Current IntelPower LibraryShop main store

Explainer

Arc flash labels for a dual-source VFD cabinet

Electrical safety and codes Published 9 min read By Current Intel engineering team

Short answer

If opening the cabinet can expose the line-side terminals of both drives, apply one bounding arc flash label: the largest calculated incident energy at an 18 in working distance and the highest nominal voltage present, whatever source each number comes from. Keep both source-specific calculations in the incident energy analysis report so the energized work permit uses the case that fits the task.

On this page
  1. Which arc flash label covers a cabinet with two VFD power sources?
  2. What does the code require the label to show?
  3. When does a two-source cabinet need two labels instead of one?
  4. How do you pick the bounding numbers when the two calculations differ?
  5. Can a drive's output limit or DC link justify a smaller label?
  6. Does the label cover the energized work permit and PPE choice?
  7. How long does the label stay valid?
  8. Questions asked

A cabinet that holds two drives fed from two different sources does not get two labels pasted side by side, and it does not get an average of the two results. If one opening exposes the line side of both drives, the cabinet carries one bounding arc flash label: the largest calculated incident energy at the study's working distance and the highest nominal voltage present, each taken from whichever source produces it. Both source-specific calculations stay in the incident energy analysis report, where the energized work permit picks the case that fits the task. NFPA 70E, 2024 edition, and NEC 110.16, NFPA 70, 2023 edition, set what that label must show. This article walks through the labeling decision, works the bounding numbers with real arithmetic, and marks the points where one label stops being enough.

Which arc flash label covers a cabinet with two VFD power sources? #

Apply one label that carries the largest calculated incident energy at the accessible parts and the highest nominal voltage present, and keep both source-specific calculations in the incident energy analysis report so the energized work permit can use the case that fits the task.

Each source feeds one calculation case at the cabinet, and the label has to describe what a worker meets when the door opens, not what a single feeder does. When one access exposes both drive line sides, the worker can meet either case, so the label states the worst of each quantity, taken independently — the largest incident energy and the highest voltage rarely come from the same source. Never average the two results and never print a number between them: an average can only understate one case, and the permit has to test the task against the real governing value.

Both cases behind the label go into the incident energy analysis report under the cabinet's equipment identifier, so the energized work permit compares the planned task against each one and takes the governing number.

What does the code require the label to show? #

NEC 110.16, NFPA 70, 2023 edition, requires a field-applied warning label on industrial control panels likely to be serviced energized, carrying the nominal system voltage, the incident energy with its working distance or the NFPA 70E PPE category, and the analysis date.

NEC 110.16 applies to switchboards, switchgear, panelboards, industrial control panels, meter socket enclosures and motor control centers likely to require examination, adjustment, servicing or maintenance while energized, and a two-drive process cabinet is an industrial control panel in that list. NFPA 70E, 2024 edition, Section 130.5(H), requires field marking wherever an arc flash hazard exists, with a label that carries at least the available incident energy and its working distance, or the arc flash PPE category (but not both), plus the nominal system voltage, the assessment date, and an equipment identifier tying the label to its line in the study.

Keep one method per piece of equipment: a label stating a calculated incident energy is worked from that analysis and its PPE, not from the PPE category tables. The 2026 NEC revises arc flash labeling details, so confirm which edition your jurisdiction enforces, and confirm the exact marking text with your authority having jurisdiction and the equipment documentation.

When does a two-source cabinet need two labels instead of one? #

Two labels are warranted when separate barriers or compartments create two distinct accessible sections, each reached without opening the other, so a worker meets one source at a time; one shared opening that exposes both line sides takes the single bounding label.

Walk the cabinet as built, locked out and verified dead. Many drive cabinets give each drive its own line-side compartment behind a separate door or dead-front cover; where a barrier forces a second access before the second source's conductors are reachable, each section is evaluated and labeled for the source it exposes, and the report ties each label to its source and protective breaker. Where a shared compartment, one open door or a removed cover puts both line sides within reach, the single bounding label governs.

Reachable line sides are a credible energized exposure even when the drives themselves are only worked de-energized, because checking a feeder for the presence of voltage is a routine troubleshooting call. If no energized access is credible — everything stays behind covers that are never removed hot — the analysis still holds both cases and records that access assumption, which the next review re-tests.

How do you pick the bounding numbers when the two calculations differ? #

Take the largest incident energy and the highest nominal voltage independently of which source each comes from: in the worked example below that is 5.8 cal/cm² at an 18 in working distance for the energy and 480 V for the voltage, one number from each source.

The example is illustrative and every input is stated: Drive 1 is fed from a 480 V motor control centre feeder, case A in the study, and Drive 2 is fed from a 240 V panelboard feeder, case B, with one opening exposing both. At an 18 in working distance the study reports 1.9 cal/cm² for case A and 5.8 cal/cm² for case B.

Case Source Nominal voltage Incident energy at 18 in Arc flash boundary
A: Drive 1 line side Motor control centre feeder 480 V 1.9 cal/cm² 21 in
B: Drive 2 line side Panelboard feeder 240 V 5.8 cal/cm² 31 in

Each boundary is solved from the same study values with the inverse-cube working-distance relationship used with IEEE 1584 results: incident energy falls with the cube of distance, so the arc flash boundary equals the working distance multiplied by the cube root of (incident energy ÷ 1.2), where 1.2 cal/cm² is the onset of a second-degree burn that NFPA 70E uses to set the boundary, distances in inches and energies in cal/cm².

Case A: 18 × (1.9 ÷ 1.2)^(1/3) = 18 × 1.165 = 21.0 in, printed as 21 in. Case B: 18 × (5.8 ÷ 1.2)^(1/3) = 18 × 1.691 = 30.4 in, printed as 31 in; boundaries round up.

The cabinet label therefore reads: 480 V nominal, the case B incident energy with its working distance, the 31 in arc flash boundary, the assessment date and the equipment identifier. The energy and boundary come from case B and the voltage from case A, and the 31 in boundary also bounds case A because it is the larger one. If the permit's task works at a 12 in working distance, the bounding case scales to 5.8 × (18 ÷ 12)^3 = 19.6 cal/cm², which is why the report keeps both cases rather than only the label line. Treat the boundary and scaling results here as a cross-check: the study report prints the governing values directly, and IEEE 1584, 2018 edition, with NFPA 70E, 2024 edition, govern the method behind them.

It cannot: the label is set by the calculated incident energy at the exposed line-side terminals, and a drive's rated output current and stored DC-link energy are not an arc-flash reduction the analysis recognizes unless the study models that drive topology from its documentation.

An incident energy analysis credits a current-limiting effect only when the study models that device's documented behavior. A drive's rated output current is a continuous rating backed by the drive's own protection scheme in its documentation; it is not an upstream arc-flash current limiter, and no generic multiplier turns it into one. The line-side case, computed from each source's available fault current and its protective breaker, sets the label for line-side work, which is what the two-source question is really about. For the output terminals, the governing case is whatever the study calculated there; if the study never analyzed the output side, that is a gap in the analysis to close, not permission to write a smaller number off the drive nameplate.

Safety note: treat every opening of this cabinet as energized until proven otherwise. De-energize both sources, lock and tag, wait the drive documentation's DC-link discharge interval, then test for absence of voltage on the line terminals, the DC bus and the output terminals before any contact. The verification step carries its own incident energy question, covered in What incident energy applies to a LOTO voltage test on a breaker.

Does the label cover the energized work permit and PPE choice? #

No: the label is the field summary, and the permit picks the applicable source case from the report for the actual task and working distance, where a shorter distance raises the incident energy well above the number on the label.

The permit compares the planned task — actual working distance, posture, whether one source is opened and locked out — against both retained cases and takes the governing result, and PPE follows that task-specific number. The label's value is only valid at its printed working distance with both sources in service.

NFPA 70E allows one label to carry shock and arc flash data together, and the conditions are laid out in Shock and arc flash data on one equipment label: what NFPA 70E allows. The boundaries the permit has to establish around the job are worked through in the knowledge base article clarifying NFPA 70E energized work permit boundaries. And whether a task can follow the PPE category tables or must ride the analysis is the subject of When NFPA 70E task tables apply to your equipment.

How long does the label stay valid? #

NFPA 70E, 2024 edition, has the incident energy analysis reviewed for accuracy at intervals not exceeding five years and updated whenever the distribution changes, and the label date must be renewed with it because NEC 110.16 puts the assessment date on the label.

A review at the five-year mark re-runs both cases, because upstream changes move them independently: a utility transformer upgrade can raise one source's energy while a breaker replacement can cut the other's, and the bounding number can flip from one source to the other. When the bounding set changes, the label is re-issued with a new date, and the superseded report stays on file so earlier permits trace to the numbers they used. Adding a third drive on a third source is a change to the distribution, not a new label on the old analysis: the new case enters the study and the bounding set is recomputed before the cabinet is worked energized again.

The decision in one line: one opening that exposes both line sides takes one bounding label — the larger incident energy with its working distance, the higher nominal voltage, the larger boundary, the assessment date and the equipment identifier — with both source cases retained in the report; separate accessible sections each take the label of the source they expose.

Questions asked

Can I print both incident energy values on one label?

Yes, if the layout keeps the two cases unmistakably separate, each with its own voltage, incident energy, working distance and boundary, and the equipment identifier ties them to the report. Many plants still choose the single bounding number because a two-value label invites the reader to pick the smaller one during a task. Either way the label date covers both cases and the report holds both calculations.

What happens to the label when one source is locked out?

The label stays unchanged because it marks the worst credible case with every source available. The energized work permit and the lockout record document which source is isolated for the task at hand. Verify absence of voltage on the conductors being approached, and treat the drive's DC bus with respect: its capacitors can hold a charge after the supply opens, so follow the drive documentation's discharge interval and verification steps before touching terminals.

How does a shorter working distance change the incident energy on the label?

Incident energy scales with the inverse cube of the distance from the arc, so halving the working distance multiplies the energy by eight and doubling it divides the energy by eight. Recompute each source case in the report at the permit task's actual distance and select PPE from that task-specific value rather than from the label number, which is only valid at the printed working distance.

Who decides that both line sides are exposed by one opening?

The engineer who owns the incident energy analysis decides, against the cabinet as built. With every source de-energized, open each door and remove each barrier the way maintenance would and record which conductors become reachable. One reach that touches both line sides forces the single bounding label; a physical barrier that forces a separate access for each source supports a label per section.

Keep reading

  • Explainer

    NFPA 70E table limits for operating switchgear breakers

    NFPA 70E's table method is bounded by available fault current, clearing time and working distance, not by the main breaker's ampere rating. A large continuous rating alone does not put switchgear outside the tables; the real gate is the calculated fault duty and the clearing time of the device that clears. When either exceeds the table limits or cannot be determined for lack of data, the compliant routes are the normal-operation exception for door-closed switching and an incident energy analysis of that switchgear.

    Electrical safety and codes

  • Explainer

    Shock and arc flash data on one equipment label: what NFPA 70E allows

    Yes. NFPA 70E, 2024 edition, does not require a separate shock label: Section 130.5(H) lists what the arc flash label must contain and leaves room for optional shock fields. Put the nominal voltage, arc flash boundary, incident energy and PPE on one legible 4 by 6 inch label, add the limited and restricted approach boundaries under their own shock heading, and print two labels only when the combined layout gets cluttered.

    Electrical safety and codes

  • Explainer

    When a 277 V monitoring enclosure needs an arc flash label

    A monitoring enclosure fed at 277 V inherits no label from the upstream gear and earns no exemption from its 125 V control circuits, because NFPA 70E draws the shock threshold at 50 V. The enclosure carries an arc flash label only when the electrical safety program permits a task that exposes the supply terminals energized; otherwise the de-energize-first decision is documented and no label is required.

    Electrical safety and codes