How-to
How to size a branch circuit from MCA and MOCP nameplate data
Short answer
Read the nameplate, not the motor currents: conductors sized to the MCA, a breaker at or below the marked maximum, an equipment grounding conductor matched to the breaker per NEC Table 250.122, and a neutral only if the wiring diagram calls for one. For the worked 208 V three-phase unit, that is three #8 AWG copper conductors, a 40 A breaker and a #10 AWG copper grounding conductor.
On this page
- What do MCA, MOCP, FLA and LRA on a packaged unit nameplate mean?
- How do I size the conductors from the nameplate MCA?
- Which breaker can I use under the marked MOCP limit?
- Does a 208 V cooling-only packaged unit need a neutral?
- What size equipment grounding conductor goes with the breaker?
- How do I verify the circuit before starting the compressor?
- Questions asked
When a packaged cooling unit hands you a nameplate with four different currents, two of them size the circuit and two of them are bait. For the 208 V, three-phase, 60 Hz, cooling-only unit worked through here, the selection is: three #8 AWG copper phase conductors, a #10 AWG copper equipment grounding conductor, a 40 A breaker listed for air-conditioning equipment, and no neutral unless the unit's field wiring diagram shows a neutral terminal. Every input comes off the nameplate, not from a recalculation of motor currents. The rules cited are NFPA 70, the National Electrical Code, 2023 edition — Article 440 for the nameplate markings, Table 310.16 for conductor ampacity, Table 250.122 for the grounding conductor — and the authority having jurisdiction and the equipment documentation get the final word on the installed circuit.
What do MCA, MOCP, FLA and LRA on a packaged unit nameplate mean? #
On this nameplate, the MCA of 28.7 A is the minimum ampacity the circuit conductors must carry, the 45 A maximum overcurrent protection is the largest breaker or fuse the unit allows, and the 28 A full-load and 156 A locked-rotor figures describe the motors — they size nothing.
The manufacturer already did the code arithmetic before printing the plate. MCA is built under NEC Article 440 as 125 percent of the largest motor in the cabinet — the compressor — plus every other load: the condenser fan, crankcase heater, controls transformer primary and any accessories. MOCP is the marking that lets the branch protection ride through compressor inrush, which is why it can sit well above the conductor ampacity without the conductor being undersized. FLA belongs to an individual motor winding; LRA is the momentary locked-rotor draw at start, not a continuous figure. Recomputing the circuit from FLA fails because you cannot see the fan, heater and transformer loads from outside the cabinet.
| Nameplate marking | Value | Role in the design |
|---|---|---|
| MCA | 28.7 A | Minimum ampacity for the phase conductors |
| MOCP | 45 A | Ceiling for the breaker or fuse rating |
| FLA | 28 A | One motor's running current; not a sizing value |
| LRA | 156 A | Momentary starting inrush the breaker rides through |
The nameplate marks are the design inputs, the same read-the-plate-first path a guide to sizing rooftop air-conditioning feeders from MCA and MOCP follows.
How do I size the conductors from the nameplate MCA? #
Pull three #8 AWG copper phase conductors with 75 °C insulation. Table 310.16 gives that size 50 A at 75 °C, and a 41–45 °C ambient correction factor of 0.82 still delivers 41 A against the 28.7 A MCA.
The arithmetic is why the next-smaller size fails the realism test even though it passes on paper. At 75 °C it is rated 35 A, and 35 A × 0.82 = 28.7 A — exactly the MCA, with zero margin, in an ambient that a rooftop conduit run in full sun reaches routinely. The #8 AWG pair holds 50 A × 0.82 = 41 A. Keep the 75 °C ampacity through the whole run: if a terminal or breaker lug is only marked 60 °C, that lower rating governs the termination end, so check the markings before you buy on the 75 °C column alone. For long runs, add a voltage-drop check at the compressor's starting current, because a sagging supply raises inrush and shortens contactor life.
If the load were a bare motor instead of a packaged unit, the sizing route would be 125 percent of the motor current — our guide to a #14 AWG motor branch circuit on a 20 A breaker covers that case — but Article 440 replaces that route with the nameplate MCA for packaged cooling equipment.
Which breaker can I use under the marked MOCP limit? #
Use a 40 A breaker. It sits above the MCA and below the 45 A marked maximum, and a breaker listed for air-conditioning equipment is tested to hold in through the locked-rotor start of the compressor instead of nuisance-tripping on the inrush.
The marked maximum is a ceiling, not a target: sizing up to quiet a nuisance trip is the wrong fix and puts the marking out of force. If the equipment instructions list fuses as an alternative, a time-delay fuse at or below that ceiling works too, provided its interrupting rating meets the available fault current at the unit — the same fault-current arithmetic used for any other branch device. You cannot exceed the mark: the manufacturer stamped it because the internal protection and wiring were evaluated to it, and a larger device voids that evaluation. If a breaker at the low end of the allowed range trips on every start, diagnose the start — low supply voltage, phase imbalance, a failing compressor — before touching the rating. Article 440 is what produces those nameplate marks; a guide to MCA versus MOCP breaker and wire sizing under NEC 440 shows the arithmetic the manufacturer applied.
Does a 208 V cooling-only packaged unit need a neutral? #
No. Do not pull a neutral unless the unit's field wiring diagram shows a neutral terminal: a cooling-only three-phase package runs its contactor coil and controls from an internal transformer across two phases, and the possibility that some component uses 120 V is not evidence of a terminal.
Look inside the control compartment or at the installation literature before you decide: the wiring diagram names every field terminal, and if a neutral appears there it is sized for whatever the diagram assigns to it. Where the service is 208Y/120 and the unit is listed to use phase-to-neutral control power, that arrangement is documented on the same diagram — the option is covered in more depth in our guide to 120 V control power from a 208 V system. Absent that terminal, a neutral in the raceway is an unused conductor that still counts toward ampacity adjustment and raceway fill.
What size equipment grounding conductor goes with the breaker? #
Pull a #10 AWG copper equipment grounding conductor. Table 250.122 keys that conductor to the overcurrent device rating, not to the load, so a 40 A device calls for #10 copper even though the phase conductors carry well under that rating continuously.
Run it with the phase conductors for the whole circuit length, land it on the unit's designated grounding terminal, and keep it green, bare or otherwise identified per the code edition in force. It never carries load current and it is never a substitute for a neutral. If the circuit ends up protected by a device with a different rating than the one planned, the grounding conductor row changes with it — recheck the table row for whatever rating is actually installed.
How do I verify the circuit before starting the compressor? #
De-energize the feeder, lock it out and verify absence of voltage before opening anything — past that point, energized work is governed by NFPA 70E, 2024 edition, an energized-work assessment and the PPE that assessment selects. With the circuit dead, check these in order:
- Match the installed phase conductors — size, material, insulation temperature rating and raceway fill — against the design above.
- Read the breaker's rating and confirm its listing for air-conditioning equipment and that it does not exceed the marked maximum.
- Confirm the #10 AWG copper grounding conductor runs the full circuit and terminates on the unit's grounding lug.
- Open the field wiring diagram: no neutral terminal means no neutral conductor in the raceway; a neutral terminal means verifying its size and termination.
- Torque-check every line, neutral and grounding termination to the manufacturer's published values.
- Energize per the manufacturer's start-up procedure, then measure running current on all three phases against the nameplate running current; a brief start toward the locked-rotor figure is normal and is not a trip condition.
The finished circuit for this nameplate reads: three #8 AWG copper conductors, a #10 AWG copper grounding conductor, a 40 A breaker within the marked maximum and no neutral — and if the breaker trips on start, the fix is a diagnosis, never a larger device.
Questions asked
Why is the MCA so close to the compressor's full-load current on this unit?
Because the packaged unit's other electrical loads are small. MCA is 125 percent of the largest motor plus every remaining load in the cabinet, such as the condenser fan, crankcase heater and controls transformer primary. When the compressor dominates and the rest is light, the MCA lands close to one motor's running current, which is exactly why the nameplate, not a recalculation, is the source.
Can I use a 30 A breaker since the running current is only 28 A?
No. The MCA is the floor for the circuit, not the running current, and a device near that floor risks nuisance trips on the compressor's locked-rotor start. Pick a breaker listed for air-conditioning equipment within the allowed range so it holds in through the start, and never trade the trip behaviour for a rating above the marked maximum.
What should I check first if the breaker trips every time the compressor starts?
Measure the supply voltage at the unit terminals during a start; a sagging feed raises inrush and pushes the breaker toward its trip curve. Then check phase imbalance, the contactor and the compressor itself. Only after the start is healthy should you consider the protective device, and even then the replacement goes in at the same or lower rating, inside the marked range.
Do these steps change for a 460 V or single-phase packaged unit?
The method does not: read MCA and MOCP from the nameplate, size the conductors to the MCA with ambient and terminal corrections, keep the breaker within the marked maximum, and match the grounding conductor to the installed device. What changes is the ampacity lookup and the conductor count. A single-phase unit uses two phase conductors, and a 460 V unit typically shows smaller currents for the same cooling capacity.