NGR maximum resistance comes from system charging current

Wiring, grounding and bonding Published 7 min read By Current Intel engineering team

Short answer

The ceiling on a neutral grounding resistor is the system's capacitive charging current: the resistor current must equal or exceed the total three-phase charging current 3·Ico, so R_max = V_LN/(3·Ico). For a 0.5 A ground-fault limit that means per-phase charging current of 167 mA or less, about 1663 Ω of minimum capacitive reactance at 480 V and 14,411 Ω at 4160 V.

On this page
  1. Why charging current sets a ceiling on the resistor
  2. The Ico-versus-3Ico trap
  3. The limits the design basis gives
  4. Where the charging current comes from
  5. Worked example: how much cable the limit holds
  6. Only the energized cable counts
  7. Verify the margin and the resistor's other ratings
  8. The decision, case by case
  9. Questions asked

Buying or setting a neutral grounding resistor starts from one number the resistor vendor will not give you: the capacitive charging current of the system it grounds. The resistor's let-through current must equal or exceed the total charging current 3·Ico of every energized cable, winding and surge capacitor, which sets the ceiling R_max = V_LN/(3·Ico). A resistance-grounded source needs a neutral to land that resistor on, and where that neutral comes from — and why a delta source supplies no ground-fault current path — is covered in why a grounded wye sources ground fault current and a delta does not. On the 0.5 A ground-fault basis used in mining-style systems, the ceiling works out to a 554 Ω resistor at 480 V and 4804 Ω at 4160 V. The rest of this article derives those numbers and shows what limits the charging current itself.

Why charging current sets a ceiling on the resistor #

Every energized conductor holds charge to ground through its insulation: cable capacitance, motor and transformer winding capacitance, surge capacitors. Under a single line-to-ground fault those capacitances discharge through the fault and return through the neutral. An intermittent arcing fault is worse than a bolted one, because each restrike recharges the system capacitance and the voltage across the system builds restrike by restrike. The resistor is what drains that charge.

The working criterion in high-resistance grounding practice is that the resistor current be at least equal to the total charging current; in zero-sequence terms, R0 ≤ Xco, where Xco is the per-phase capacitive reactance to ground. Vendor HRG design guides — Eaton publishes one for low-voltage systems — describe what this buys: grounding that keeps the safety benefits of a grounded system while cutting the risk of service interruptions from ground faults. A little too much resistor current is the safe error, since it only raises the fault current and the touch voltage during a fault. Practical high-resistance grounding sits well under 5 A of let-through.

The Ico-versus-3Ico trap #

The sizing equations demand a comparison between the resistor current and the total charging current 3·Ico — the sum over all three phases — never the per-phase charging current Ico. A mining-style system limited to 0.5 A with pickup near 200 mA looks like a violation only when the comparison is made against Ico: the resistor then appears several times stronger than the charging current allows. Read correctly, a per-phase charging current under a third of the resistor current is exactly what a compliant design looks like when the total just fits under the limit. Compare the wrong quantities, or count cable that is normally de-energized, and the same system can look bad when it is fine, or fine when it is not. Settle the factor of 3 before drawing any conclusion.

The limits the design basis gives #

Take the basis directly: ground-fault current limited to 0.5 A through the resistor, pickup at 200 mA. The per-phase ceiling is that limit divided by 3: 167 mA, written 0.1667 A. At 480 V, V_LN = 480 V ÷ √3 = 277.1 V, so Xco = 277.1 V ÷ 0.1667 A = 1663 Ω and R_max = 1663 Ω ÷ 3 = 554 Ω. At the medium-voltage bus, V_LN = 2401.8 V, so Xco = 2401.8 V ÷ 0.1667 A = 14,411 Ω and R_max = 14,411 Ω ÷ 3, about 4804 Ω.

Quantity 480 V system 4160 V system
Line-to-neutral voltage V_LN 277.1 V 2401.8 V
Per-phase charging-current ceiling 167 mA 167 mA
Minimum capacitive reactance Xco 1663 Ω 14,411 Ω
Resistor ohms at the fault-current limit 554 Ω 4804 Ω

These are design-basis estimates, to be checked against the resistor and relay documentation and the requirements your installation works to. The method is what transfers, not the 480 V column: substitute your own line-to-neutral voltage. At higher distribution voltages the same walk-through is given in how to size an NGR for a 13.8 kV mining system.

Where the charging current comes from #

When a cable datasheet does not publish capacitance, estimate it from the insulation geometry. The usual formula is C = 0.0169 × e ÷ ln(D/d), in µF per 1000 ft, with e the relative permittivity of the insulation — 2.3 for XLPE, 2.8 for EPR — D the diameter over the insulation and d the diameter under it. Capacitance rises as the insulation gets thinner relative to the conductor, which is one reason shielded medium-voltage construction carries more capacitance per 1000 ft than unshielded 600 V cable.

Charging current per 1000 ft per phase follows from the line-to-ground voltage: Ic = 2π × f × C × Eo, which comes out in mA per 1000 ft when C is in µF and Eo is in kV. At 60 Hz the factor 2πf is 377, so Ic ≈ 377 × C × Eo. Multiply by the energized length in thousands of feet and sum every run that can be energized together, then add motor winding, surge-capacitor and transformer capacitance from the equipment datasheets, since neither formula covers them. Where the datasheet publishes capacitance, use it and skip the geometry. The total is an estimate with real uncertainty — design input to be confirmed against the equipment documentation, not a measured value.

Worked example: how much cable the limit holds #

Example inputs, illustrative rather than a datasheet: 4160 V three-phase, 60 Hz, line-to-ground voltage 2401.8 V, and a shielded XLPE feeder whose datasheet lists 0.11 µF per 1000 ft to ground. Charging current per 1000 ft: Ic = 377 × 0.11 × 2.4018 ≈ 100 mA. One continuously energized run of this cable therefore tops out at 167 ÷ 100 ≈ 1.67 thousand ft, about 1700 ft. A single 2500 ft run draws 2.5 × 100 = 251 mA and crosses the ceiling by itself.

The same 0.11 µF per 1000 ft on the 480 V system draws 377 × 0.11 × 0.2771 ≈ 11.5 mA per 1000 ft, so the ceiling there allows 167 ÷ 11.5 ≈ 14.5 thousand ft of cable. The ratio between the columns is 2.4018 kV ÷ 0.2771 kV = 8.67: identical capacitance draws 8.67 times the charging current at the medium-voltage bus, and shielded construction widens the real gap further. That ratio, not the cable itself, is why a fault-current limit that is comfortable at 480 V must be recalculated before it is carried to a 4 kV system.

Only the energized cable counts #

Charging current exists only where voltage exists: a feeder downstream of an open contactor or breaker contributes nothing. Total 3·Ico therefore changes with the operating state, and this is the second half of the mining-system answer — the cable goes off with the motor, so installed length is not the number to compare with the limit. The design case is still the worst simultaneous configuration: every feeder that can be closed at once, plus the runs that stay energized from the source to each switching device. The field symptom of a system near the line is a ground-fault trip or alarm exactly when a feeder is energized, with no fault present — that feeder's charging current is reaching toward the pickup. Compute the worst case rather than trusting the absence of trips, and re-run the calculation whenever cable length, cable type or connected equipment changes.

Verify the margin and the resistor's other ratings #

After commissioning, read the standing neutral current from the ground-fault relay with the system healthy and all feeders in their normal state. That reading is the charging current returning through the resistor, and the relay is the right instrument for it because it measures in its own designed circuit. Compare it with the calculated total and investigate any drift upward — new capacitance has been connected somewhere. The relay itself, its ratings and its replacement are covered in ground fault relay replacement for high-resistance grounding.

Then confirm the resistor datasheet against the duty it will actually see: voltage rating at or above the line-to-neutral voltage, thermal and time rating covering the relay trip time plus the switching device's clearing time, and a continuous path for the standing charging current where the design expects one. If any of this verification opens the resistor enclosure or the relay circuit, treat it as de-energized work: lock out, test for absence of voltage, and follow NFPA 70E, 2024 edition, which covers electrical safety-related work practices — confirm the details with your authority having jurisdiction and the equipment documentation.

The decision, case by case #

Choosing a resistor: compute 3·Ico for the worst-case energized configuration and set the resistor current equal to it or slightly above. On the design basis above, the ohms are the last row of the table. Auditing an existing mining-style system on the same basis: it satisfies the equations as long as the simultaneously energized total stays under the fault-current limit and each feeder sits well under its pickup — the apparent violation was a per-phase comparison, and switched cable explains the rest. Carrying the same limit to the medium-voltage system: divide the allowed cable length by 8.67 before assuming it transfers. Wherever the numbers land close to the pickup, change one thing at a time and re-measure the standing neutral current after each change.

Questions asked

Besides resistance, what ratings must the resistor datasheet satisfy?

Three checks. The voltage rating must cover the line-to-neutral voltage, which is what appears across the resistor during a ground fault. The thermal and time rating must cover the ground-fault relay trip time plus the switching device's clearing time, not the pickup time alone. And where the design expects a standing charging current, the resistor must tolerate that current continuously. Read all three from the resistor manufacturer's datasheet and coordinate them with the relay settings actually programmed.

How do I check charging current on a system that is already running?

Read the standing neutral current. With the system healthy and every feeder in its normal state, the ground-fault relay's neutral-current reading is the charging current returning through the resistor. Compare it with your calculated total and investigate any upward drift, because new capacitance has been connected somewhere. Repeat the check after any change in cable runs, cable type or connected equipment, and expect the reading to track the relay's stated measurement accuracy rather than the calculation exactly.

What adds charging current besides the cables?

Motor and transformer winding capacitance, surge capacitors, and any line-to-ground filter or power-factor capacitors. On medium-voltage motor circuits the surge capacitors are often the largest single item after the cable, so read their value from the capacitor datasheet instead of estimating. Count only equipment that can be energized at the same time: a motor switched off at its contactor removes its winding and surge-capacitor contribution until the contactor closes again.

Keep reading

  • Troubleshooting

    Locating a ground fault on a resistance-grounded 480 V system

    Phase-to-ground readings of 420, 380 and 77 V with all phase-to-phase voltages at 480 V mean the neutral has shifted toward P3: a first ground fault on P3, its current limited by the neutral grounding resistor. Locate it by resistor voltage and current, timing against process events, then feeder-by-feeder isolation, because a second fault on another phase becomes a phase-to-phase fault through ground.

    Wiring, grounding and bonding

  • Selection guide

    Choosing generator neutral grounding for a 480 V diesel set

    For a 480 V diesel set, choose the neutral grounding method in this order: bond every frame to the equipment grounding system regardless of method; pick three-pole or four-pole transfer switches so the neutral is grounded at one source at a time; solidly ground the wye if it feeds 277 V phase-to-neutral loads. For a three-wire set, high-resistance grounding with a 5 A resistor is the defensible choice.

    Wiring, grounding and bonding

  • Explainer

    Grounding a 600 V induction generator neutral

    High-resistance ground the neutral of each generator through its own resistor, sized for a few amps, but only after the stator is confirmed wye with an accessible neutral: the delta winding of the step-up transformer isolates the generator side, so that side must be grounded on its own. Set the Multilin 369 50G/51G pickup below the resistor current after confirming the pickup amp basis.