Comparison
87T zone with a capacitor bank: outside, or separate CT inputs
Short answer
Keep the capacitor bank outside the 87T zone when the layout allows it. If it must sit inside, land the motor and capacitor CTs on separate 3-winding 87T restraint inputs instead of paralleling secondaries, and leave the bank neutral floating on the ungrounded delta motor side with 59N broken-delta detection for the first earth fault.
On this page
Keep the capacitor bank outside the 87T zone wherever the physical layout allows. If the bank must sit inside the zone, use a relay with a third restraint input and land the motor CT and the capacitor CT on separate inputs rather than paralleling their secondaries, because paralleling only sums correctly when both CTs share the same ratio and accuracy class. And keep the bank neutral floating: on an ungrounded delta motor side, a grounded wye bank grounds the whole system through capacitive reactance and destroys the availability the ungrounded arrangement was chosen for. Detect the first earth fault with 59N residual overvoltage from a broken-delta VT set, not with the differential or a phase overcurrent element, because the fault current is only the system charging current and is far too small for either to see.
What defines the 87T zone #
The differential zone is bounded by the current transformers on each winding. Current entering the zone must equal current leaving it; any difference beyond the relay's slope and pickup settings is a fault inside the zone. IEEE C37.96, the guide for AC motor protection, and IEEE C37.91, the guide for protective relaying of power transformers, both describe the scheme this way: the relay's selectivity is exactly as good as the CT placement, and every branch inside the CTs must have its current accounted for.
That definition decides the capacitor question immediately. A power-factor bank tapped between the transformer secondary CT and the motor terminal CT injects a current into the zone that the relay has no input for. The relay sees it as differential current that rises and falls with bank switching, and either you desensitize the 87T until it is useless or you misoperate on every bank energization.
Two arrangements compared #
| Arrangement | How the bank current is handled | When it works | Watch for |
|---|---|---|---|
| Bank outside the zone | Transformer secondary CT sits upstream of the bank tap; the bank gets its own CT, unbalance and overcurrent elements | Bank tap is physically upstream of the secondary CT, or the CT can be relocated | The zone shrinks to exclude the bank; bank faults need their own protection |
| Bank inside, separate relay inputs | 3-winding 87T: motor CT on one restraint input, capacitor CT on another; the relay applies ratio and vector compensation per input and sums in software | Motor and bank feeders are the only branches on that bus, and the relay has a free winding input | Any other load on the bus shows up as differential current; set each input's ratio separately |
| Bank inside, paralleled CT secondaries | Motor and capacitor secondary currents summed in one pair of conductors into a 2-winding input | Only with identical CT ratios, identical accuracy class, and low burden | Ratio mismatch between a bank-sized CT and a motor-sized CT produces false differential current that scales with load |
The outside-zone arrangement is the one to prefer: simplest, cheapest, and the 87T never has to know the bank exists. Take the inside-zone arrangement only when the layout forces the bank between the zone CTs and your relay has a third winding input. Reserve paralleling for the textbook case of matched CTs, which a motor-block layout almost never gives you.
The same two-core rule applies either way: the bank feeder CT needs one core for the capacitor relay functions (unbalance, phase overcurrent) and a separate core for the 87T if the bank is in the zone. The capacitor functions want a core sized and classed for the small steady bank current; the 87T core must survive motor locked-rotor current and transformer inrush without saturating. One core cannot serve both.
The arithmetic of the sum #
Inside the zone, the transformer secondary carries the phasor sum of motor and capacitor current. The motor current lags the bus voltage; the capacitor current leads it by close to 90 degrees. For a three-phase bank:
Ic = Qc / (√3 × Vll), with Qc in volt-amperes reactive and Vll in volts.
Worked example. A 1 MVar bank on a 4.16 kV motor bus:
Ic = 1,000,000 VA / (1.732 × 4160 V) = 138.8 A per phase, leading.
Suppose the motor draws 700 A per phase at 0.85 lagging power factor. Its reactive component is 700 × sin(31.8°) ≈ 369 A lagging. The bank subtracts 139 A of that, so the reactive component seen by the transformer falls to about 230 A, the real component stays at 700 × 0.85 = 595 A, and the transformer carries √(595² + 230²) ≈ 638 A instead of 700 A. That reduction is the whole point of the bank, and it is also why the two currents must be summed as phasors with correct ratio compensation per input, not added as scalars or forced through mismatched CTs in parallel.
For the transformer-side through-fault and CT sizing numbers that feed the 87T settings, the method in the transformer secondary fault current calculation article is the place to start.
Bank neutral: floating, on an ungrounded motor side #
With a delta transformer winding facing the motor bus and nothing grounded, the system carries no zero-sequence current, so the 87T needs no zero-sequence trap on that side. The first line-to-earth fault is limited to the system charging current, roughly Ig = 3 × ω × Cph × Vln, where Cph is the per-phase capacitance to earth of everything galvanically connected: cables, surge capacitors, the machine windings. On a medium-voltage motor bus that is typically a few amperes — orders of magnitude below any 87T or phase-overcurrent pickup.
Grounding the wye bank neutral connects that delta side to earth through the bank's capacitive reactance. A first earth fault now drives current through the bank, and the availability benefit of running through a first fault is gone. Keep the neutral floating.
Two consequences follow from a floating neutral:
- The bank needs its own unbalance protection, because a single ungrounded wye has no neutral current path to put a CT in. Set the unbalance element from the bank manufacturer's permitted voltage-shift or fuse-failure data, not from a generic percentage.
- First-fault detection must be by voltage, not current. Wire a 59N residual overvoltage element to a broken-delta VT set and alarm on the first earth fault; add a sensitive directional earth-fault element on the feeders if you need selectivity for the second fault. The pickup traps behind a 59N element are exactly the kind covered in the article on an earth fault setting that trips without a fault — residual circuits pick up standing system unbalance if you set them blindly.
Before touching anything inside the switchgear, de-energize the block, apply your lockout, and verify absence of voltage at each phase with a tested instrument; medium-voltage capacitor units hold a charge after isolation and need their designed discharge time and a verified discharge path before anyone opens a can or a fuse compartment.
Setting procedure #
- Read the transformer nameplate: vector group, rated MVA, both winding voltages. These fix the 87T's ratio and phase-shift compensation per input.
- Read the motor full-load and locked-rotor current from the motor datasheet, and the bank Qc and connection from the capacitor datasheet.
- Compute Ic from the formula above and the net transformer current at the operating point, as in the worked example.
- Specify two-core CTs on the bank feeder and separate motor CTs. Size each 87T core for the highest through-current it sees without saturating, including motor starting and bank energization; the CT test report gives ratio and class per core.
- If the bank is inside the zone, land motor and capacitor CTs on separate relay inputs and enter each input's ratio and winding assignment. If the relay has only two winding inputs, move the bank outside the zone instead of paralleling.
- Set the 87T slope and minimum pickup from the relay manual, including CT ratio mismatch and any tap-changer range. Enable second-harmonic inrush restraint and confirm in the manual how the relay behaves for capacitor-energization transients.
- Set the bank unbalance element from the manufacturer's data, wire the 59N to the broken-delta VT, and confirm the 59N alarms rather than trips for the first earth fault.
Commissioning checks #
- Secondary-inject each 87T input with balanced simulated through-current and confirm the measured differential current is near zero.
- Verify polarity and ratio on every core, including the capacitor core.
- With the bank de-energized and the motor running, read the relay's differential and restraint quantities; energize the bank and read them again. Differential should stay near zero in both states, and the net secondary current should drop by roughly the bank's reactive contribution — about 139 A primary in the worked example.
- Inject residual voltage on the 59N input and confirm alarm-only action.
- Trip-test the capacitor unbalance and phase-overcurrent elements from their dedicated core and confirm they do not operate the 87T output.
The decision, case by case: bank tap upstream of the secondary CT — take the outside-zone arrangement and protect the bank with its own CT and relay. Bank forced inside the zone and a three-input relay available — land the CTs on separate restraint inputs, never in parallel. Ungrounded delta motor side — leave the bank neutral floating, unbalance-protect the bank from its own data, and alarm the first earth fault with 59N.
Questions asked
What happens if the capacitor CT and motor CT have different ratios and are paralleled into one 87T input?
The parallel connection only adds correctly when both CTs produce the same secondary amperes per primary ampere. A bank CT sized for the small leading bank current and a motor CT sized for locked-rotor current do not match, so the sum carries a ratio error that the relay reports as differential current growing with load. Land each CT on its own restraint input with its own ratio setting instead.
Should the capacitor bank neutral be grounded when the motor side is ungrounded?
No, if the ungrounded arrangement was chosen for availability. A grounded wye bank ties the delta motor side to earth through capacitive reactance, so a first line-to-earth fault drives current through the bank and the run-through-fault benefit is lost. Keep the neutral floating and alarm on the first earth fault with a 59N element on a broken-delta VT.
Why can't the 87T or a phase overcurrent element detect the first earth fault on the ungrounded motor side?
On an ungrounded system a first line-to-earth fault carries only the system charging current, roughly three times omega times the per-phase capacitance to earth times the phase-to-neutral voltage, often just a few amperes on a medium-voltage motor bus. That is far below any differential or phase-overcurrent pickup, so detection must come from residual voltage, not residual current.
How much does a power-factor bank reduce the current the transformer actually carries?
The bank current leads the bus voltage by close to 90 degrees and subtracts from the motor's lagging reactive component. In the worked example, a 1 MVar bank at 4.16 kV contributes about 139 A leading per phase; if the motor draws 700 A at 0.85 lagging power factor, the reactive part falls by roughly that bank current and the transformer carries about 595 A instead of 700 A.