Motor differential CT saturation and C50 burden limits
Short answer
At the estimated 1030 A internal fault, the 100:5 A C50 core-balance CT driving a 2.35 ohm loop must develop roughly 121 V, about 2.4 times its 50 V class capability, so heavy saturation is the expected case. The differential element may still trip within the first cycles, but the feeder 50/51 elements on the phase CTs are the reliable backstop for high-magnitude internal and terminal faults.
On this page
- What a C50 rating actually guarantees
- The loop burden, not the nameplate, sets the demand
- The secondary voltage demand at 1030 A through a 2.35 ohm loop
- What saturation does to a fundamental-frequency relay
- Why the element can still win the race
- Where the feeder 50/51 backup carries the decision
- The decision, case by case
- Questions asked
Short answer: at the estimated internal-fault level, this CT cannot stay linear, so plan for saturation on high-magnitude internal faults and let the feeder 50/51 elements carry them. A 100:5 A C50 core-balance CT driving a measured 2.35 ohm loop would need roughly 121 V of secondary voltage at the estimated differential current, well past the 50 V its class guarantees, so the core saturates before the secondary current tracks the fault. That does not mean the differential element never trips on a large fault: saturation takes time, and an element responding to fundamental-frequency current can often decide within the first cycles. The worked numbers below show why, and the last section gives the decision for each case.
What a C50 rating actually guarantees #
IEEE C57.13, Standard Requirements for Instrument Transformers (2016 edition), pairs a classification letter with a secondary terminal voltage rating. For the C classification the secondary winding is distributed, so the excitation characteristic can be calculated from nameplate data, and the CT must hold its stated ratio accuracy up to the stated secondary terminal voltage: 50 V for a C50. A K classification adds a guaranteed excitation knee-point of at least 70 percent of that voltage rating, and a T classification must be demonstrated by test because its characteristic cannot be calculated from the nameplate alone.
The class number is a capability at the CT's secondary terminals under the standard's classification conditions. It is not a universal knee voltage, and it says nothing about your burden, your residual flux, or the DC offset in your fault. Confirm the rating against the standard edition the CT was purchased to and against the manufacturer's excitation curve for the actual unit.
The loop burden, not the nameplate, sets the demand #
Every ohm in series with the secondary circuit multiplies the secondary current into the voltage the core must support: lead resistance out and back, terminal blocks, any series devices, the relay input, and the CT's own winding resistance. That total, not the class letter alone, decides whether the circuit fits inside what the CT can deliver. Two effects push the core toward saturation faster than any resistive arithmetic shows: the DC component of an asymmetrical fault current, and residual flux left in the core by a previous event. Treat the resistive result as the best case, not the worst. For a deeper treatment of the same mechanism, the knowledge-base page on high nominal CT burden, saturation and accuracy works through how burden drives both accuracy and saturation. Before you open or re-measure a CT circuit, isolate it under your lockout procedure and verify absence of voltage, and keep the secondary shorted: never open-circuit an energized CT secondary.
The secondary voltage demand at 1030 A through a 2.35 ohm loop #
Inputs, each with its source:
- CT ratio 100:5 A, C50 classification, from the motor-end core-balance CT nameplates
- Assumed primary differential current of 1030 A, the estimate of at least 2.7 times the motor's full-load current, pending the short-circuit study. That figure implies about 381 A of full-load current; for a 3500 HP machine at 95 percent efficiency the input power is near 2.75 MW, which at 4160 V three-phase lands at roughly 381 A only around unity power factor, so read the actual nameplate current before any setting work
- Measured external loop resistance of 2.3 ohms, covering the complete outgoing and return wiring, terminals and relay input
- Corrected CT secondary winding resistance of 0.05 ohms; the first commissioning reading of 0.5 ohms was corrected in the record, and this example uses the corrected value
The rule in words: secondary current equals primary current divided by the ratio, and the voltage the CT must develop equals that secondary current times the total loop resistance.
The arithmetic:
- Ratio: 100 / 5 = 20
- Secondary current: 1030 A / 20 = 51.5 A
- External loop voltage: 51.5 A x 2.3 ohms = 118.45 V
- Winding-resistance voltage: 51.5 A x 0.05 ohms = 2.575 V
- Total demand: 51.5 A x 2.35 ohms = 121.025 V, about 121 V
Result: the demand is roughly 2.4 times the 50 V the C50 classification represents. These are resistive screening numbers, not a transient saturation model, and any impedance not measured resistively must be added in its proper representation. The decision this leads to: at any differential current near this estimate, assume the core saturates heavily. Get the CT excitation curve and complete an application check instead of accepting the nameplate class. When you need the burden spelled out step by step, the knowledge-base article on current transformer burden calculation for saturation avoidance covers the same quantity for a relay circuit.
What saturation does to a fundamental-frequency relay #
Once the core saturates, the secondary waveform collapses into narrow spikes clustered near the current zeros, and the fundamental-frequency component stops growing with the primary fault. A relay that filters and responds to fundamental-frequency current only, as this installation's motor protection relay does, therefore sees an operating quantity that stalls even as the true fault current rises: the relay reads less than the conductor carries. Two practical checks follow. Compare the relay's filtered current with the raw secondary waveform rather than trusting the displayed value alone, and do not accept a sinusoidal secondary-injection test as proof, because a clean injection never exercises saturation and demonstrates nothing about it.
Why the element can still win the race #
A CT does not saturate at the instant of fault inception. The core starts with usable flux headroom, and how long that headroom lasts depends on the fault inception angle, the burden, the remanent flux and the degree of asymmetry. An instantaneous differential element that decides within the first cycles can trip on a genuinely large internal fault before the waveform collapses, which is the same behavior that makes core-balance CTs workable on feeder protection. The operative word is can. With demand this far past the class rating, tripping before saturation is plausible rather than assured, and only a saturation study built on the real excitation curve and the measured burden settles it for your circuit.
Where the feeder 50/51 backup carries the decision #
The phase CTs at the contactor end, with their 50/51 elements, are the protection that does not depend on the core-balance CTs staying linear. Set the phase instantaneous pickup above the maximum starting current, and coordinate the time element with the study. The motor sits 1000 feet from the contactor, so the feeder cable impedance stands between the protection point and the machine: model the cable explicitly and do not treat the two terminals as one electrical node. If you need the source impedance the study starts from, the article on calculating source impedance from prospective short-circuit current shows the method, and the article on setting 50 and 87 functions on a fused medium-voltage motor starter covers how the instantaneous element relates to starting current on this class of equipment.
For the motor's own contribution, use the machine reactance from the study. As an illustrative screening case only: taking the stated 0.18 per unit value as 1.133 ohms on the 6.29 ohm base, applying nominal phase voltage across that reactance alone and neglecting resistance gives 4160 V / (1.732 x 1.133 ohms), or roughly 2120 A. That is not the total internal phase-fault current: the source contribution, the fault topology and the decay of the motor's own current all need the short-circuit study, which the engineering team running it should confirm with the motor manufacturer's fault-contribution model.
The decision, case by case #
- Keep the differential scheme. Low-level internal faults produce secondary currents the loop handles easily, and large faults often trip in the first cycles before the core saturates. Confirm both behaviors with the CT excitation curve and a saturation study using the measured burden.
- Treat high-magnitude internal and terminal faults as the feeder 50/51's job. Its phase CTs have the ratio headroom, its instantaneous element rides above starting current, and its coordination must include the feeder cable and source impedance rather than a single lumped bus.
- Cut the burden where you can. Correct poor terminations, check lead routing and conductor size, remove unnecessary series devices, then re-measure the loop with the circuit isolated and shorted, and recalculate the demand before returning the scheme to service.
- Replace the CTs only if the study confirms demand past the class rating at maximum fault duty. A higher class or a higher ratio buys voltage capability, but check sensitivity to the minimum differential fault current before committing, because the same change weakens the low-level signal the differential element depends on.
Questions asked
Would a higher CT ratio reduce the saturation risk?
Yes, mechanically: the voltage demand scales with secondary current, and a higher ratio lowers secondary current for the same primary fault, so a 200:5 CT in the same loop would see roughly half the demand voltage. The cost is sensitivity, because a smaller differential current delivers less secondary signal, so the relay's minimum pickup must still clear the smallest fault you want caught. Compare excitation curves and pickup settings, not just ratios.
What is the difference between C, K and T classifications?
IEEE C57.13 designates relaying accuracy classes by a letter plus a secondary terminal voltage rating. C and K windings are distributed so the excitation characteristic can be calculated from nameplate data; K additionally guarantees a knee-point at least 70 percent of that voltage rating. A T winding's characteristic cannot be calculated that way and must come from test. Confirm the exact class behavior against the standard edition your CT was purchased to.
Does fault-current DC offset change the arithmetic?
It makes it worse. The resistive calculation assumes symmetrical sinusoidal current, while a fault that starts with maximum asymmetry carries a decaying DC component that drives core flux well past what the RMS secondary current implies, and remanence from an earlier through-fault adds to that. With demand already past the class rating there is no margin left, which is why the resistive result should be read as the best case.