Current IntelPower LibraryShop main store

Selection guide

Sizing a VFD for a three-phase motor on single-phase input

Variable frequency drives Published 7 min read

Short answer

On single-phase input, size the drive's continuous output current at no less than twice the motor nameplate full-load amps when the drive's 50% derating applies, and feed it from a branch circuit sized to 125% of the drive's published single-phase input current — never from the ideal wattage estimate. For a 10 hp, 208 V motor that means a drive rated at least 61.6 A output.

On this page
  1. What single-phase input changes inside the drive
  2. The selection rule: rated output current at twice motor FLA
  3. Size the input circuit from the drive's rated input current
  4. Wiring and parameter order
  5. Worked example: 10 hp motor fed from 240 V single phase
  6. Proving the selection under load
  7. When a drive is the wrong phase converter
  8. Questions asked

Size this drive by current, not by horsepower. A 50% single-phase-input derating means the drive's continuous rated output current must be at least twice the motor's nameplate full-load amps — for the 10 hp example in this article, at least 61.6 A. The inverter still makes a true three-phase output, but only two rectifier legs charge the DC bus, and the parts in that path carry the difference. The input circuit is a separate decision — conductors, overcurrent device and disconnect come from the drive's published single-phase input current, not from a wattage estimate. Below: what derating protects, the selection table, the NEC input rule, the wiring order, and a fully worked 10 hp example.

What single-phase input changes inside the drive #

On three-phase input, six diode pulses per cycle keep the DC bus topped up. On single phase, two diodes charge the bus only near the crest of each half-cycle, so the bus capacitors carry the load between peaks. Three things follow: the conducting diodes see higher RMS and peak current, the capacitors absorb more ripple current, and the bus voltage dips further between charging pulses.

The inverter is unaffected in principle — it still synthesizes a true three-phase output, and the motor never runs as a single-phase load. The derating is an input-and-bus limit, and it shows up in protection too. A three-phase-rated drive fed from one phase can flag an input phase loss, because that detection is based on DC-link voltage behaviour, and a bus already rippling hard from single-phase charging can cross the same threshold on ripple alone. A drive documented for single-phase input tolerates the missing phase; an undersized one still trips on excess bus ripple.

The selection rule: rated output current at twice motor FLA #

A 50% derating means the drive may deliver half of its three-phase output rating, so the rating you buy must cover the motor doubled:

Required drive output current ≥ motor FLA ÷ 0.50 = 2 × motor FLA

That is not the same as a drive 50% larger by horsepower. Published single-phase rules vary by manufacturer and frame:

Published single-phase-input rule What the drive may deliver Output rating to buy for a motor at FLA
50% derating 0.50 × rated output current 2.0 × FLA
57.8% of three-phase rating (up-size by √3) 0.578 × rated output current 1.73 × FLA
Two-thirds of output current 0.667 × rated output current 1.5 × FLA

Field guidance ranges from about 50% to 70% depending on maker and frame. The manual for the exact catalog number governs; when no published figure is in hand, select at 2 × FLA — the row that costs one frame size and removes the question.

Selection is not finished at continuous current. Acceleration torque draws more than running current, and a drive limits at its peak current, not its running rating — a loaded or high-inertia start can sit in current limit and stall before reaching speed. Match the drive's published overload duty, current and time, to the machine's worst start rather than to its nameplate horsepower.

Size the input circuit from the drive's rated input current #

NFPA 70, the National Electrical Code, 2023 edition, Article 430, Part X, covers adjustable-speed drive systems; its 430.122 requirement is that conductors supplying a power conversion unit have an ampacity of at least 125% of the unit's rated input current. Confirm the requirement with your authority having jurisdiction and the drive documentation, since editions and local amendments differ.

The number you apply it to is the drive's published single-phase input current for that catalog number, because it already contains the pulsed input waveform and the drive's losses. The clean wattage estimate for this case — 34.5 A, arithmetic in the worked example below — assumes unity input power factor and a lossless drive, so treat it strictly as a lower bound. VFD supply components are sized by rated input current, and the same published figure sets the overcurrent device within the manual's maximum allowable rating. Also confirm the drive's short-circuit current rating meets or exceeds the available fault current on that branch; a drive selected for current but not for fault duty still fails the installation.

Wiring and parameter order #

  1. Record the motor nameplate first: voltage, full-load amps, frequency, rated speed, and confirm the winding is connected as the nameplate directs.
  2. Confirm the exact catalog number is documented for 240 V single-phase input, and use the input-terminal arrangement the manual specifies. Published single-phase wiring guides feed two input terminals and jumper the third to its neighbour (L2 to L3); that is a guide, not a substitute for the manual of the unit on your bench.
  3. Set input phase-loss monitoring the way the manual directs for single-phase operation — this kind of setting normally lives with the drive's protection and fault configuration. If the model has no documented single-phase input, stop and pick one that does.
  4. Select by continuous output current using the 2 × FLA rule, then check overload duty against the machine's worst start.
  5. Enter the motor nameplate data exactly — the nameplate voltage, not the supply voltage — so the volts-per-hertz pattern matches the winding.
  6. Set acceleration and current limit for the driven machine before the first run.

An input reactor is worth considering on the line side: it trims the current peaks the rectifier draws and the distortion returned to the service, and the trade-offs covered in choosing a line reactor or motor reactor for a VFD apply unchanged. It does not add a third phase, add bus capacitance, or reduce the derating. Because the two-pulse input current is harmonic-rich, one mid-size drive on a lightly loaded service is exactly the case covered in assessing VFD harmonics when one small drive runs a plant.

Worked example: 10 hp motor fed from 240 V single phase #

Inputs, with sources:

  • Motor: 10 hp, 208 V three-phase, from the case as asked. Nameplate FLA governs; where it is not at hand, NFPA 70 Table 430.250 lists 30.8 A for that size and voltage.
  • Supply: 240 V single-phase.
  • Derating: the manufacturer's 50% figure for this drive on single-phase input.
  • Efficiency assumption for the input estimate: 0.90, the assumption behind the roughly 35 A figure people quote.

Rules in words: divide motor FLA by the allowed fraction to get the drive rating; convert shaft power through efficiency and voltage to get an ideal input current; multiply the drive's rated input current by 1.25 for conductor ampacity.

Drive rating: 30.8 A ÷ 0.50 = 61.6 A. Select a 240 V-class drive whose continuous output current is at least 61.6 A. For contrast, Table 430.250 shows a 15 hp, 230 V three-phase motor at 42 A, and a 15 hp-class drive lives in that territory — the buy-50%-more-horsepower answer falls about 20 A short.

Ideal input current: 10 hp × 746 W/hp = 7,460 W; 7,460 W ÷ 0.90 = 8,289 W; 8,289 W ÷ 240 V = 34.5 A, assuming unity input power factor and a lossless drive.

Branch-circuit floor: 1.25 × 34.5 A = 43.1 A even under those ideal assumptions — at minimum #8 AWG copper at 75 °C (50 A, Table 310.16). The real sizes come from the selected drive's published single-phase input current × 1.25, and they will land above the estimate.

Decision: buy the drive rated at least 61.6 A output, take its published single-phase input current, and size conductors, overcurrent device and disconnect from it. If the data sheet publishes no single-phase input current, that model was not documented for this service. These results are estimates — check them against the governing code edition and the equipment documentation before ordering.

Proving the selection under load #

Before any of this, open nothing energized: lock out the supply, prove absence of voltage, and respect the drive's stated DC-bus discharge time before touching terminals.

  • Energize with no run command and confirm no input or bus fault appears at rest.
  • Run the motor uncoupled or unloaded where the machine permits, and watch that acceleration completes without touching current limit.
  • Add load in steps, recording acceleration time, peak output current, running current and DC-bus indication from the drive's diagnostics.
  • Measure both line conductors with a true-RMS meter rated for distorted waveforms; an averaging clamp under-reads pulsed drive input current.
  • Run at the highest continuous load long enough to expose heating, and treat repeated ripple-related trips as a sizing symptom, not a tuning problem.

No-load success validates nothing. The decisive test is acceleration plus continuous duty at maximum mechanical load, inside the derated current and thermal limits.

When a drive is the wrong phase converter #

If the machine needs no speed control, an oversized drive is doing one job — making three phases — at a high cost in frame size. A motor swap or a rotary converter is often the simpler install, and the trade-offs in running a three-phase motor on single-phase 208 V cover that ground. When you do need speed control or a controlled start, the derated drive is the standard answer, and it is done routinely.

Questions asked

Why can't I size the branch circuit from the 34.5 A estimate?

Because it is a lower bound, not a design value. The 34.5 A figure assumes unity input power factor and a lossless drive; the drive's published single-phase input current already includes the pulsed waveform and the losses. Conductor ampacity is 125% of that published figure under NFPA 70, 430.122. Even the ideal floor computes to 43.1 A.

Will the drive trip on input phase loss when fed single phase?

That depends on the drive. Models documented for single-phase input tolerate the missing phase; others latch an input phase loss fault and must not be used this way. Detection is based on DC-link voltage, so a heavily rippling bus on an undersized drive can trip even when single-phase operation is allowed. Read the fault table for your exact model.

Do I enter the motor's 208 V or the supply's 240 V for the motor data?

Enter the nameplate voltage. The volts-per-hertz pattern must match the winding: configuring a 208 V motor as 240 V raises magnetizing current and heating. Dual-voltage motors marked 208–230/460 are normally content either way, but the drive's motor-data entry should still match the connection actually made.

Does an input reactor reduce the required derating?

No. A reactor trims the line-side current peaks and the harmonics sent back into the service, but it changes nothing about two-diode charging or DC-bus ripple, which is what the derating protects. Keep the full 2 × FLA selection and treat the reactor as power-quality hardware, not as capacity.

Can I pick a smaller drive if the motor never runs at full load?

Only if you can prove the load current, including acceleration, stays inside the drive's derated output current and its overload duty. Record the running and peak current the machine actually draws with a true-RMS meter, then check both against the derated continuous and overload ratings. A high-inertia start that sits in current limit stalls before reaching speed even when running current would have fit.

Keep reading

  • Selection guide

    Choosing a line reactor or motor reactor for a VFD

    Pick the side first. A line reactor goes between supply and drive input, sized on drive input amps at 3% impedance for transient buffering or 5% for harmonic reduction; a motor reactor goes between drive output and motor, sized on motor FLA, for reflected-wave protection on long shielded leads. The two are not interchangeable.

    Variable frequency drives

  • Explainer

    Running a three-phase motor on single-phase 208 V

    Yes — a spinning three-phase motor fed across two terminals regenerates the third leg, but winding heating caps it near 30-40% of rated horsepower, so it is a bench trick, not a supply. For real loads, use a rotary phase converter with an idler at least the next size above the largest motor, or a single-phase-input VFD for motors only — never a drive for amplifiers or power supplies.

    Motors and motor starters

  • How-to

    Assessing VFD harmonics when one small drive runs a plant

    No filter is justified on ratings alone: 6 hp × 0.746 kW/hp = 4.48 kW is 6.6% of 68 kW connected capacity. Measure voltage THD at the shared bus with the drive off and then running, and read the drive's input current. If the bus stays under IEEE 519's 5% THD limit with no single harmonic above 3%, leave it alone; if it climbs over, an input reactor on the drive is the fix.

    Power quality and harmonics