding make the islanded fault the hard case?
- How do you size the neutral grounding resistor on a 13.8 kV bus?
- Which protection elements must be armed in every operating state?
- When is the transformer-side position the right choice?
- How do you switch positions without losing the ground reference?
- Questions asked
On a plant with one generator and one 69/13.8 kV step-up transformer sharing a 13.8 kV bus, each neutral runs through its own grounding resistor and each resistor sits behind a neutral disconnect switch. The decision is which switch stays closed. Close the generator-side switch as the normal position and use the transformer-side switch for the states where the generator breaker is open. One fixed position leaves either the machine or the bus ungrounded in some operating state; both resistors installed, with a per-state switching rule, is the design that keeps every state grounded.
Which neutral grounding switch should be closed on a 13.8 kV generator bus? #
Close the generator-side neutral disconnect switch as the normal position and use the transformer-side switch only for the states where the generator breaker is open: that pairing is the only one of the two that keeps the machine and the bus grounded in every operating state.
The scheme behind the question is one generator and one step-up transformer, high side to the 69 kV grid, low side to the main bus, each neutral brought out through its own neutral grounding resistor (NGR) and each neutral path carrying a neutral disconnect switch (NDS). The two positions are not rival designs; they are two positions of one design, and the engineering job is to assign each operating state to the position that keeps a ground reference where it is needed.
The default goes to the machine side because the machine is the element with the narrowest protection: stator ground protection exists only while the generator has its own grounded neutral. The transformer side then serves the states in which the generator breaker is open and the bus alone needs a reference. The table in the next section is the decision tool; sizing, protection and the transfer procedure follow.
What goes wrong when the transformer-side switch is the only one closed? #
The generator loses its ground reference whenever it runs excited with its breaker open, so a stator ground fault has no defined return path, the stator ground element cannot see it, and the machine floats unreferenced above ground.
The failure depends on where the generator breaker sits. When the breaker is between the generator terminals and the bus, opening it removes the machine from the transformer NGR and from the bus at the same time. An excited machine at speed-no-load, synchronizing or held hot for a fast restart, then has no neutral return and no grounded point anywhere on its windings.
A stator ground fault in that state arcs against the core with no measurable current. The ground element is blind because its measuring circuit hangs on the neutral path that the switch position has disconnected, and the first sign of trouble may be the differential element or a visible failure long after the insulation is burning. This single state decides most installations: if the plant ever runs the machine excited with its breaker open, the generator-side switch is the closed position for that state, and by extension the sensible default for the rest.
How does each switch position behave in the four operating states? #
List the four states the plant actually runs: grid supply with the generator tied in, grid supply alone, generator island after the utility trips, and the generator excited with its breaker open; no single fixed switch position keeps all four of them grounded.
| Operating state | Generator-side NDS closed | Transformer-side NDS closed |
|---|---|---|
| Grid supply, generator tied in | Machine and bus grounded through the generator NGR; stator protection on its designed current | Machine grounded through the bus and the transformer NGR, which changes the stator fault current and the relay settings; bus grounded |
| Grid supply, generator breaker open | Bus left with no ground reference | Bus grounded through the transformer NGR |
| Generator island after the utility trips | Machine and bus grounded; stator protection armed | Same as the tied-in state |
| Generator excited, breaker open | Machine grounded; stator protection armed | Machine ungrounded; stator ground protection blind |
Read the table by column. The generator-side column fails in one state only, grid-only operation with the breaker open, while the transformer-side column fails in the last row and alters the machine's ground-fault numbers wherever the machine is tied in. Neither column passes all four states on its own. That result is the argument for keeping both NGRs installed and assigning the switch position state by state, rather than choosing one position for the life of the installation.
Why does the delta 69 kV winding make the islanded fault the hard case? #
A delta winding on the 69 kV side feeds no ground-fault current toward the grid, so once the utility clears a line fault the generator can sit behind the delta still energizing that faulted line, and only the plant's own relays can end it.
With the utility side wye-grounded and the transformer high side delta, the plant contributes no zero-sequence current toward a 69 kV ground fault; the article on grounded wye versus delta ground fault current explains why the winding connection decides that. When a single-line-to-ground fault lands on the line, the utility substation clears its end, the 27 undervoltage element opens the incoming breaker, and the generator holds its own bus and load as an island.
The line section beyond the open breaker is then ungrounded: the utility ground source is gone and the delta supplies none. The 59Vo residual overvoltage element detects that neutral displacement and trips the plant off the line; where the faulted line must be dropped faster than the 59Vo time delay allows, an intertrip channel over a communication link does it directly. This case does not move the switch decision, because it plays out on the 69 kV side under either NDS position, and both positions need the same 27 and 59Vo coverage. What islanding does stress is the machine's grounding path, and the article on generator islanding overvoltage with high impedance neutral follows that behavior further. Take the 59Vo pickup from the ground-fault study, not from a relay default.
How do you size the neutral grounding resistor on a 13.8 kV bus? #
Size each resistor from the line-to-ground voltage divided by the designed ground-fault current: on a 13.8 kV bus with a 400 A design current the value lands near 20 ohms, and both resistors in this scheme work on the same line-to-ground voltage.
Ohm's law on the single-phase circuit gives the resistor, and the design current is the choice you make: high enough for the ground relays to measure cleanly, low enough to bound the damage and to suit the machine's allowable ground-fault current. Worked example, with illustrative inputs: a 13.8 kV three-phase, 60 Hz system, low-resistance grounding chosen at 400 A.
- Line-to-ground voltage: 13,800 V / 1.732 = 7,967 V.
- Resistor: 7,967 V / 400 A = 19.9 ohms, so select the next standard value, 20 ohms.
- Solid ground-fault current with the selected resistor: 7,967 V / 20 ohms = 398 A, and the resistor duty at that current is 398 A x 398 A x 20 ohms = 3,168,080 watts, about 3.2 megawatts, which the resistor's short-time rating must cover for relay time plus breaker time from the study.
- Transfer overlap with both switches closed: the two resistors land in parallel at 10 ohms, so 7,967 V / 10 ohms = 797 A. Check both resistors and the relays against that doubled current for the seconds the transfer takes.
Fix the design current against IEEE C37.101-2021, the IEEE guide for generator protection, which covers generator grounding methods and stator ground protection, and confirm the final values with the local authority having jurisdiction and the equipment documentation. Stator core damage limits can push the machine's own design current far below the bus value; that changes the machine's resistor and relay settings, not the switch choice. The method-level decision, low resistance against high resistance, is worked through in the guide to choosing generator neutral grounding for a 480 V diesel set.
Which protection elements must be armed in every operating state? #
Three relay functions carry the scheme across its states: the stator ground element that needs the generator-side resistor in circuit, the 27 undervoltage element that separates the plant from a collapsed grid fault, and the 59Vo residual overvoltage element that trips the ungrounded island.
The stator ground element's settings are valid only for the grounding point they were calculated from. Running the machine tied in with its own switch closed, as the state table does, holds the machine's ground current at its designed value; the tie-in states with the transformer-side switch closed put the fault path through the transformer resistor and the bus, a different measurement, so the interlock keeps that combination out of service instead of re-programming the relay for it.
On the machine neutral itself, a 59N neutral overvoltage element across the resistor backs the stator ground function, with its pickup set from the study above normal neutral unbalance. On the incoming breaker, 27 separates the plant from a collapsed grid fault and 59Vo trips the ungrounded island. Prove all of them by secondary injection on their test schedule, with the switchgear de-energized for that work.
When is the transformer-side position the right choice? #
The transformer-side switch is the permanent position only for a plant that never energizes the generator while its breaker is open, and it is the required position for every grid-only state in which the generator is disconnected from the bus.
Two uses are legitimate. First, every grid-only state: the generator out of service, racked out, or not yet installed. The transformer NGR is then the only ground source the bus has, so its switch is closed and the generator-side switch is open. Second, as the permanent default for a plant whose machine is always de-excited before its breaker opens: no speed-no-load holding, no test runs with the breaker racked out while the field is on, no automatic restart that closes the field first.
Even then, walk the one-line and the operating procedures once to confirm the breaker location and that no mode leaves the machine excited behind an open breaker. Where both neutral paths must come out together for resistor maintenance, grounded-wye voltage transformers on the bus can hold a limited ground reference while the work is on; the note on NGR fault current bypass via grounded wye voltage transformers explains the mechanism and its limit. That path carries amperes rather than the designed ground-fault current, so it is a maintenance bridge, not an operating state.
How do you switch positions without losing the ground reference? #
Switch the positions make-before-break with an interlock that never allows both switches open at once, transfer while the system is healthy rather than during a fault, and treat a both-open indication as an immediate alarm on the bus.
- Write the four states and their switch positions onto the one-line diagram and into the switching order: generator-side closed whenever the machine is energized or about to be, transformer-side closed whenever the generator breaker is open, at least one closed always.
- Transfer to grid-only operation while the machine is still tied in and the system is healthy: close the transformer-side switch, open the generator-side switch, then trip the field and open the generator breaker. The resistors sit in parallel for the seconds of the overlap, the 797 A case checked in the sizing example.
- Build the machine up in the reverse order: close the generator-side switch before the field breaker closes so the machine is referenced before it is energized, synchronize with the transformer-side switch still holding the bus, close the generator breaker, then open the transformer-side switch and return to the one-resistor state.
- Interlock the two switches so at least one is always closed, alarm on any both-open indication, and prove the position indication against the one-line after every transfer.
- Keep the islanding proof independent of the switch positions: secondary-inject the 27 and 59Vo circuits and confirm the incoming breaker trips on each.
A transfer like this is switching by the plant's switching order, not maintenance, and the conditions NFPA 70E, 2024 edition, sets for operating a switching device directly are the ones to check first; the article on NFPA 70E table limits for operating switchgear breakers walks through them. Any hands-on work inside the cubicles, relay injection or resistor inspection included, starts with the equipment de-energized, locked out and verified dead.
Questions asked
What voltage stress does an ungrounded stator see during a ground fault?
With the machine unreferenced, a single stator ground fault drives the two healthy phases to line-to-line voltage above ground, about 1.73 times their normal line-to-neutral value. Insulation, surge protection and any neutral-connected instrumentation on that machine must be rated for that displacement, and the fault keeps arcing until the machine is tripped and de-excited, because no relay sees a return current.
How does high-resistance grounding of the generator change the scheme?
Stator core damage limits often push generator grounding to a few amperes instead of a few hundred: a distribution transformer and secondary resistor on the machine neutral limit the primary ground current, and the stator ground relay is set to that small current. The generator-side neutral disconnect switch stays the default position; only its resistor value and relay settings differ from the bus resistor.
What changes if the generator has no neutral brought out?
A delta-wound or single-bushing machine still gets a grounding point on its own side: a grounding transformer, commonly zig-zag, connected at the machine terminals with the resistor on its neutral. That grounded assembly takes the place of the machine NGR behind the generator-side switch, and the same state table and interlock rule apply unchanged.
What must the neutral disconnect switch itself be rated for?
It carries no current while the system is healthy, so its continuous rating is modest, but it must stand the system line-to-line voltage across its open contacts and carry the designed ground-fault current for the clearing time the study gives, on a short-time duty basis. Confirm both against the switchgear and resistor documentation, and prove its position indication against the one-line.