Explainer
Grounded or floating control power transformer secondaries in MCCs
Short answer
Ground the secondary, on the return terminal that the bucket breakers do not switch. A floating 230 V winding with no insulation monitor gives you a first earth fault no breaker clears and leaves bucket wiring live after its breaker opens; floating only earns its keep with an insulation-monitoring device and double-pole breakers, neither of which this MCC has.
On this page
Ground one terminal of the secondary on every control transformer in the lineup — the return conductor that the bucket breakers do not switch — and stop treating floating as an option here. The 690 V primary works out to about 398 V phase-to-earth, well past the 150 V-to-ground point at which control-transformer application guidance reading the NEC calls for a grounded secondary. Floating buys one thing only: the MCC keeps running through a first earth fault. Without an insulation monitor to announce that fault and two-pole breakers to interrupt both live conductors, a floating control system gives you what this lineup already shows — a first fault no breaker clears, both conductors live to earth at undefined voltage, and one bucket whose wiring stays energized with its breaker open.
What a floating secondary does on a first earth fault #
A floating secondary winding has no reference to earth, so neither conductor sits at a defined potential; winding-to-earth capacitance and insulation leakage set whatever your meter reads. That is why a healthy floating system can show substantial voltage from each terminal to earth with no fault present.
When the first real earth fault arrives, there is no metallic return path, so the fault current is the small capacitive current, far below any MCB trip rating, and nothing operates. The physics is the same reason why a grounded wye sources ground fault current and a delta does not: no earthed reference, no fault current.
The fault does not go away. It quietly grounds one conductor and pushes the other to the full secondary voltage to earth. A second earth fault on that opposite conductor then closes a loop through the protective-bonding network and the enclosure steel between two buckets: a short circuit whose path may not pass through either bucket's breaker, or an unintended path that bypasses a control contact and holds a coil in. Continued operation after the first fault is a maintenance obligation, not a fault-free state.
What one bond changes #
Bond the return and the first fault becomes an ordinary short. A fault on the switched conductor now has a metallic path: secondary terminal, faulted wiring, protective-bonding conductor, back to the bond point. The branch MCB sees a current it can clear, and the faulty bucket drops out while the rest of the lineup stays up. A fault on the bonded return itself touches a conductor already at earth potential — no shock, no trip, and it is found by inspection rather than by a breaker.
One obligation stays regardless of the decision: floating the winding never floats the metalwork. Protective bonding of the transformer frame, the distribution panel and the bucket steel is separate from the secondary arrangement and does not change either way.
Where the bond goes: the unswitched return #
In this lineup every single-pole MCB sits in the same secondary conductor, and the other conductor is a common return shared by all buckets. The bond belongs on the return. Then every MCB interrupts the ungrounded conductor, and the wiring downstream of an open breaker sits at earth potential through its coils instead of at line voltage.
Put the bond on the wrong conductor — the one feeding the breakers — and the return becomes the leg at full secondary voltage to earth, permanently connected to the transformer no matter which breakers are open. That is the defect already on this job: one bucket's wiring stays energized to earth with its breaker open because the earthed conductor is on the breaker side. Make the bond at one point, at the transformer's return terminal or the ground bus in the same enclosure, and label it.
Grounded versus floating, side by side #
| Bonded return | Floating secondary | |
|---|---|---|
| First earth fault | Fault current flows through the bond; the branch MCB clears it | Near-zero capacitive current; nothing trips; the circuit keeps running |
| Conductor voltage to earth | Bonded side about 0 V, other side full secondary voltage | Undefined; set by capacitance and leakage; either conductor can sit near full voltage |
| Branch interruption | Single-pole MCB in the ungrounded leg is sufficient | Both poles must interrupt; one-pole breakers leave the circuit connected to a live conductor |
| Required extras | One labeled bond point | An insulation monitoring device and a fault-response procedure |
| Troubleshooting | Voltage-to-earth readings point straight at the fault | Both conductors read live; faults must be sectionalized to find |
For IEC-built MCC lineups, unearthed control power is the exception, specified where a process must ride through a first fault — not the default.
Deciding the bond for these control transformers #
Inputs:
- Primary: 690 V, three-phase, line-to-line, from the MCC supply on this installation.
- Secondary: 230 V, single-phase, from the control transformer nameplate.
- Distribution: one single-pole MCB per bucket, all in the same secondary conductor; the other conductor is the unswitched common return, confirmed by tracing the panel wiring.
- Earth-fault monitoring: none installed.
Rule in words: control-transformer application guidance reading NFPA 70, the National Electrical Code (2023 edition) — Article 250 covers grounding and bonding, Article 450 the transformer installation — requires the secondary of a control transformer to be grounded whenever the primary exceeds 150 V to ground. On a three-phase supply, the phase-to-earth voltage is the line-to-line voltage divided by the square root of three, 1.732. Confirm the requirement with the local authority having jurisdiction and the transformer documentation before bonding.
Arithmetic:
- 690 V ÷ 1.732 = 398 V phase-to-earth at the primary.
- 398 V > 150 V, so the secondary gets a system bond — on all six transformers in this lineup, not just the two that happen to be accidentally grounded.
Acceptance readings after bonding the return: the nameplate secondary voltage between the two conductors, 0 V from the bonded return to earth, full secondary voltage from the switched leg to earth with its MCB closed, and 0 V from the load side of an open MCB to earth.
Decision: if the return reads the full secondary voltage to earth instead of 0 V, the bond is on the switched conductor — move it to the unswitched terminal before anything else. If the return reads 0 V but a bucket still shows voltage to earth with its MCB open, there is a second earth on that bucket's switched leg: find it and remove it.
Making the change on this MCC #
Before opening any terminal cover, open and lock out the transformer primary and test for absence of voltage from each secondary conductor to earth — on a floating or wrongly bonded secondary, zero volts between the two conductors proves nothing.
- Trace the two accidental earths by sectionalizing the return and the switched legs bucket by bucket, the same divide-and-measure method used to locate a ground fault on a resistance-grounded 480 V system. Use a low-impedance tester or a suitably rated test lamp; a high-impedance DMM alone will chase capacitive indications.
- Remove the accidental bonds. The one on the breaker-side conductor is the reason bucket wiring stayed live with the breaker open.
- Add one bond from the unswitched return to the panel ground bus on every transformer in the lineup, so the whole MCC behaves the same way.
- Verify against the acceptance readings above, bucket by bucket, and record the arrangement on the drawing.
If a specification insists on a floating secondary for any transformer, the honest price is an insulation monitoring device on that winding, two-pole MCBs on its branches, and a standing instruction to clear the first fault. Otherwise ground it.
Questions asked
Is there ever a good reason to float a control power transformer secondary?
One: the process must ride through a first earth fault without stopping. That only counts as a design when an insulation monitoring device announces the fault, both poles of every branch are interrupted, and someone is dispatched to clear the fault before a second one appears. Floating without monitoring trades a controlled, localized shutdown for uncontrolled troubleshooting time, because the system is built to keep the fault invisible.
Both secondary conductors read voltage to earth on my meter. Is the winding faulted?
Not necessarily. A floating winding's potential to earth is set by capacitance and leakage, and a high-impedance meter will show a large reading with no fault present. Confirm with a low-impedance tester or a suitably rated test lamp: a real earth fault pulls that conductor decisively to earth and holds it there, while a capacitive indication collapses as soon as you load it.
Where exactly is the bond made, and can there be more than one?
One point only: the unswitched return terminal at the transformer, or the ground bus in the same enclosure. A second bond elsewhere in the control wiring creates a parallel return path through the protective-bonding network and makes ground-fault behavior depend on fault location again, which is exactly what the single bond removes.
Does the NEC govern a 690 V IEC-built MCC installed in Africa?
No. Local installation rules govern, and the engineer of record confirms the arrangement with the authority having jurisdiction and the transformer and MCC documentation. The NEC citation here is a sanity check, not the authority: the 150 V-to-ground threshold and the bond-on-the-unswitched-return practice hold as engineering under either code framework.