Current IntelPower LibraryShop main store

How-to

Calculating low-side fault current with source impedance

Protection: breakers, fuses and SCCR Published 7 min read

Short answer

For a 20 MVA, 8.2%, 161:13 kV transformer with an assumed 2500 MVA utility source, the source adds 0.008 pu to the transformer's 0.082 pu, and dividing the 888 A low-side base current by the 0.090 pu total gives about 9.87 kA. If the nameplate secondary is actually 13.8 kV, the answer is about 9.3 kA.

On this page
  1. What is the low-side fault current for a 20 MVA, 8.2%, 161:13 kV transformer?
  2. Which fault does this calculation cover?
  3. How do you turn the utility fault level into a source impedance?
  4. How do you put the source and transformer on one base?
  5. How do you calculate the fault current step by step?
  6. How much difference does the source strength make?
  7. Why does a 13.8 kV secondary change the answer?
  8. How do you check the result before using it?
  9. Questions asked

Divide the transformer's low-side base current by the source and transformer impedances added together on one base. That is the whole method once the utility is treated as a finite source instead of an infinite bus: for the 20 MVA, 8.2%, 161:13 kV unit used here, fed by an assumed 2500 MVA source at 161 kV, the bolted three-phase fault at the low-side bushings comes out at about 9.87 kA. The infinite-bus shortcut of dividing by the transformer impedance alone gives about 10.8 kA, so a source this strong moves the answer by under 9%. The nameplate secondary voltage sets the base current, and swapping in a nominal system voltage is the second way this calculation goes wrong.

What is the low-side fault current for a 20 MVA, 8.2%, 161:13 kV transformer? #

About 9.87 kA for a bolted three-phase fault at the low-side bushings: the assumed 2500 MVA source contributes 0.008 pu, the transformer contributes 0.082 pu, and the 888 A base current divides by the summed impedance. Two things qualify that number. The source strength is an example, not a value for your plant: the utility's available three-phase fault level at the transformer's primary connection is an input you must obtain, and the answer moves with it, as shown below. And the figure is symmetrical rms amperes for a bolted fault with zero arc impedance; a real arc adds impedance and lowers the current, which matters if the number feeds an arc-flash study.

Which fault does this calculation cover? #

This method gives the symmetrical current of a bolted three-phase fault at the transformer's low-side bushings, with the utility source and the transformer impedance in series; it does not give line-to-ground fault current, arc-flash incident energy or a breaker's clearing time. A three-phase fault involves only the positive-sequence network, which is why two magnitudes and a division are enough. A single line-to-ground fault depends on the zero-sequence impedances of the source and transformer and on how the secondary winding is grounded, and it takes deriving available MVA from sequence impedances for single line-to-ground faults rather than the straight sum below.

How do you turn the utility fault level into a source impedance? #

Divide the transformer's base MVA by the source's three-phase short-circuit MVA: an assumed 2500 MVA at the high-side bus gives 20 ÷ 2500 = 0.008 pu, with no ohms and no voltage referral anywhere in the method. If the utility quotes amps instead of MVA, convert first with short-circuit MVA equal to √3 × kV × kA, taken at the transformer's primary connection; converting a prospective short-circuit current into a source impedance covers that step on its own. A level quoted at a remote substation is not your source, because the line impedance between the two points belongs in the source term. Ohm's law runs voltage over current, so the ohmic form of the same source is phase voltage divided by fault current, equivalently the line voltage squared over the three-phase MVA, about 10.4 Ω here, never current divided by voltage. A transformer also transforms impedance, by the square of its turns ratio, and the per-unit method is the bookkeeping that performs that transformation for you.

How do you put the source and transformer on one base? #

Put both on the transformer's own nameplate base and add them straight across: source plus transformer gives 0.090 pu total as seen from the low-side bushings. The nameplate percent is already per-unit on the nameplate MVA and voltage ratio, so the transformer needs no conversion; only the source does. If a datum arrives on a different base, rescale before adding: multiply by the ratio of the base MVA values and by the square of the inverse voltage ratio. A unit with both a self-cooled and a forced-cooled rating carries one nameplate percent on a stated base, and choosing the per-unit base MVA between ONAN and ONAF ratings changes the numbers you write down but never the amperes at the end. This straight addition treats both impedances as magnitudes; a utility source and a power transformer are both predominantly inductive, so for screening the scalar sum is standard practice, while a software study adds resistance and reactance separately.

How do you calculate the fault current step by step? #

Work five steps on one set of bases: fix the base MVA and voltages, convert the source, add the impedances, find the low-side base current, then divide, which here is 888 A over the summed impedance.

  1. Fix the bases. Base MVA 20 MVA, base voltages 161 kV and 13 kV, all from the nameplate. Every impedance below lives on these bases.
  2. Convert the source. Source impedance = base MVA ÷ source short-circuit MVA = 20 ÷ 2500 = 0.008 pu.
  3. Convert the transformer and add. 8.2% ÷ 100 = 0.082 pu. Total: 0.008 + 0.082 = 0.090 pu.
  4. Find the low-side base current. I_base = 20,000 kVA ÷ (√3 × 13 kV) = 888 A.
  5. Divide. I_fault = 888 A ÷ 0.090 pu = 9867 A, call it 9.87 kA.

Rounding √3 to 1.73, as older worked examples do, returns 889 A and about 9880 A, the same result within rounding. When your hand answer and a printed example disagree by a few amperes, look at that √3 first; when they disagree by a factor near 1.73, look at the voltage section below.

How much difference does the source strength make? #

A finite source always lowers the low-side current: the infinite-bus shortcut gives about 10.8 kA here, and including the example source cuts 8.9% off that, exactly the source's share of the total impedance. That share is the whole sensitivity. Calculating transformer interrupting current from impedance alone is the infinite-bus case, the upper bound you get when the utility impedance is zero. The table holds the transformer fixed and moves only the source, all at 13 kV:

Source at the high-side bus Source impedance Total impedance Low-side fault current
Infinite bus 0.000 pu 0.082 pu 10.83 kA
The example source 0.008 pu 0.090 pu 9.87 kA
A weaker source, 500 MVA 0.040 pu 0.122 pu 7.28 kA

Utilities quote an available fault level as a maximum and a minimum. The maximum, the strongest source and lowest impedance, is the one that sets interrupting duty and equipment ratings; the minimum serves protection sensitivity, not duty. A reinforced substation raises the maximum, so carry the utility's future level into the study when it publishes one.

Why does a 13.8 kV secondary change the answer? #

Because the base current changes with the voltage: the same MVA at a 13.8 kV secondary gives about 837 A, and the unchanged impedance total then delivers about 9.3 kA, roughly 6% below the answer at the nameplate secondary. Read the secondary voltage off the nameplate and use it. A transformer designed for the higher voltage is a different base, not a rounding of the lower one, and its per-unit impedance belongs to that base; if your system nominally runs at the other voltage, keep the nameplate voltage as the base and refer through the ratio rather than substituting. The classic hand-calculation error lives here too: dividing the MVA rating by 13.8 kV gives 1449 A, which omits the square root of three from the base current. Carried through, that base produces 17.7 kA after division by the transformer impedance, while the true infinite-bus value at that voltage is 10.2 kA, so the slip inflates the answer by exactly √3. If your hand result runs about 1.73 times a software result, this is the first thing to check.

How do you check the result before using it? #

Run five checks in the direction of power flow, from the utility data to the low-side terminals, and confirm the finished duty against the equipment documentation and the authority having jurisdiction before anyone uses it.

  1. Utility input. Confirm the figure is the three-phase rms symmetrical fault level at the transformer's primary connection, and use the utility's maximum-available value for equipment duty.
  2. Nameplate. Read the MVA, both voltages and the impedance percent off the unit itself; the secondary voltage on that plate decides which of this article's two answers is yours.
  3. Bases. Both impedances on the same MVA and voltage bases; rescale anything that is not before it enters the sum.
  4. Sanity. The result must stand far above the base load current, rise when the source strengthens, and come out identical when only the base MVA changes; those three checks catch a slipped base faster than any rerun.
  5. Standard. For AC high-voltage breakers rated on a symmetrical-current basis, the fault-current calculation follows ANSI/IEEE C37.010-1979, the IEEE guide for calculating fault currents to apply those breakers; confirm the edition in force with the authority having jurisdiction and the equipment documentation before the number enters a rating study.

For the example as stated, carry the finite-source result into the study: the infinite-bus figure is only its upper bound, and the nameplate secondary, not the system's nominal voltage, sets the base. Nothing in this calculation opens energized equipment; if field verification inside a panel follows, it runs under NFPA 70E, 2024 edition, the US workplace electrical safety standard, with the circuit de-energized and verified absent of voltage first, as your site's electrical safety program requires.

Questions asked

What if the utility quotes the source fault current in amps instead of MVA?

Convert it with short-circuit MVA equal to 1.732 × line-to-line kV × kA. A three-phase fault level of about 8.97 kA at the high-side bus returns the assumed source strength used here, so the two forms are interchangeable. Take the figure at the transformer's primary connection; a level quoted at a remote substation needs the line impedance in between added to the source.

Can I run the same calculation on a different MVA base?

Yes. The base MVA is bookkeeping: on a 100 MVA base the source becomes 0.040 pu, the transformer 0.410 pu, the total 0.450 pu, and the low-side base current 4441 A, and dividing returns the same amperes. Scale every impedance to the chosen base before adding, and never sum impedances quoted on different bases.

Does the utility's X/R ratio change the result?

For the symmetrical rms value, no: the calculation above needs only magnitudes. For peak and asymmetrical duty in the first cycles, yes: a higher source X/R raises the peak current and the breaker duty multiplier. Fault MVA alone carries no X/R, so ask the utility for it when the result feeds breaker rating or a peak-current check.

Does this fault current give me the arc-flash incident energy?

No. Incident energy also needs the arcing current, the clearing time of the device actually protecting the secondary read from its time-current curve, and the working distance. The current calculated here is only the source term; a fault current without a clearing time is not an incident-energy result.

Keep reading

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR

  • How-to

    Calculating Transformer Interrupting Current From Impedance

    Use the impedance's own base: 10.2% is stated on the 8,333 kVA self-cooled (OA) rating, so rated current at 5.04 kV is 1,653 A and the transformer-limited secondary fault current is 1,653 ÷ 0.102 ≈ 16.2 kA. That figure sizes a breaker on the secondary bus; a primary breaker's interrupting rating is set by the upstream available fault current, not by the transformer.

    Protection: breakers, fuses and SCCR

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.

    Protection: breakers, fuses and SCCR