Current IntelPower LibraryShop main store

Explainer

Protecting a motor fed by a VFD with a protection relay

Protection: breakers, fuses and SCCR Published 7 min read

Short answer

With the relay CTs upstream of the drive's isolation transformer, the relay measures feeder current into the rectifier, so its thermal model cannot track motor heating. Use it as a backup time-overcurrent and ground-fault device, leave motor overload to the drive, and set a 0.3–0.5 s delay to ride through 6–12× transformer inrush.

On this page
  1. The relay measures the feeder, not the motor
  2. Where the CTs sit decides what the relay is
  3. Why the thermal model cannot follow the motor
  4. Inrush: the arithmetic you owe the 51 element
  5. Settings that follow from the CT location
  6. Prove it at first energization
  7. Questions asked

You have a motor protection relay on a feeder that ends in an isolation transformer, a drive and a 700 HP motor, with fuses ahead of the drive for short circuit and contactors the relay trips. Two questions come with that one-line: what should the relay be set to protect, and does transformer inrush matter. With the CTs ahead of the isolation transformer, the relay sees feeder current into the drive rectifier, not motor current, so it cannot protect the motor thermally — that duty stays with the drive. Use the relay as an independent phase and ground-fault backup for the feeder, transformer and drive input, and set its time-overcurrent delay to ride through 6–12× transformer full-load current lasting 0.1–0.5 s.

The relay measures the feeder, not the motor #

A drive is a rectifier, a DC bus and an inverter. Line current into the rectifier relates to motor current only through power balance, at whatever efficiency and power factor the drive is running at that moment, so every function that needs true stator current loses its meaning upstream of the drive: the thermal model (device 49), stall and locked-rotor detection, jam, and current unbalance. What still works at this CT location is phase overcurrent (50/51) for feeder, transformer and drive-input faults, ground fault through zero-sequence CTs, and the trip path to the contactors. The boundary between useful and blind is the one drawn in what current-only motor protection can and cannot detect — moved a whole drive upstream.

IEEE C37.96-2012, the IEEE Guide for AC Motor Protection, collects recommended protection practice for AC motors, and its current-based and thermal methods assume the relay measures stator current. A line-side CT on a drive-fed motor breaks that assumption. Relay manufacturers have published application papers on exactly this problem; read the one covering your relay and confirm what its instruction manual documents for drive applications before committing settings.

Where the CTs sit decides what the relay is #

CT location The relay sees Still works Dead functions
Ahead of the isolation transformer (this one-line) Total feeder current: transformer magnetizing current, drive harmonics, real load 50/51 backup, zero-sequence ground backup, contactor trip; inrush must be ridden through Motor thermal model, stall, jam, true unbalance
Between transformer and drive Drive input current, no energization inrush 50/51 backup for the drive input; no inrush timer needed Everything on the motor side of the rectifier
At the drive output True motor current, PWM at variable frequency Thermal model, stall, jam, unbalance — only if the relay inputs are documented for that waveform and frequency range Feeder, transformer and drive-input coverage, which then needs its own device

Your one-line is the first row. Accept that, and the relay's job is written: backup phase and ground protection plus the isolation path. Moving the CTs to between transformer and drive makes the inrush question disappear and nothing else improves for the motor, because the rectifier is still in the way. The drive output is the only spot where the thermal model truly works, and on a PWM output it is the spot a protection relay's measurement chain is least likely to be documented for.

Why the thermal model cannot follow the motor #

Run the numbers on a constant-torque load. Illustrative inputs: 700 HP, 4160 V motor, nameplate full-load current 90 A; drive input at full speed and load about 82 A (522 kW shaft at 746 W per HP, motor efficiency 0.95, drive efficiency 0.97, displacement power factor 0.96, so apparent power = 522.2 / (0.95 × 0.97 × 0.96) = 590 kVA, and 590,000 / (1.732 × 4160) = 82 A). At half speed and full torque, motor current is still about 90 A, but shaft power halves, so the drive draws about 41 A. A thermal model integrates current squared: the relay computes (41 / 90)² = 0.21 of rated heating while the motor actually dissipates (90 / 90)² = 1.0 — full rated heating — with its shaft-driven fan at half airflow. A motor running toward its thermal limit reads idle.

The blindness covers every motor-side event. In a stall the drive current-limits, so feeder current stays modest while the motor sits at standstill with no forced cooling; if the drive's own protection catches it, fine, and if it does not, the line-side relay cannot. NFPA 70, the National Electrical Code, 2023 edition, Article 430.126, covers motor overload protection on adjustable-speed drives and requires an individual overload on each motor where one drive feeds several — the code places that duty with the drive, which is where the physics already points. Confirm the requirement with the authority having jurisdiction and the drive documentation.

Decision: enter the drive's motor model from the nameplate — full-load current, service factor, cooling class, speed-dependent cooling if the drive supports it — and either repoint the relay's 49 at the transformer and feeder or switch it off. Do not leave it set to the motor's 90 A upstream of the rectifier.

Inrush: the arithmetic you owe the 51 element #

Inrush matters only because the CTs are upstream of the transformer; downstream of it the relay never sees energization. Before you have event records, estimating transformer inrush current for protection coordination from the transformer's impedance and saturation behaviour gives you the peak and decay to design around. Worked example, illustrative inputs: 750 kVA isolation transformer at 4160 V, so full-load current = 750,000 / (1.732 × 4160) = 104 A. First-cycle energization inrush runs 6–12× that — 625 to 1,250 A — decaying through pickup in 0.1–0.5 s; take 8 × 104 = 833 A as the planning value. Set the backup 51 pickup at 1.2 × 104 = 125 A, and inrush sits at 833 / 125 = 6.7× pickup, so the element starts timing on every power-up. Two settings close the gap:

  • Time delay: 0.5 s definite time, the top of the 0.3–0.5 s band that covers the decay. If the relay offers only inverse curves, check the curve's operating time at 6.7× pickup and keep it well above the measured decay.
  • Instantaneous 50: a load-based setting such as 1.5–2× drive input (123–164 A here) sits far below 833 A and trips on every energization. Either set it above 1.3 × 833 ≈ 1,080 A — above inrush, below available fault current — or leave short-circuit clearing to the fuses, which is their job on this one-line.

Inrush also carries 30–60% second harmonic, the quantity differential schemes use to restrain; on a plain backup 51 you buy the discrimination with time, not harmonics. The capacitor banks after the transformer are the drive's business: the precharge circuit limits their charging current, and every power-up spends precharge-component life, so follow the drive manual's restart limit rather than asking the relay to police power-ups.

Settings that follow from the CT location #

  • Motor side: the drive carries thermal, stall, overload and output ground-fault protection, entered from the motor nameplate.
  • 51 phase backup: pickup 1.10–1.25× feeder full-load current — 125 A in the example — definite time 0.3–0.5 s.
  • 50 phase backup: above 1.3× the planning inrush, about 1,080 A here, or omitted in favour of the fuses.
  • Ground backup: zero-sequence CT around all three feeder phases, pickup above the measured standing residual, same energization window applied.
  • 49 thermal: repointed to the transformer and feeder (pickup on transformer full-load current, transformer time constant) or off.
  • Cables: fuses clear short circuit on the feeder, the 51 backs them up, and the repointed 49 covers feeder and transformer overload; a fault on the transformer secondary draws through the winding and is seen the same way.
  • Contactors: tripped by the relay's overcurrent and ground functions and by drive major faults wired into the relay, so one isolation path serves both.

Prove it at first energization #

Opening the relay or drive cubicle to check CT polarity and wiring is panel work: de-energize the feeder, lock it out and test for absence of voltage at the terminals you will touch. Anything that must stay live falls under your site's energized-work procedure per NFPA 70E, 2024 edition, which covers workplace electrical safety.

Then energize and read the relay's own event records. The captured inrush peak and decay confirm or correct the 833 A and 0.5 s planning values — if the trace is still above pickup at 0.5 s, lengthen the delay. The 51 should start timing and reset on every power-up rather than trip, and a secondary-injection test on the phase and ground elements proves the contactor trip path end to end. The numbers here are worked estimates: check them against the governing code, the transformer test report and the drive and relay documentation before you finalize.

Questions asked

Can I move the relay CTs to the drive output and keep the thermal model?

Only if the relay and its CTs are documented for that service. The drive output is a PWM waveform at whatever frequency the process runs, and motor protection relays state a measurement frequency range and assume a sinusoidal input; outside that range, or on raw PWM, the measurement is undocumented. The drive's own output sensors already measure that current, so an external relay there mostly duplicates hardware the drive already has.

What changes if the motor has a bypass starter for across-the-line starting?

Then the relay has a real motor job, but only if its CTs sit ahead of the point where the drive path and the bypass path join, so they see motor current in either. In bypass the motor draws locked-rotor current instead of the drive's current-limited ramp, so the thermal model, locked-rotor timer and start supervision all come back into play and must be set from the motor data sheet.

Should I switch the relay's thermal element off?

Two workable choices. Repoint it at the transformer and feeder, with pickup on transformer full-load current and a transformer-sized time constant, or switch it off and let the drive's motor model carry overload alone. Leaving it set to the motor's 90 A full-load current upstream of the rectifier is the one option that is wrong: it will track a current with no relation to the motor.

Do the zero-sequence CTs need the inrush treatment too?

Yes. A core-balance CT around all three phases sums load current and inrush to nearly zero in theory, but the DC offset and saturation mismatch of the first cycles can leave a false residual that picks up a sensitive ground element. Block or delay the ground function through the same energization window you apply to the phase overcurrent.

Is the relay redundant with modern drive protection?

Not quite redundant. The drive protects the motor only while its control power, firmware and output sensors are healthy, and its trips stop at the drive. The relay is the independent layer that opens the contactors for feeder, transformer and drive-input faults, including faults inside the drive itself. Keep its 50/51 and ground settings independent of the drive's.

How often can the drive be powered up?

That limit belongs to the drive's precharge circuit, not the relay: every power-up pushes charging current through precharge resistors or a precharge contactor built for a limited number of operations. Follow the restart-per-hour figure in the drive manual; if it states none, get the number from the drive manufacturer instead of testing to failure.

Keep reading

  • Comparison

    What current-only motor protection can and cannot detect

    Three per-phase current amplitudes support overload, phase loss, current unbalance, stalled acceleration and short-cycling protection, and nothing else. Undervoltage, ground fault, winding temperature and mechanical overloads such as high head pressure need their own inputs: a voltage measurement channel, a core-balance current transformer, and temperature or pressure sensors.

    Protection: breakers, fuses and SCCR

  • How-to

    Estimating transformer inrush current for protection coordination

    The rules of thumb are screening gates, not coordination inputs: reported inrush runs 8 to 30 times full-load current and lasts 10 cycles to a minute. Plot the decay curve Ipu = 6 × t^-0.31 with t in seconds — it passes through 25× at the first peak, 12× five cycles in and 3× at 10 s — keep the protective device curve above it and below the transformer damage curve, and handle cold-load pickup separately.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.

    Motors and motor starters