Explainer
Shock and arc flash data on one equipment label: what NFPA 70E allows
Short answer
Yes. NFPA 70E, 2024 edition, does not require a separate shock label: Section 130.5(H) lists what the arc flash label must contain and leaves room for optional shock fields. Put the nominal voltage, arc flash boundary, incident energy and PPE on one legible 4 by 6 inch label, add the limited and restricted approach boundaries under their own shock heading, and print two labels only when the combined layout gets cluttered.
On this page
- Does NFPA 70E allow shock and arc flash data on one label?
- What must an arc flash label contain?
- What shock data belongs on the same label?
- Are the shock boundaries and the arc flash boundary the same thing?
- Do transformer size exemptions still excuse small panels from arc flash labels?
- Will shock and arc flash fields fit on a 4 by 6 inch label?
- When should you print two labels instead of one?
- How often does a combined label need updating?
- Questions asked
The shock hazard analysis and the arc flash risk analysis stay separate studies, but nothing in NFPA 70E, 2024 edition, forces you to separate their printouts. The standard tells you what an arc flash label must carry, where it must sit, and when it must be refreshed; it never demands a second label for shock data. So the practical answer is one combined label: the required arc flash fields on top, the limited and restricted approach boundaries and the nominal voltage grouped under a shock heading below, everything sized to stay legible. This article walks through the required content, the shock fields worth adding, why the boundary names must never blur into each other, and the arithmetic that shows a combined layout fits the standard 4 by 6 inch blank.
Does NFPA 70E allow shock and arc flash data on one label? #
Yes, NFPA 70E, 2024 edition, requires one marked arc flash label on the equipment with a defined list of fields and never a separate shock label, so a combined label is compliant when every required field stays legible and each boundary is named for the hazard it controls.
Section 130.5(H) is a content and placement rule, not a layout rule. It neither asks for shock data nor forbids it, so the extra fields are the label designer's call. Combined layouts are common practice across arc flash study software precisely because the standard is silent on them: printing the shock block adds helpful information without touching a required field.
The combined label stays compliant only while every required field stays legible. If the shock block crowds the incident energy line into unreadable type, the layout has started costing compliance, and that is the point to split it, not before.
What must an arc flash label contain? #
NFPA 70E, 2024 edition, Section 130.5(H) sets the floor: the nominal system voltage, the arc flash boundary, and at least one value from a short list that ranges from incident energy at a stated working distance to a site-specific level of PPE. Those three lines are the label's non-negotiable content.
- Nominal system voltage, the voltage the analysis was run at.
- Arc flash boundary, the distance at which the analysis says incident energy falls to the burn-onset threshold.
- At least one of the following: the available incident energy and its corresponding working distance, or the arc flash PPE category for the equipment, with the standard offering incident energy or category but not both, or else the minimum arc rating of clothing or a site-specific level of PPE.
Section 130.5(H) names where the marking belongs: switchboards, panelboards, industrial control panels, meter socket enclosures and motor control centers in other than dwelling units, whenever that equipment is likely to require examination, adjustment, servicing or maintenance while energized, with the label clearly visible to a qualified person before that work starts.
A workable label also carries an equipment identifier and the study date, because a field with no name and no date cannot be checked against the study report that produced it. When the label carries incident energy, the clothing decision follows from that number, and the incident energy to PPE level selection guide walks the mapping from cal/cm² into arc-rated clothing categories.
Editions and local amendments differ. Confirm the field list against the edition your jurisdiction adopts, with your authority having jurisdiction, and with the equipment documentation.
What shock data belongs on the same label? #
The shock hazard analysis applies at 50 V and above, and Section 130.4(D) makes you identify a limited approach boundary and a restricted approach boundary from the nominal voltage; those two distances are the shock fields worth printing beside the arc flash data.
Section 130.4(D) sends those boundaries to Table 130.4(E)(a) for AC systems and Table 130.4(E)(b) for DC, both keyed to nominal voltage. The same voltage always produces the same two boundaries, which is why they survive being printed once on a label.
The distances read straight from the table. For a 240 V panelboard, the table sets the limited approach boundary at 3 ft 6 in (1.0 m) for exposed fixed circuit parts, with an 'avoid contact' restricted approach boundary; at higher nominal voltages the limited boundary grows and the restricted boundary becomes a stated distance instead of an instruction. NFPA 70E puts these boundaries on the qualified person rather than on the label, so printing them is optional, but keep them. A boundary re-derived from memory at an open door under time pressure is the one most often misremembered, and the label's job is to remove exactly that kind of recall.
Are the shock boundaries and the arc flash boundary the same thing? #
No, the limited and restricted approach boundaries control how close a person gets to energized parts for shock protection, while the arc flash boundary marks where incident energy drops to 1.2 cal/cm², the onset of a second-degree burn; different hazards, different distances, different PPE logic.
| Boundary | What it controls | Where the number comes from |
|---|---|---|
| Limited approach boundary | The closest approach for shock protection, for any person | Table 130.4(E)(a) or (E)(b), by nominal voltage and exposure type |
| Restricted approach boundary | The inner shock limit, inside which only qualified persons work with insulated tools and PPE | Same tables, by nominal voltage |
| Arc flash boundary | The distance where the thermal energy of an arc falls to 1.2 cal/cm² | The incident-energy analysis for that specific equipment |
The two families answer different questions and rarely produce the same distance. On a high-energy switchboard the arc flash boundary can sit well beyond the shock boundaries; on a small panelboard the order can reverse, with the arc flash boundary inside the limited approach boundary. That spread is why each boundary on the label must be named for its own hazard: a worker who reads a bare boundary distance with no owner walks away with one number standing in for two.
For who may cross each approach boundary and what changes at the line, the guide to NFPA 70E approach boundaries and shock limits covers that ground in detail.
Do transformer size exemptions still excuse small panels from arc flash labels? #
No, the transformer-kilovoltampere cutoffs that older editions carried as informational guidance no longer appear in NFPA 70E, so a 208 or 240 volt panel fed from a small transformer earns its label the same way every other panel does: from the analysis, not a nameplate shortcut.
The cutoffs in older notes were informational language, a transformer rating near 125 kVA with a voltage ceiling, carried through editions before 2015. That text described when an arc flash hazard might not exist; it was never a labeling exemption, and Article 130.5 in the current edition carries no such cutoff. Whether a small panel holds an arc flash hazard is a result the incident-energy analysis produces from the actual source impedance, conductor sizes and clearing times, numbers no nameplate rule can stand in for. The walkthrough of arc flash risk in 240 V and lower panels shows what that evaluation looks like when the supply transformer is small.
The decision is the same as for any other panel: run the analysis, print the label from its output, and let the shock fields ride along because the nominal voltage clears 50 V.
Will shock and arc flash fields fit on a 4 by 6 inch label? #
Yes, with room to spare: a worked layout below puts ten data rows and a signal-word header on a 4 in by 6 in label in 3.0 in of stacked rows against 5.25 in of usable height, and the arithmetic shows where those numbers come from.
Worked example, with illustrative inputs: a 4 in wide by 6 in tall blank, a signal-word header band across the top, and twelve-point type throughout.
- Header band: 4 in × 0.75 in = 3 sq in of the 24 sq in blank.
- Rows to place: equipment identifier, nominal system voltage, arc flash boundary, incident energy at working distance, working distance, minimum arc rating, PPE description, limited approach boundary, restricted approach boundary, study date, ten rows in all.
- Usable height below the header: 6 in − 0.75 in = 5.25 in.
- Row height at twelve-point type with normal leading: 0.30 in per row, so ten rows stack to 10 × 0.30 in = 3.0 in.
Ten rows at 3.0 in sit inside 5.25 in of usable height with 2.25 in left over, and 3.0 ÷ 5.25 ≈ 0.57 says the combined layout uses about 57 percent of that height. The stress case is line-side and load-side data: printing each side separately adds a second boundary line, a second incident energy with working distance, a second arc rating and a second PPE line, so 14 × 0.30 in = 4.2 in, and 4.2 ÷ 5.25 = 0.80 still fits. Area is not the binding constraint; legibility is. Print at final size, then read every field from the working distance under the lighting the equipment actually gets, and treat any line that needs a squint as a failed layout. This arithmetic checks the layout only; the boundary and energy values themselves come from the analysis and the tables.
When should you print two labels instead of one? #
Split the data only when the printed layout hides or confuses a required field: two nominal voltages on one structure, line-side and load-side results that double the arc flash rows, or a small enclosure door that cannot carry a full-size label without blocking the nameplate.
- Two voltages on one structure, a 480 V switchboard with 120/208 V control power sections for example, needs a boundary set per voltage. Print one arc flash label per voltage with its own shock fields; merging them puts two different distances under one word.
- Line-side and load-side results on transformer secondaries and switchboards deserve their own layout decision, and the walkthrough on labeling transformer secondaries and switchboard line sides covers where those labels go.
- A door too small for the full blank: keep the required 130.5(H) fields on the equipment and move the optional shock block to the study report or to a second label mounted beside, never dropped.
The governing rule either way: required fields first, optional shock fields second, and a split the moment legibility drops. One safety note belongs beside this work: affixing a label means opening an enclosure, so de-energize it and verify absence of voltage before the door comes open, or treat the approach under the boundaries the label itself states.
How often does a combined label need updating? #
Section 130.5(E) caps the review interval for the arc flash risk analysis at 5 years and requires a refresh after any major modification or renovation, and the label has to follow the study; a label stamped with a study older than that interval is the field version of a stale result. Utility available fault current changes, a feeder breaker replacement that moves the clearing time, or a renovation all pull the review date closer than the maximum.
The decisions, case by case:
- A typical switchboard, panelboard or MCC with one voltage and one set of values: one combined label in the worked-example layout, required fields on top, the two shock boundaries under their own heading.
- Dual-voltage equipment or equipment with distinct line-side and load-side results: one arc flash label per voltage or per side, shock fields on each, no merged block.
- Any label still citing pre-2015 field lists or transformer-size exemptions: re-verify the study against NFPA 70E, 2024 edition, and reprint before the next scheduled work on that equipment.
Print the combined label, prove it reads cleanly from the working distance, and keep the study report it came from. That is the whole job.
Questions asked
What happened to the prohibited approach boundary on older labels?
The 2015 edition of NFPA 70E removed the prohibited approach boundary from the shock scheme, so the current tables define only the limited and restricted approach boundary. A label produced under an earlier edition that lists three shock boundaries is a reprint candidate: have the study re-verified against the current edition and reprint it with the two boundaries the current table defines.
Does the limited approach boundary depend on which part of the equipment you face?
Yes. The shock table splits each voltage range into exposed movable conductors, such as exposed cable or movable parts, and exposed fixed circuit parts, such as bus behind a panelboard face, and the limited approach boundary can differ between the two columns. Confirm which exposure applies to the working face before the number is printed on a combined label.
Can the label show a PPE category instead of an incident energy value?
Yes. Section 130.5(H) requires at least one of several values and allows either the incident energy with its working distance or the arc flash PPE category, but not both. A category comes from the PPE category tables and holds only while the equipment and task match the table conditions; an incident energy result from the analysis carries no such conditions and leaves the field crew one less lookup.
Does NFPA 70E set a required label size or font?
No. The standard sets the content, the placement and the duty to keep the information current; it does not set dimensions, typeface or colors. The 4 by 6 inch blank is industry practice, sized because it holds the required fields legibly. Any size works as long as a qualified person can read every required field before starting the task.