Current IntelPower LibraryShop main store

Troubleshooting

Identifying unknown terminals on a NEMA size 1 motor starter

Motors and motor starters Published 6 min read

Short answer

Those unmarked terminals are auxiliary contacts on an adder block. With the starter locked out and verified dead, confirm each pair by resistance: open with the armature released and a fraction of an ohm when pressed marks a normally open contact. Wire that pair across the Start pushbutton as the seal-in, and put the overload's normally closed contact in the coil return.

On this page
  1. What those terminals actually are
  2. De-energize and verify before anything opens
  3. Confirm against the wiring diagram first
  4. The ohmmeter test that settles it
  5. Match the coil marking to the supply you actually have
  6. Wire the three-wire Start/Stop circuit
  7. Prove it dead, then prove it running
  8. Questions asked

The connectors you have not identified on a NEMA size 1 starter are, in nearly every case, auxiliary contacts: small pilot-duty contacts in an adder block fitted to the contactor, electrically separate from the L1/L2/L3 and T1/T2/T3 power poles, the coil terminals, and the overload. Confirm the pair with the wiring diagram for your exact catalog number and one resistance check on a locked-out, verified-dead starter: a contact that reads open with the armature released and a fraction of an ohm with the armature pressed is normally open, and that pair is the seal-in contact for a three-wire Start/Stop circuit, with the overload's normally closed contact in the coil return.

What those terminals actually are #

A size 1 starter grows extra contacts through bolt-on auxiliary blocks on the top or side of the contactor. NEMA starter catalogs document these adders in normally open and normally closed forms; one major enclosed-starter line accepts up to four of them, NO or NC, through size 1. The block you cannot name is one of these.

Auxiliary terminals on NEMA and IEC contactors carry two-digit numbers under an international marking convention approved by CENELEC: the first digit says which contact it is, and the second digit encodes its function. The scheme decodes in the diagram legend for your product line, and the digits are not portable — a pair numbered one way on one starter line is numbered differently on another, so treat terminal numbers from any other starter as noise until your own diagram confirms them.

What the block is not: it is not a power pole, it is not the coil, and it is not the overload trip contact. A starter is a contactor plus an overload in one unit, and the split between the switching half and the protection half is laid out in motor starter vs contactor; each half owns different terminals, and the unmarked block belongs to the switching half's auxiliary group.

De-energize and verify before anything opens #

NFPA 70E, 2024 edition, requires de-energizing, locking out, and testing for absence of voltage with an adequately rated instrument before work on exposed conductors — confirm how your local authority having jurisdiction and the machine documentation apply it. Lock out every source feeding the starter, including any separate control-transformer supply; a stopped motor is not isolation. An ohmmeter is a dead-circuit instrument: across a live terminal it gives meaningless numbers and can be destroyed. Nothing below happens with power on.

Confirm against the wiring diagram first #

The meter test settles function; the diagram settles identity:

  • Copy the full catalog number, series, and coil code off the starter nameplate.
  • Pull the wiring sheet for that catalog number from the manufacturer or an authorized distributor.
  • Read which terminal pair belongs to the auxiliary block and whether it is supplied NO or NC.
  • Test with the meter only when the markings are illegible or the block does not match the diagram — then the next section is the authority.

Size 1 tells you horsepower capability, not terminal layout; two size 1 starters from different product lines share nothing in the numbering.

The ohmmeter test that settles it #

Worked through on one suspect block, starter locked out and verified dead, meter on the resistance range:

  1. Photograph and label every conductor before removing anything.
  2. Disconnect enough wiring to remove parallel paths through coils, lamps, and other contacts — you measure the contact, not the circuit around it.
  3. Touch the meter leads together and read the lead resistance: 0.2 Ω in this example.
  4. Measure across the suspect pair with the armature released: the meter shows OL (open).
  5. Press the contactor armature fully and repeat: 0.6 Ω.
  6. Subtract the leads: 0.6 Ω − 0.2 Ω = 0.4 Ω of true contact resistance.

Open at rest and 0.4 Ω when pressed is a normally open auxiliary. The second pair on the same block read 0.5 Ω released and open pressed: 0.5 Ω − 0.2 Ω = 0.3 Ω closed at rest, which is the normally closed one.

Reading, armature released Reading, pressed What you have Decision
OL (open) 0.4 Ω Normally open auxiliary Seal-in across the Start button
0.3 Ω OL (open) Normally closed auxiliary Status or interlock use only
No repeatable change No repeatable change Not a contact, or wrong pairing Re-check isolation and the terminal pair

The change of state is the identification; the absolute resistance only has to be small. Auxiliary contacts on NEMA starters carry pilot-duty ratings — classes such as A600 and P300 in the specifications — which run a coil circuit comfortably and nothing larger; check the marked rating before switching any load beyond the control circuit.

Match the coil marking to the supply you actually have #

Read the coil label before planning the control circuit; it decides the supply, not the other way round.

Example: the coil is marked 120 V, and measured line-to-neutral voltage is 121 V. 121 V ÷ 120 V = 1.008, so the supply sits 0.8 % above nameplate — a direct match, and the coil runs straight off L1 and the circuit neutral with no control transformer.

If the label instead reads 24 V, the decision changes: that coil gets a 24 V control transformer or a correctly rated replacement coil, because 121 V on a 24 V coil burns it within seconds. A 480 V coil belongs line-to-line on a 480 V system, not to neutral. The control return is a circuit neutral, never the equipment grounding conductor.

Wire the three-wire Start/Stop circuit #

With a 120 V coil, a three-phase supply, and no control transformer, the standard three-wire circuit assembles like this:

  1. Take the control hot from L1 to the Stop pushbutton (normally closed).
  2. From Stop to the Start pushbutton (normally open) — call this node A.
  3. From the other side of Start (node B) to one coil terminal.
  4. Land the verified normally open auxiliary across node A and node B, in parallel with the Start button.
  5. From the other coil terminal through the overload's normally closed contact to the circuit neutral.
  6. Land the motor leads on T1/T2/T3, using the poles the diagram names when the supply is single-phase, so the current passes through the overload elements.

When Start is pressed the contactor picks up, the auxiliary closes, and the coil stays fed after the button is released; opening Stop or the overload contact drops it. The holding contact goes across Start and nothing else — across Stop or the overload it would feed the coil around the devices that exist to break it. The same L1-to-neutral control arrangement is drawn end to end in wiring a three-phase coolant pump starter from a 120 V signal.

Before final terminations, set the overload to the motor's nameplate full-load current; the element and jam setting are covered in selecting overload and jam protection for a reversible motor. And if the motor's leads are as unmarked as the starter's terminals were, identifying unmarked 9-lead motor leads is the companion job at the T terminals.

Prove it dead, then prove it running #

  • Every power conductor on L and T studs only; the auxiliary pair in the control circuit only.
  • Terminations tight to the starter's documented torque values.
  • Overload setting on the motor nameplate full-load current.
  • Trace that Stop and the overload contact break every path feeding the coil, including the seal-in.

Then re-energize under your plant's normal commissioning practice with the machine clear: measure coil voltage on a Start command — the 121 V on a 120 V coil match you verified earlier — press Start briefly, confirm the contactor picks up and holds, press Stop, and confirm it drops out. Holds, stops, and drops out: the identification is proven by function, and the starter is wired.

Questions asked

Can I identify the terminals by trying them with power on?

No. Energized guessing can put line voltage across a coil or contact meant for a different duty, short the control supply, or close a power circuit you did not intend. Identify every pair dead, with the circuit locked out and absence of voltage verified, then wire to the diagram and do a controlled functional test.

What resistance should a healthy auxiliary contact read?

After nulling the meter leads, expect a fraction of an ohm — the worked example landed at 0.4 ohm after subtracting 0.2 ohm of lead resistance from a 0.6 ohm reading. The decisive sign is the state change between released and pressed, not the absolute number. A contact that reads tens of ohms, or flickers as the armature moves, is suspect.

Why does the seal-in contact go across the Start button and nothing else?

The seal-in only has to keep the coil fed after the Start button is released. Wiring it across Stop or the overload contact would feed the coil around the very devices meant to break it, so the starter would not stop on command and an overload could not trip it. Across Start, both Stop and the overload still interrupt the coil circuit.

Can the auxiliary contact carry the motor current instead of the power poles?

No. Auxiliary contacts on NEMA starters carry pilot-duty ratings in classes such as A600 and P300, far below the motor current a size 1 starter's L and T poles switch. Motor power always goes through the line and load terminals; the auxiliary pair serves the control circuit only.

Do I need a control transformer for a 120 V coil?

Not automatically. If the supply is a 120/240 V or 120/208 V system, L1 to the circuit neutral puts 120 V on the coil with no transformer, which is how many machine starters are built. A transformer is needed when the coil voltage differs from what is available — a 24 V or 480 V coil needs one, or a correctly rated replacement coil.

Keep reading

  • Explainer

    Motor starter vs contactor: using a starter as one

    A motor starter is a contactor with an overload relay added: the relay's normally closed contact opens the coil circuit on sustained overcurrent. A starter works wherever a contactor is called for, provided three checks pass — horsepower rating at the supply voltage, coil voltage, and the overload setting against the motor's nameplate full-load current. A NEMA Size 1 covers a 3 HP motor.

    Motors and motor starters

  • Troubleshooting

    Motor running over nameplate amps after soft starter bypass

    The motor averages 192.7 A against 164.0 A FLA with only about 0.90% voltage-magnitude unbalance, so the supply is not the proven cause. Treat excess shaft load or excess motor loss first, and confirm negative-sequence voltage with a three-phase power-quality analyzer reading V2/V1, total kW and speed before replacing the starter or the motor.

    Motors and motor starters

  • How-to

    Wiring a three-phase coolant pump starter from a 120 V signal

    Run the machine's 120 V coolant output through the overload relay's normally closed contact to a contactor with a 120 VAC coil, and set the overload dial to the pump's nameplate full-load current — 1.8 A on a typical 1/2 HP three-phase pump, inside a 1.3–2.1 A adjustable range. Then bump-test rotation and swap any two motor leads if the pump runs backward.

    Motors and motor starters