Explainer
Ground fault current path for an ungrounded generator fault
Short answer
The fault current on the ungrounded unit is not supplied by that unit's own winding loop. It leaves the grounded generator's faulted phase lead, crosses the bus, runs down the faulted winding segment to the failure point and returns through the ground grid to the grounded neutral. Fault position scales the driving voltage; the grounding impedance sets the magnitude.
On this page
On a two-generator island with one unit grounded through a neutral grounding transformer and resistor and its twin deliberately ungrounded, a ground fault on the ungrounded unit does not need a circular route through that unit to flow. The current takes a one-way trip: out of the grounded generator's faulted phase lead, across the bus to the faulted unit's terminal, down the winding segment between that terminal and the failure point, through the fault to ground, and back through the ground grid to the grounded neutral. There is no return loop through the ungrounded machine because it has no neutral connection. Trace the path from the grounded source, size the ground-fault protection around the grounding impedance, and treat the fault position on the winding as a scale factor on the driving voltage.
Where the fault current comes from and how it returns #
Trace the conductive path from the only intentional grounding point, not from the fault's physical location. The grounded generator supplies current from its faulted phase lead through its terminal, the bus and feeder conductors, and the ungrounded unit's terminal connection. Inside the faulted machine, the current runs along the connected portion of the faulted phase winding to the insulation failure, then through the fault into the grounding conductor system. The ground grid carries the return to the grounded unit's neutral grounding transformer and resistor, and back through that unit's own winding to its phase lead, closing the loop.
The ungrounded unit participates only as a conductor. Its winding segment between terminal and fault sits in series with the path; the rest of its winding, and its absent neutral connection, play no part. This is the same principle that decides which sources can feed a ground fault at all: the grounded-wye neutral sources and returns the current, while a delta winding with no ground reference cannot, as covered in why a grounded-wye source supplies ground fault current and a delta does not.
| Segment | Role in the loop |
|---|---|
| Grounded generator phase lead and terminal | Source of the fault current |
| Bus and feeder conductors | Carry the current to the faulted unit |
| Faulted winding segment | Connects the faulted unit's terminal to the fault point |
| Fault and grounding conductors | Path into the ground grid |
| Ground grid and neutral grounding transformer/resistor | Return path to the grounded neutral |
What the fault position changes #
Fault position sets two things: the driving voltage and the amount of winding in the path. Before the fault, each point on a wye-connected winding sits at a fraction of the phase-to-neutral voltage between the neutral and the terminal. A fault halfway along the winding from the terminal sees roughly half the phase voltage as its driving voltage, and only the segment between the terminal and the fault is in series with the loop.
Position changes magnitude, not topology. Every position on the winding uses the same source, bus, winding segment, ground grid and grounded neutral. The ungrounded machine's floating neutral shifts with loading and charging symmetry, but that shift moves the pre-fault voltage at the fault point by a small margin; it does not change the identity of the return path.
Both machines and the connected cables also feed the fault through their phase-to-ground capacitance. That charging contribution exists in every AC system and is set from system capacitance data; on a resistance-grounded island it is small next to the resistor-limited current and does not replace the intentional return.
A worked magnitude example #
Every input below is an illustrative example, not a rating from any installed machine or grounding package:
- System: 4160 V, three-phase, 60 Hz, two wye generators on an islanded bus.
- Grounding: the grounded unit's neutral grounding package presents 6 Ω at the generator neutral, an example value; the installed figure comes from the grounding design and the transformer ratio.
- Fault: bolted phase-to-ground fault on the ungrounded unit, with winding, bus, fault and ground-path impedances ignored.
Arithmetic: the phase-to-neutral voltage is 4160 V ÷ √3 ≈ 2402 V. A bolted fault at the ungrounded unit's terminal sees that full driving voltage, so the resistor limits the current to about 2402 V ÷ 6 Ω ≈ 400 A. A fault halfway down the winding sees about half the driving voltage, roughly 1201 V, so the same loop carries about 1201 V ÷ 6 Ω ≈ 200 A. The result is an estimate: a real installation subtracts winding, bus and fault impedance, and the installed resistor data plus a system study set the actual numbers. The decision these figures support is that a fault anywhere on the ungrounded winding, even halfway down, still draws a current limited only by the grounded unit's grounding impedance.
Why there is no loop through the ungrounded neutral #
An ungrounded generator neutral does not mean the machine is isolated from ground fault behavior; it means there is no deliberate metallic return through that unit. The intentional return lives at the grounded unit, so the grounded unit is both the dominant source and the return for a fault on its twin.
If neither unit were grounded, the system would become a classic ungrounded network in which the only fault current is capacitive charging current, and a sustained single-line-to-ground fault drives the healthy phases' voltage to ground up toward line-to-line level. That failure mode is exactly what low-resistance grounding of one unit exists to prevent, which is why grounding one unit of an islanded pair beats grounding neither.
Generator breaker status and the grounding philosophy also decide which path exists in each operating configuration. Assess the configuration that is actually running rather than assuming the design grounding stays effective through every switching state.
Protection checks for the faulted unit #
IEEE C37.101-2006 catalogs the relaying schemes applied against stator ground faults for each grounding method, and IEEE C37.102-2023 covers generator protection relaying overall; editions and local amendments differ, so confirm the applicable requirements with your authority having jurisdiction and the equipment documentation.
Stator differential protection (device 87) compares current at both ends of each phase winding and trips on imbalance, so it responds to ground faults whose current exceeds its pickup. It cannot detect a turn-to-turn fault inside one winding, because such a fault barely changes the current entering versus leaving the winding. Match the two units' current transformers in type, ratio and knee point, and prove them at commissioning; otherwise the less sensitive unit's scheme underreaches for a fault the other unit's scheme would catch, and repair cost and lost output differ between the machines for no engineering reason.
Where the grounding method leaves part of the winding without effective ground fault coverage, near the neutral where the driving voltage approaches zero, full coverage calls for a 100 percent stator ground scheme, either third-harmonic voltage methods or low-frequency injection. The guide above describes the options for each grounding method.
Verifying the installed arrangement #
Before reasoning from relay indications, prove the assumed arrangement exists as built. De-energize, lock out and test for absence of voltage before opening any generator terminal box, switchgear cubicle or neutral grounding enclosure.
Then, from the approved one-line and grounding drawings compared against the as-found connections: trace the grounded neutral through its transformer and resistor to the ground grid; confirm the second unit's neutral has no grounding connection; identify how frames, bus and grounding conductors bond to the same grid; and record whether the fault is single-phase-to-ground or involves another conductor. Resolve any drawing-versus-installation discrepancy before using the assumed path for a protection decision. This is the same trace-the-return discipline used when locating a ground fault on a resistance-grounded 480 V system, applied here at generator voltage.
Prove the relay and CT circuits with the approved commissioning test method, not by creating a fault. Never energize equipment to test a suspected ground fault.
The decision for this arrangement #
Treat a ground fault on the ungrounded unit as a fault fed through the bus by the grounded unit: one source, one return, the faulted winding segment in series, magnitude set by the grounding impedance and scaled by fault position. Set ground-fault pickup and differential sensitivity against the resistor-limited current calculated from the installed grounding data, verify CT matching in commissioning, and add a 100 percent stator ground scheme where neutral-end coverage is required.
Questions asked
Does the ungrounded generator supply any of its own ground fault current?
Only its charging current. Every phase conductor and winding has capacitance to ground, so the ungrounded unit feeds a small capacitive current into a fault on its own winding. That contribution is normally far smaller than the resistor-limited current the grounded unit delivers through the bus, and it returns through the phase-to-ground capacitances rather than through any neutral connection, because the ungrounded unit has none.
Will stator differential protection see every fault on the winding?
No. Differential relaying compares the current entering and leaving each phase winding and trips on the difference, so it responds well to ground faults whose current exceeds its pickup. A turn-to-turn fault within one winding leaves the entering and leaving currents nearly equal, so the differential scheme does not detect it, a limit the IEEE generator protection guides state plainly. Turn fault coverage needs a different scheme.
How are faults near the neutral end of the winding covered?
Fundamental-voltage ground fault methods lose sensitivity as the fault point approaches the neutral, because the driving voltage there approaches zero. Full-winding coverage calls for a 100 percent stator ground scheme: third-harmonic voltage comparison or low-frequency current injection. IEEE C37.101 describes these schemes for each grounding method, and the relay vendor documentation defines pickup and commissioning for the specific model.