Current IntelPower LibraryShop main store

Explainer

Reverse feeding a step-down transformer on a high leg delta

Power distribution and transformers Published 7 min read

Short answer

Yes — feed the 240 V wye winding from your 240 V 4-wire delta service, leave X0 insulated and floating, take 480 V from the delta and corner ground it. Never tie X0 to the grounded center tap: it applies 0.50 per-unit zero-sequence voltage across windings rated 138.6 V and can circulate 25 per-unit current in a 2% impedance delta.

On this page
  1. The 240 V four-wire delta service
  2. What reverse feeding changes
  3. Why X0 must float
  4. Worked example: tying X0 on the high leg service with a 2% impedance unit
  5. What floating costs and what the corner bond buys
  6. Grounding the corner per code
  7. Commissioning checks
  8. When the delta-wye unit is the better buy
  9. Questions asked

Yes — the connection works. Feed the three wye terminals (X1, X2, X3) from the service, leave X0 insulated and unconnected, take 480 V line-to-line from the delta winding, and ground one corner of that delta. The one error that destroys the transformer is bonding X0 to the grounded center tap of the 4-wire service: it applies 0.50 per-unit zero-sequence voltage across windings rated 138.6 V and can circulate about 25 per-unit current in the delta of a 2% impedance unit. Left floating, the wye point rests at the supply's zero-sequence voltage and the only price is an energization transient. Keep overcurrent protection out of the grounded phase, and mark the high leg.

The 240 V four-wire delta service #

A 4-wire delta is not an ungrounded delta with a stray conductor. The fourth wire is the center tap of one utility winding, and that tap is the grounded conductor. To ground, two phases read 120 V and the third, the high leg, reads 240 × √3 ÷ 2 = 207.8 V, called 208 V. NFPA 70, the National Electrical Code, 2023 edition, requires in 110.15 that the conductor with the higher voltage to ground on a 4-wire, midpoint-grounded delta be durably identified, orange by common practice. Mark it at every termination and on the panel schedule. None of this blocks the reverse feed; it only fixes what X0 must never be tied to.

What reverse feeding changes #

The transformer is indifferent to direction as long as voltage ratio, frequency and kVA match. What changes is everything around it. Manufacturer application guidance on reverse-fed dry-type units lists the penalties: the voltage taps, wound into one winding, end up on the high-voltage output side, so the output is what moves when a tap is changed; inrush is higher when the unit is energized from the low-voltage winding; and the thermal rating reflects the intended direction of flow. Read the nameplate for kVA, %Z and any statement on reverse feeding before committing, then rerun the arithmetic below with the real impedance.

Because inrush is worse reverse-fed, the practice is to select the largest overcurrent device the code allows rather than a tight one. The trip-versus-inrush tradeoff is the one behind estimating transformer inrush current for protection coordination. The same nameplate impedance also sets the fault level on the output bus, and calculating transformer interrupting current from impedance shows the shortcut.

Why X0 must float #

The wye winding on the low-voltage side is a 138.6 V winding. Bond X0 to the grounded center tap and the three windings see 120, 120 and 207.8 V — 0.87, 0.87 and 1.50 pu on the winding base. The high-leg winding is overfluxed 50%, and the phasor sum of the three applied voltages no longer closes. That residue is zero-sequence voltage, and a closed delta is the one path zero-sequence current can take: it circulates inside the delta, reflects into the fed-side lines, and never appears on a ground-fault indicator because it never touches the grounding path. The unit runs hot at no load while every ground check reads clean. That is the zero-sequence circulating current mechanism of ungrounded wye-delta banks, and the cure is to withhold the path.

Insulate X0 and land no neutral at the transformer at all — not the service neutral, not a jumper to the enclosure ground bar. Grounds and neutrals are different things here: the enclosure, core and the secondary system still take their code-required grounding; only the wye point stays isolated. With no zero-sequence return, nothing circulates, while load current and negative-sequence current still pass.

Worked example: tying X0 on the high leg service with a 2% impedance unit #

Inputs, each with its source:

  • Phase-to-ground voltages of 120 V, 120 V and 207.8 V, from the 4-wire delta with grounded center tap — the service in question.
  • Winding rating of 240 ÷ √3 = 138.6 V, set by the wye design of this 480 V delta to 240 V wye unit.
  • Impedance of 2% on the unit's own base — an assumed typical value; the nameplate %Z replaces it.

Rule in words: bonding X0 to the grounded center tap applies the zero-sequence voltage — the phasor average of the three phase-to-ground voltages — across each winding, and the delta answers with circulating current limited only by per-unit impedance: circulating current ≈ V0 ÷ Z, both in pu. The equivalent form for a plain supply unbalance is unbalance ÷ (3 × Z).

Arithmetic:

  • Rated winding voltage: 240 ÷ √3 = 138.6 V.
  • Phase-to-ground phasors with the center tap as reference: 120∠0° V, 120∠180° V and 207.8∠90° V.
  • Zero-sequence voltage: V0 = (120 − 120 + j207.8) ÷ 3 = j69.3 V, so 69.3 V.
  • In pu on the winding base: 69.3 ÷ 138.6 = 0.50 pu.
  • Calibration: a 6% phase-voltage error is a 0.02 pu zero-sequence voltage, and 0.06 ÷ (3 × 0.02) = 1.0 pu — full-load current circulating from a 6% supply error.
  • The tied high leg: 0.50 ÷ 0.02 = 25 pu.

Result: the delta circulates up to 25 times rated winding current, at no load, for as long as the bond exists. The 25 pu is an upper bound set by the transformer impedance alone; source impedance trims it, but not to a survivable number.

Decision: the threshold is full-load current. Any tie that applies zero-sequence voltage above the impedance figure pushes the delta past it, and this tie applies twenty-five times that figure, so the bond must never be made. Insulate X0 and leave it floating; the point then settles at 69 V to ground, the normal resting state of this connection.

What floating costs and what the corner bond buys #

Floating, X0 rests at the phasor centroid — the 69 V computed above under balanced load — steady and harmless. The price lands at switch-on: reverse-feed guidance warns that an ungrounded wye point can push winding voltage transients on the order of 200% of rated during energization, so everything on the output bus must tolerate a brief overvoltage, and surge protection on that bus is worth adding for sensitive electronics.

Grounding a corner of the delta sets the reference of the secondary system only; it does nothing to the fed-side wye point, which still floats. Both connections are needed: X0 isolated on the supply side, one corner bonded on the output side.

Grounding the corner per code #

NFPA 70, 2023, 250.26 identifies the grounded conductor of a corner-grounded delta as one phase conductor. Article 240.22 bars an overcurrent device in series with an intentionally grounded conductor, so protection goes in the two ungrounded phases only and the grounded phase runs unbroken from transformer to load. Bond the secondary as a separately derived system per 250.30, with the grounding electrode conductor and bonding jumper sized and located per that article. Corner grounding leaves two conductors at 480 V to ground, so breakers, disconnects, drives and cable on that bus must be rated for corner-grounded 480 V duty per their own documentation. Label the secondary as a corner-grounded delta at the transformer and at the first disconnect, and keep the primary high-leg marking in place. Confirm the grounded-conductor and marking rules with the authority having jurisdiction and the equipment documentation; editions and local amendments differ.

Commissioning checks #

Nothing gets opened energized: the feeder comes off, gets locked out, and absence of voltage is tested at the transformer terminals before any termination is touched. With the load disconnected:

  • Secondary line-to-line: the nominal voltage on all three pairs; unequal readings mean a tap or winding problem, not the connection.
  • X0 to ground with X0 floating: about 69 V and steady. A solid 0 V means X0 is bonded to the grounded conductor somewhere — find and remove the bond.
  • Fed-side no-load current: small and balanced on all three lines. High or unequal no-load current, or a warm case with no load, means X0 is tied or the core is saturating.
  • After the corner bond: 0, 480 and 480 V from the three delta terminals to ground.
  • Phase rotation at the secondary terminals before any motor load is connected.

When the delta-wye unit is the better buy #

The reverse-fed delta is the right answer for one three-phase load at the higher voltage and nothing line-to-neutral. Buy the 240 V delta to 480/277 V wye unit when 277 V lighting is in the plan, when a system ground without corner-grounded overcurrent rules is wanted, or when the installation will outlive its labeling: the dedicated unit is the more expensive option and removes every special case in this article. A third route is reverse feeding step-down transformers in series for 480 V output, which keeps the same X0 rules at every stage. For the single machine, commit: floating X0, corner-grounded high-voltage delta, overcurrent devices in the two ungrounded phases, high leg marked.

Questions asked

What should X0 read to ground with the wye point left floating?

About 69 V on this high leg service, because the floating point rests at the supply's zero-sequence voltage. That reading is normal and should hold steady under balanced load; a solid 0 V means X0 is bonded to the grounded center tap somewhere and the delta is circulating current. Remove the bond before the transformer overheats at no load.

Can the corner-grounded 480 V delta supply 277 V loads?

No. A corner-grounded delta has no neutral: one phase is grounded and the other two sit at 480 V to ground, so there is no 277 V line-to-neutral circuit. Every load on that bus must be a 480 V line-to-line load. If 277 V lighting or receptacles are in the plan, use a 240 V delta to 480/277 V wye transformer instead.

Would a grounding bank or resistor on the wye point help?

No. A wye-delta grounding bank with its wye point resistor-grounded would sit at the same 69 V zero-sequence voltage this supply already has between ground and the floating point, so it would conduct continuous current through its impedance while changing nothing at the transformer. This service is already referenced to ground through the center tap; leave X0 floating.

How do you size the 240 V side overcurrent protection?

From the low-voltage line current, which is twice the 480 V load current at the same kVA because the voltage halves. Reverse-fed units also see higher inrush energized from the low-voltage winding, and manufacturer guidance is to pick the largest overcurrent device the code allows so inrush neither trips it nor fatigues it. Read the nameplate impedance before finalizing the choice.

Keep reading

  • Explainer

    Isolation transformer design checks for a new 480 V neutral

    The 650 kVA delta-star isolation transformer at Substation 2 is the right fix: its star point is a separately derived, solidly grounded 480 V neutral the 3P+E feeder can never supply. It is sound once five checks pass: load-based sizing, nameplate percent impedance, separately derived system grounding, redone protection settings, and no ties across the transformer's phase shift.

    Power distribution and transformers

  • How-to

    Calculating voltage drop through step-up and step-down transformers

    Yes. A primary voltage drop passes through the turns ratio almost one-for-one in percent — 5% low at 12 kV is 5% low at 480 V — so the study must run every segment from the generator terminals to the farthest branch outlet, combining drops as percentages.

    Power distribution and transformers

  • Explainer

    Why a grounded wye sources ground fault current and a delta does not

    Only a winding with a grounded neutral sources ground fault current: the neutral closes the zero-sequence loop, so a bolted line-to-ground fault on a grounded-wye 480 V system reaches tens of kiloamps. A delta has no neutral, so its zero-sequence path is open and the same fault carries only capacitive charging current of an amp or two, detected as a neutral voltage shift rather than current.

    Wiring, grounding and bonding