Building a dry-type transformer damage curve for coordination

Protection: breakers, fuses and SCCR Published 7 min read

Short answer

Use IEEE C57.12.59, the guide for dry-type transformer through-fault current duration, together with the manufacturer's winding withstand data — never the liquid-immersed curves of IEEE C57.109. Plot the boundary on the current that actually flows in the protected winding, add relay plus breaker clearing time, and keep total clearing below the boundary across the whole through-fault range.

On this page
  1. The guide that matches the winding construction
  2. What to collect before drawing anything
  3. Worked example: base currents for an autotransformer
  4. Plotting the boundary and the protection
  5. Verify the plot before trusting it
  6. The decision, case by case
  7. Questions asked

The damage curve for a dry-type transformer comes from IEEE C57.12.59, the guide for dry-type transformer through-fault current duration, read together with the manufacturer's winding withstand data — not from IEEE C57.109 or IEEE C37.91, which serve liquid-immersed transformers. Plot the boundary on the current that actually flows in the winding you are protecting, not on terminal kilovolt-amperes alone, then overlay the total clearing time of the relay plus the breaker: the protection must interrupt every studied through fault before the boundary, from the smallest case to the largest. The procedure below includes a worked base-current example for a 950 kVA dry-type autotransformer.

The guide that matches the winding construction #

IEEE C57.12.59, Guide for Dry-Type Transformer Through-Fault Current Duration, sets recommendations for the overcurrent protective devices that limit how long a dry-type distribution or power transformer carries through-fault current. It was first published in 1989 and revised twice; the 2015 revision is the edition to coordinate against unless your study contract names another. Confirm the governing edition with the authority having jurisdiction and the equipment documentation.

IEEE C57.109-2018 is a similarly shaped document for a different technology: it presents through-fault duration and coordination curves for liquid-immersed transformers, sorted into the categories defined for that construction. IEEE C37.91, the guide for protecting power transformers, is the relaying document engineers read alongside it. Borrowing those curves for a dry-type unit puts oil-immersed winding withstand on your plot — different thermal mass, different mechanical structure, no defensible margin in either direction. That includes the cumulative damage accounting kept under the IEEE C57.109 cumulative damage program: it tracks exposure for liquid-immersed units and does not stand in for a dry-type boundary.

Through-fault damage also has two parts — heating that accumulates roughly as I²t, and electromagnetic forces that scale with the square of the instantaneous current. The published points therefore bend; they are not one straight line you can extend by hand past the last point the source document gives.

What to collect before drawing anything #

From the nameplate: rated kilovolt-amperes, every terminal voltage, the connection — two-winding, autotransformer, tap arrangement — impedance and cooling class. From the manufacturer: winding withstand or damage data, if published, and the basis of its current axis, whether amperes or multiples of a named winding's rated current. Read the axis label before you transpose anything, because a curve entered on the wrong basis shifts by the ratio of the two base currents.

From the study: the CT ratio and its location, the relay curve family and settings, the breaker's interrupting time, and the maximum and minimum through-fault cases. Keep RMS symmetrical current, asymmetrical current and peak current distinct, and convert between them only by the method the guide or the manufacturer's data defines.

Worked example: base currents for an autotransformer #

Example inputs, stated so you can check every step: a three-phase dry-type autotransformer rated 950 kVA, stepping 13.8 kV down to 4.16 kV, 60 Hz. These are illustrative values; substitute your own nameplate. The base current comes from the nameplate and the standard three-phase relation I = S ÷ (√3 × V_LL), with S in volt-amperes, V_LL in volts and the result in amperes; for a single-phase unit it is I = S ÷ V.

  • High-voltage terminal: I_H = 950,000 ÷ (1.732 × 13,800) = 950,000 ÷ 23,902 = 39.7 A
  • Low-voltage terminal: I_L = 950,000 ÷ (1.732 × 4,160) = 950,000 ÷ 7,205 = 131.9 A

At rated load an ideal autotransformer splits the current this way: the series winding carries the high-voltage terminal current, 39.7 A, and the common winding carries the difference between the terminal currents, 131.86 − 39.74 = 92.1 A. The low-voltage terminal delivers 131.9 A, but the common winding inside sees only 92.1 A — a boundary drawn on the terminal base overstates that winding's stress by 43%. On a two-winding dry-type unit the terminal base and the winding base coincide; on this construction they do not.

Under fault conditions the split moves with fault location, fault type and tap position, and some terminal faults load a winding far beyond these rated-load relations. Translate each studied fault into winding currents from the connection, the ratio and the tap, and let the manufacturer's winding data decide the withstand. Treat the numbers above as an estimate to be checked against the nameplate and the equipment documentation.

Plotting the boundary and the protection #

  1. Fix one current basis for the whole plot — for example, common-winding amperes — and write it on the axis. Everything on the plot converts into that basis or stays off it.
  2. Enter the boundary points from IEEE C57.12.59-2015 for the transformer's rating category, plus the manufacturer's winding curve where one exists, without altering their current basis. Where the two disagree, the lower curve is the boundary.
  3. Calculate the maximum through-fault current — a bolted three-phase fault at the protected terminals — from the transformer impedance: the method in Calculating transformer interrupting current from impedance gives that number.
  4. Calculate the minimum case with the source impedance included, because the protection must still clear a light fault before the boundary: the method in Calculating low-side fault current with source impedance covers it.
  5. Convert each studied case from terminal current to the plotted winding's current using the connection, the ratio and the tap, and record the conversion beside the plot.
  6. Plot the relay on the same basis: the secondary pickup in amperes times the CT ratio gives primary amperes, and operating times come from the relay's published curve at each multiple of pickup.
  7. Add the total clearing time: relay operating time plus the breaker's interrupting time. The trip instant is not clearing until the breaker has interrupted.
  8. Check every current between the minimum and maximum cases: total clearing must stay below the boundary throughout, while remaining selective with any downstream device that is meant to clear first. Never extend a curve segment beyond its last published point.

Verify the plot before trusting it #

Trace one point end to end, with example settings that are illustrative only: a 150:5 CT on the 4.16 kV terminal, a multiplier of 30, and a phase relay set to a 3.0 A secondary pickup, which is 90 A of terminal current. The studied fault is 1,320 A at that terminal, about ten times its rated current.

The CT secondary then carries 1,320 ÷ 30 = 44 A, which is 44 ÷ 3.0 = 14.7 times pickup; the relay's published curve for those example settings gives 0.42 s to close its output contact, the breaker adds 0.05 s — three cycles at 60 Hz — and the total is 0.47 s. That point, 1,320 A at 0.47 s, must sit below the boundary on the terminal axis and at its winding-current translation on the winding axis, and the same coordinates must come out of the study software and the hand-drawn plot.

Secondary injection verifies the relay pickup and timing, and the breaker's timing test report verifies its clearing. De-energize the circuit and verify absence of voltage before opening the relay or CT wiring, and never open a CT secondary circuit while primary current flows. One thing no field test does is validate the damage boundary: the boundary is documentation, and it stays tied to the guide edition and the manufacturer data you plotted it from.

The decision, case by case #

Two-winding dry-type unit on a standard rating: the IEEE C57.12.59-2015 curve for its rating is the damage boundary, and your coordinated relay-plus-breaker clearing time must sit under it from the smallest to the largest studied fault. Autotransformer or tap-winding construction: the same guide as the framework, plus the manufacturer's winding withstand data, plotted on the winding current — where the terminal base and the winding base disagree, the winding basis decides, as the 92.1 A common-winding example shows. Any dry-type unit: never the C57.109 or C37.91 curves, and if an existing study borrowed them, redraw the boundary before trusting its margins.

Questions asked

Can I use the IEEE C57.109 curve as a conservative stand-in for a dry-type transformer?

No. IEEE C57.109-2018 is the through-fault duration guide for liquid-immersed transformers; its categories and curve points describe oil-immersed winding behavior, not dry-type. Nothing guarantees it sits below the dry-type boundary at any point, so treating it as conservative is itself an unverified claim. Build the boundary from IEEE C57.12.59-2015 and the manufacturer's winding data instead.

Which edition of IEEE C57.12.59 should a study reference?

The guide was first published in 1989, revised in 2001 and again in 2015, and the 2015 revision is the latest edition. Older study files may cite the earlier texts, so check any curve values taken from them against the edition your study applies, and confirm the governing edition with the authority having jurisdiction and the study contract.

Can the damage curve come from my coordination software library?

Yes, and a coordination package is the practical way to print the plot on logarithmic current-time axes. Verify every library record against the guide edition or the manufacturer document you intend to apply before trusting the drawing, because a record entered on the wrong current basis shifts the whole boundary sideways and can create margin that does not exist.

How does magnetizing inrush fit against a damage curve?

The boundary is a through-fault withstand limit, not an inrush setting. Magnetizing inrush reaches many times rated current for a fraction of a second and is normal, repeatable stress the protection must ride through. Check the relay and any instantaneous settings against the inrush case as well as the fault cases, so the settings tolerate inrush and still clear real through faults below the boundary.

Keep reading

  • How-to

    Calculating low-side fault current with source impedance

    For a 20 MVA, 8.2%, 161:13 kV transformer with an assumed 2500 MVA utility source, the source adds 0.008 pu to the transformer's 0.082 pu, and dividing the 888 A low-side base current by the 0.090 pu total gives about 9.87 kA. If the nameplate secondary is actually 13.8 kV, the answer is about 9.3 kA.

    Protection: breakers, fuses and SCCR

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.

    Protection: breakers, fuses and SCCR

  • How-to

    Calculating Transformer Interrupting Current From Impedance

    Use the impedance's own base: 10.2% is stated on the 8,333 kVA self-cooled (OA) rating, so rated current at 5.04 kV is 1,653 A and the transformer-limited secondary fault current is 1,653 ÷ 0.102 ≈ 16.2 kA. That figure sizes a breaker on the secondary bus; a primary breaker's interrupting rating is set by the upstream available fault current, not by the transformer.