Current IntelPower LibraryShop main store

How-to

Calculating voltage drop through step-up and step-down transformers

Power distribution and transformers Published 9 min read

Short answer

Yes. A primary voltage drop passes through the turns ratio almost one-for-one in percent — 5% low at 12 kV is 5% low at 480 V — so the study must run every segment from the generator terminals to the farthest branch outlet, combining drops as percentages.

On this page
  1. Does a voltage drop on the transformer primary show up on the secondary?
  2. What voltage drop limits apply to feeders and branch circuits?
  3. Which parts of the emergency power path need a voltage drop calculation?
  4. How do I combine drops taken at different voltages?
  5. How much does the 500 ft medium-voltage run drop at 720 kVA?
  6. Is percent impedance the same as voltage regulation?
  7. Can transformer taps make up for feeder voltage drop?
  8. How do I fix the 250 ft and 125 ft runs when they miss the limit?
  9. Questions asked

Yes, it passes through. A transformer changes the voltage base, not the percentage error: hold the primary 5% low and the ideal secondary sits 5% low too, so 600 V lost up top is 24 V lost at the bottom. That means the voltage drop study for this emergency system covers the whole chain — generator terminals under load, both transformers, the 500 ft medium-voltage run, and the 250 ft and 125 ft low-voltage runs — not just the piece between the step-up and step-down units. The sections below give the limits, the segment-by-segment method, one worked chain, and the fixes when a segment misses.

Does a voltage drop on the transformer primary show up on the secondary? #

Yes — it passes through the turns ratio almost one-for-one in percent, before transformer regulation adds anything.

The nominal ratio of the 12 kV-to-480 V unit is 12,000 / 480 = 25:1. A 600 V reduction on the primary is 600 / 12,000 = 5% of primary voltage, and the ideal secondary follows: 5% × 480 V = 24 V. The working relationship is:

Secondary terminal voltage ≈ primary terminal voltage × effective tap ratio − load-dependent internal drop

The first term transfers any primary deviation straight through. The second is set by load current, power factor and winding impedance, and it is the only part a transformer adds on its own. This is why a study that stops between the two medium-voltage transformers tells you nothing about the voltage the loads actually receive.

What voltage drop limits apply to feeders and branch circuits? #

Plan to 3% on branch circuits and 5% combined feeder-plus-branch to the farthest outlet, the figures in NFPA 70, National Electrical Code, 2023 edition informational notes to 210.19(A) and 215.2(A)(1); the energy code adds mandatory 2% feeder and 3% branch limits at design load.

The NEC notes recommend, not require: informational notes are explanatory text, and as written they are not enforceable rules. Many jurisdictions amend them into mandatory limits, and reviewers enforce them, so treat them as the design target. ANSI/ASHRAE/IES 90.1, the energy standard for buildings (the 2019 and later editions carry this provision), makes 2% on feeders and 3% on branch circuits at design load a mandatory requirement wherever that code is adopted. Confirm the adopted editions and amendments with the authority having jurisdiction before the design is fixed.

One premise to note: the 5% total is measured from the source, and for an emergency system the source is the generator terminals, assumed to hold nominal voltage under load. A generator that sags under load is not voltage drop, but it lands on the same terminals.

Which parts of the emergency power path need a voltage drop calculation? #

Every segment from the generator terminals under load to the farthest branch outlet — roughly 875 ft of route across three voltage levels, and each piece carries a different current, so there is no single circuit to plug into one equation.

Work the path in this order:

  1. Generator terminal voltage at design load (720 kVA here) — regulator setpoint and loading set the starting point.
  2. Generator-to-step-up-transformer conductors — the length is not on the one-line yet; get it.
  3. Step-up transformer, low voltage to medium voltage — effective tap ratio plus regulation at actual load.
  4. The 500 ft medium-voltage run of three 2 AWG 15 kV 133% insulated conductors.
  5. Step-down transformer, medium voltage to low voltage — same treatment as item 3.
  6. Switchboard and distribution-panel connections inside the electrical room — short, but not zero impedance.
  7. Utilization transformer, 480 V to 120/208 V — incoming voltage, selected tap, loading, regulation.
  8. The 250 ft feeder to the 120/208 V panelboard — sized on that panel's design load, not the 720 kVA total.
  9. The 125 ft branch circuit to the farthest device — carrying only its own load, perhaps 16 A.

The cable description gives size and insulation level only; conductor material, resistance and temperature rating come from the cable data sheet. The "step-up transformer to step-down transformer only" shortcut omits items 1, 2, 6, 7, 8 and 9 — and it is exactly those items that decide the endpoint voltage.

How do I combine drops taken at different voltages? #

Convert each segment to a percentage of its own incoming voltage and chain them: total drop = 1 − (1 − d1)(1 − d2) … (1 − dn); adding raw volts from a medium-voltage segment to a low-voltage segment is meaningless.

Worked chain, illustrative: two transformers each regulating about 1.75% at their actual load (replace with your units' data), and the 0.08% medium-voltage feeder calculated next section:

1 − (1 − 0.0175)(1 − 0.0008)(1 − 0.0175) = 1 − (0.9825)(0.9992)(0.9825) = 0.0355, or 3.5%

Simple addition gives 1.75 + 0.08 + 1.75 = 3.58%, close enough while drops are small; run the final study with actual voltages propagated through impedances, where taps, power factor and unbalance change the answer. On the low-voltage base, nominal × 0.965 = 463 V at the switchboard at design load. NEMA MG 1 (2021 edition) permits successful motor operation within ±10% of rated voltage, so 463 V on a 460 V nameplate (414 to 506 V) is serviceable — but 3.5 of the 5% is spent before the first low-voltage run, leaving about 1.45% for the utilization transformer, the 250 ft feeder and the 125 ft branch combined.

How much does the 500 ft medium-voltage run drop at 720 kVA? #

About 9 V line-to-line, or 0.08% — negligible: at 12 kV the 720 kVA transfers at only 34.6 A, so 500 ft of 2 AWG aluminum drops almost nothing, and this run is not where your budget goes.

The arithmetic, with every input stated:

  • Current: I = S / (√3 × V) = 720,000 VA / (1.732 × 12,000 V) = 34.6 A
  • Resistance: 2 AWG aluminum ≈ 0.31 Ω per 1000 ft at 75 °C (DC resistance per NEC Chapter 9 Table 8, temperature-adjusted; reactance is negligible at this length — confirm against the 15 kV cable data sheet)
  • Drop: VD = √3 × I × R × L = 1.732 × 34.6 A × 0.31 Ω/kft × 0.5 kft = 9.3 V
  • Percentage: 9.3 V / 12,000 V = 0.08%

If the conductors were 2 AWG copper at about 0.19 Ω/kft, the drop would be 1.732 × 34.6 × 0.19 × 0.5 = 5.7 V, or 0.05%. This is an estimate to check against the governing code and the cable data, but the margin is so wide that the decision stands either way: the 2 AWG run passes on voltage grounds, and its size stands or falls on ampacity and fault duty, not on drop.

Is percent impedance the same as voltage regulation? #

No — percent impedance comes from the short-circuit test and governs fault current and paralleling; regulation is the load-dependent secondary voltage change at a stated power factor, and the two numbers are not interchangeable.

Percent impedance is the voltage, in percent of rating, needed to circulate rated current with the secondary shorted — which is why it sizes your downstream fault duty. Regulation at a given load and power factor runs roughly as the load fraction times (%R × cos φ + %X × sin φ). The reactive term dominates at 0.8 power factor, so a unit with 5 to 6% impedance can regulate around 3 to 4% at full load and a fraction of that at light load. The 1.75%-per-transformer figures used above are illustrative inputs, not nameplate facts: get R and X, or the regulation curve, from the transformer test report for the final study — the load-loss figure gives you %R directly. Never read an impedance like 5.75% off a nameplate and book 5.75% of steady-state voltage drop; that overstates the loss at most power factors.

Can transformer taps make up for feeder voltage drop? #

No — taps are fixed-percentage ratio changes, commonly two above and two below nominal at ±2.5% and ±5%, built in at manufacture; they correct a steady primary-voltage mismatch, not a load-dependent drop that varies from light load to full.

The percentages are predetermined when the transformer is built; you select a position by reterminating, you do not get a continuous adjustment. Raise a tap to chase full-load drop and the light-load voltage rides high, because the correction is constant while the problem is not. The utilization-nameplate spread — 480 V supply with 460 V motor nameplates, 208 with 200, 120 with 115 — is the few percent of headroom the 5% recommendation already assumes, so spending taps to re-eat it double-counts. The decision: size the conductors to the limits first, then set taps so the no-load secondary sits at or a hair above nominal, and recheck under load. A tap change is off-load work — generator locked out, transformer isolated, and absence of voltage verified at the terminals before anything is reterminated.

How do I fix the 250 ft and 125 ft runs when they miss the limit? #

Upsize conductors first: at 96 A three-phase and 208 V, 250 ft of 3/0 aluminum drops 5.4 V (2.6%, over the 2% energy-code feeder limit) while 250 kcmil drops 3.5 V (1.7%); the 125 ft, 16 A, 120 V branch needs 8 AWG copper, not 12 AWG.

The arithmetic, illustrative inputs stated (96 A panel design load at 208 V three-phase; 16 A branch at 120 V; resistance values at 75 °C from NEC Chapter 9 Table 8 with temperature adjustment):

  • Feeder, 3/0 aluminum at ≈0.13 Ω/kft: VD = √3 × 96 A × 0.13 Ω/kft × 0.25 kft = 5.4 V on 208 V = 2.6% — fails the 2% feeder limit.
  • Feeder, 250 kcmil aluminum at ≈0.085 Ω/kft: VD = 1.732 × 96 × 0.085 × 0.25 = 3.5 V = 1.7% — passes.
  • Branch, 12 AWG copper at ≈1.9 Ω/kft: VD = 2 × I × R × L = 2 × 16 A × 1.9 Ω/kft × 0.125 kft = 7.6 V on 120 V = 6.3% — fails badly.
  • Branch, 8 AWG copper at ≈0.74 Ω/kft: VD = 2 × 16 × 0.74 × 0.125 = 3.0 V = 2.5% — passes the 3% branch limit.

Treat these as estimates to check against the governing code and equipment documentation. The fix ladder, in order of cost and sanity: verify and set the generator regulator to hold nominal voltage at design load with the manufacturer's approved settings, the cheapest volts you will buy; upsize the conductors as shown — the same arithmetic goes into fixing voltage drop on a long 277 V lighting feeder; move the 120/208 V panelboard closer to its load, which often beats buying copper; and keep a buck-boost transformer for the one punishing run, checking its correction range and load compatibility against conductor changes. A fixed shunt capacitor bank is not a voltage regulator: its output follows reactive demand, so at light load it can leave the bus high and the power factor leading, and it needs a power-factor, harmonic and generator-compatibility study first. A current-transformer bias added to the generator sensing circuit is a control modification for the generator manufacturer, not a feeder-sizing remedy.

The decision for this path: keep the medium-voltage transfer as drawn — it costs you 0.08%; hold the generator at nominal under load; let taps align the ratios to nominal; and spend the conductor upsizing where the current actually lives, on the 250 ft and 125 ft runs.

Questions asked

Are the NEC voltage drop percentages enforceable?

As written, no: the 3% and 5% figures sit in informational notes, which the 2023 NEC treats as explanatory rather than enforceable rules. Many state and local amendments make them mandatory, inspectors do enforce them, and the energy code limits are mandatory where that code is adopted. Treat 3% on branch circuits and 5% total as the design target, and confirm the adopted editions and amendments with the authority having jurisdiction.

Why does stepping up to medium voltage cut the voltage drop so much?

Current, not distance, drives the drop. The same 720 kVA draws 866 A on the low-voltage side but only 34.6 A on the medium-voltage side — twenty-five times less current, exactly the turns ratio — so the resistive drop collapses with it for the same conductor. That is why 500 ft of 2 AWG loses 0.08%, while the equivalent low-voltage transfer would need an unbuildable conductor to stay inside 5%.

Does the voltage drop note apply to the transformers themselves?

The informational notes speak to conductor drop between the source and the farthest outlet; a tap position or a supply-voltage deviation is a voltage change, not conductor loss. Track both anyway, because the load only sees the voltage that actually arrives: regulation, tap settings and conductor drop all belong in the same running budget even though the notes address only the conductors.

What happens if the generator runs 2% below nominal under load?

Everything downstream shifts down about 2% through both transformer ratios before any conductor drop is counted, so a chain already sitting at 4.5% total lands near 6.5% at the farthest outlet. Set and verify the regulator setpoint at design load first, using the generator manufacturer's approved adjustments — it is the cheapest correction on the whole project.

Do I need X and R separately, or just percent impedance, to predict regulation?

You need both components. Regulation at a stated load and power factor follows the resistive part times cosine plus the reactive part times sine, scaled by load fraction, so a 6% impedance unit with low resistance can still regulate several percent at 0.8 power factor. Get the reactance-to-resistance split or the regulation curve from the test report; the nameplate impedance alone will not predict steady-state voltage.

Keep reading

  • How-to

    Fixing voltage drop on a long 277 V lighting feeder

    The drop budget on this feeder limits the loop to 0.40 Ω — 0.267 Ω per conductor — so size up the copper or split the load across the three phases of the wye system, which relaxes the limit sixfold. Raise the source only after the two-endpoint check, because a fixed boost that fixes full-load voltage also overvoltages the panel at light load.

    Power distribution and transformers

  • How-to

    Powering a 600 V three-phase machine from 240 V single phase

    The nameplate works out to 20.8 kVA of apparent power. Fed from the single-phase shop service, that is about 87 A before converter and transformer losses, so the machine needs a rotary phase converter sized to its total demand plus a reverse-connected step-down transformer, unless tracing shows the internals run on 200 to 220 V. Verify loaded voltage balance before releasing the machine to production.

    Power distribution and transformers

  • Selection guide

    Sizing a transformer for a 200 HP across-the-line motor start

    Select a 1000 kVA transformer with nameplate impedance of 6.5% or less. The 3 kVA-per-HP rule gives 600 kVA for the 200 HP pump alone; adding 390.9 kVA of always-on load gives 990.9 kVA, so that is the screening size. The dip screen confirms it: 8.8% sag at 5.75% impedance, inside the 10% target, while 750 kVA would need 4.9% impedance to pass.

    Power distribution and transformers