Choosing a line reactor or motor reactor for a VFD
Short answer
Pick the side first. A line reactor goes between supply and drive input, sized on drive input amps at 3% impedance for transient buffering or 5% for harmonic reduction; a motor reactor goes between drive output and motor, sized on motor FLA, for reflected-wave protection on long shielded leads. The two are not interchangeable.
On this page
Pick the side of the drive before you pick a rating. A line reactor goes between the supply and the drive input terminals: size it on the drive's input full-load amps, at 3% impedance for transient buffering or 5% when harmonic current is the problem. A motor reactor, also sold as a load or output reactor, goes between the drive output terminals and the motor: size it on the motor full-load current, and its job is reflected-wave protection on long motor leads, where documented limits such as 150 m apply only to shielded cable. The two are not interchangeable, and a 5% reactor on a 480 V line drops about 24 V line-to-line at rated current — by design, not by fault.
Pick the side before the rating #
The fastest way to waste money on a reactor is to mount it on the wrong side of the drive. The symptom you actually have tells you the side:
| Symptom | Side | Reactor | Size on |
|---|---|---|---|
| Drive trips on input overvoltage or overcurrent when other loads switch; nuisance trips of the upstream breaker on supply spikes; measured current distortion on the feeder | Input | Line reactor | Drive input full-load amps, drive nameplate |
| Motor insulation failures, motor heating at normal load, or drive output faults on a long cable run | Output | Motor reactor | Motor full-load amps, motor nameplate |
| Both sets of symptoms | Both | One on each side | Each reactor on its own current |
A line reactor adds series impedance ahead of the drive rectifier: it slows the rate of current rise, lowers the harmonic current the drive draws from the supply, and softens supply transients before they reach the DC bus. A motor reactor adds impedance in the PWM output path, slowing the voltage edges so less reflected-wave overshoot builds up at the motor terminals on a long cable run. Swapping in a bigger drive frame, resetting the fault repeatedly or changing fuses removes neither cause.
Line reactor: choose the impedance and the current rating #
Read the input full-load amps off the drive nameplate — not the motor FLA — and take the next standard reactor rating at or above it. Do not buy large margin: the impedance percentage is defined at the reactor's rated current, and reactor manufacturers state that a 5% reactor behaves as a 3% reactor when it carries 60% of that rating. A big oversize buys almost none of the filtering you are paying for.
Match the reactor voltage class to the supply, not to the motor: the class must equal the bus feeding the drive. Published three-phase families for the common 230 to 575 V systems offer a choice of 3% or 5% impedance with ratings up to about 250 A, and the single-phase 120/230 V class sits near 4% impedance over roughly 4 to 25 A. Treat these as screening numbers; the datasheet of the family you buy governs.
| Supply condition you have | Impedance | What you get |
|---|---|---|
| Stiff supply, no distortion problem, goal is buffering | 3% | Absorbs normal line spikes and surge currents, stops most nuisance trips of upstream breakers, costs the least voltage drop |
| High measured current distortion, strict distortion limits, or a drive with no DC link choke | 5% | More series impedance for harmonic reduction, at the price of more voltage drop at rated current |
If the drive already contains a DC link choke, 5% is not the default: the choke adds series impedance internally, and 3% covers the remaining job of buffering supply transients. When the drive runs at or near its overload rating for long stretches, check the reactor's own overload rating on the datasheet before sizing on nameplate amps alone.
Sizing a 5% line reactor for a drive with a 40 A input #
Inputs, an illustrative case of the kind you read off a drive nameplate and a panel schedule: a 480 V, three-phase, 60 Hz supply at the drive; a drive nameplate input of 40 A; no DC link choke in the drive; nuisance input trips plus measured feeder distortion, which points at the input side and the 5% column.
The rule in words: an impedance rating is the line-to-line voltage drop across the reactor at its rated current, expressed as a percentage of the line voltage.
The arithmetic:
- Full-load drop: 0.05 × 480 V = 24 V line-to-line at 40 A. That 24 V is the reactor working, not a fault.
- Part load: the drop scales with current. At 24 A, which is 60% load, the drop is 24 V × 0.60 = 14.4 V — 3% of line voltage.
- Oversize penalty: a 50 A reactor carrying 40 A drops 24 V × (40 A ÷ 50 A) = 19.2 V, about 4% effective impedance, so a point of filtering is gone.
The voltage budget: at nominal supply the drive input sees the line voltage minus the reactor drop, which is 456 V here. If the supply measures 5% low under load, 456 V at the terminals, the drive sees 456 V − 24 V = 432 V, which is 10% below nominal — the edge of the ±10% band the drive's own voltage class typically nameplates.
The decision: buy the 5% unit at the 40 A class rating when the lowest voltage you measure at the drive under load stays within 5% of nominal. If it sags more than 5%, buy 3% instead — 14.4 V at full load — or fix the supply first, and confirm the drive's nameplate input range against that 432 V floor when you place the order.
Motor reactor: size on motor FLA and check the lead length #
Size the output reactor on the motor full-load current at the drive output — the same nameplate figure that drives selecting overload and jam protection for a reversible motor — and keep it at or below the drive's rated output current. Output reactors are chosen by current rating and documented lead-length limit, not by working an impedance percentage the way you do on the line side. One published family for the same 230 to 575 V classes spans roughly 2.5 to 110 A.
The lead-length limits are where selections go wrong. They are documented for shielded cable and only for the models rated for them: on one published line, the 72 A and higher models carry limits of up to 150 m of shielded motor cable and output frequency up to 120 Hz. Below those current ratings, or on any other family, those numbers do not apply — read the datasheet before ordering, and do not carry the shielded-cable figure across to an unshielded run at all.
Follow the drive manual's own motor-lead table first; the reactor buys margin where that table runs out. Lowering the carrier frequency cuts the drive's switching losses and the motor's audible noise, but the peak voltage at the motor terminals is set by the pulse rise time and the cable length, so it is not a fix for long leads. Where your length or voltage class exceeds what output reactors cover, the next steps are dv/dt and sine filters, specified against the drive manufacturer's documentation.
Install and verify #
De-energize the drive supply and lock it out, wait out the DC bus discharge time stated in the drive manual, and verify zero volts on the input and bus terminals with a meter rated for the voltage before you touch anything.
Wire a line reactor in series with all three supply phases ahead of the drive, both line conductors on a single-phase input, and a motor reactor in series with U, V and W between the drive and the motor. If the reactor nameplate marks line and load ends, respect the marking. Torque the terminals to the datasheet values, and mount the reactor where the enclosure ventilation can carry its heat: reactors dissipate heat in normal operation.
Checks at load:
- Measure the input current on each phase; the phase-to-phase imbalance should be small.
- Measure the voltage drop across the reactor and compare it with the impedance figure. A drop far above the nameplate percentage means an undersized rating or a wiring error.
- Check the reactor surface temperature after an hour at load. A unit too hot to hold at normal load is undersized or starving for air.
- If the motor draws above nameplate amps with the reactor in circuit, that is a load problem, not a reactor problem — the same investigation as a motor running over nameplate amps after a soft starter bypass.
If the drive keeps tripping before the reactor arrives, derate the process and install it at the next window. Do not bypass the drive's protection faults to keep the line running.
Questions asked
Can one reactor serve both the line side and the motor side?
No. A line reactor is rated for supply-frequency current at the drive input; a motor reactor is rated for the PWM current at the drive output. A line reactor moved to the output is outside its rating and can overheat on the switching ripple, and neither device fixes a problem on the wrong side. If both sides need help, buy one for each, each sized on its own current.
How do I size a line reactor for a single-phase 120 or 230 V drive?
Use the single-phase reactor class for that input voltage, published at about 4% impedance over roughly 4 to 25 A, sized on the drive nameplate input current. Above 25 A the common single-phase families run out, so check the manufacturer's catalog for a larger family or address the distortion at the drive itself.
My drive has a DC link choke. Do I still need a line reactor?
Not for harmonics. The link choke already adds series impedance inside the drive, which is why 5% line impedance is recommended mainly where no choke is present. A 3% reactor still buffers supply spikes and surge currents that cause nuisance input trips. Measure the feeder distortion first; if it is already inside your limit, add nothing.
Does the 150 m motor-lead limit apply to unshielded cable?
No. That figure is documented for shielded motor cable on the specific models rated for it, and it does not transfer to unshielded runs or to lower-current models. For an unshielded run, use the lead-length table in the drive manual and the limit on the reactor datasheet; if neither covers your length, a dv/dt or sine filter is the next step.