Sizing cable withstand with fuse total I²t let-through

Protection: breakers, fuses and SCCR Published 6 min read

Short answer

Use the fuse's total clearing I²t, read at your system voltage and prospective fault current, not the pre-arc value. Compare it against the cable's adiabatic withstand from IEEE Std 242. For a 400 A Class J fuse on 500 kcmil copper XLPE with a 10 kA fault, withstand is about 1.29 × 10⁹ A²s and the fuse let-through passes with large margin, so ampacity or voltage drop sets the size, not fault energy.

On this page
  1. Write down the three inputs first
  2. Do not use these four numbers
  3. Set the fuse rating against load and ampacity
  4. Check voltage drop at full load
  5. Calculate the cable's adiabatic withstand
  6. Compare the fuse total I²t against the withstand
  7. Confirm the result end to end
  8. Questions asked

Use the fuse's total clearing I²t, read at your system voltage and your calculated prospective fault current, when you check a supply cable against its fuse. The pre-arc (melting) I²t belongs to semiconductor protection and fuse-to-fuse coordination; the cable absorbs energy during both the melting and the arcing intervals, so only the total applies to conductor heating.

If the resulting size looks oversized, the cause is almost never the method. It is usually one of the wrong-input items in the first step below, or the plain fact that ampacity or voltage drop set the size long before fault energy did. Worked through this article: a Class J 400 A fuse, 500 kcmil copper with XLPE insulation, a 480 V circuit with 10 kA of prospective fault current at the fuse. That cable's withstand is about 1.29 × 10⁹ A²s and the fuse let-through clears it with roughly two orders of magnitude to spare.

One safety note before any of this is measured or changed in the field: de-energize the circuit, lock it out and verify absence of voltage at the terminals before opening any panel, gutter or fuse switch.

Write down the three inputs first #

Cable withstand and fuse let-through are both functions of inputs that people routinely mix up, so fix them on paper before any arithmetic:

  • System voltage. Fuse total I²t rises with applied voltage, because arcing energy does.
  • Prospective fault current at the cable's source end, from your short-circuit study. Let-through is read at this value, not at the datasheet table maximum. The method behind that number is the same one used when calculating source impedance from prospective short-circuit current, so the two studies should agree.
  • The exact fuse class and rating, for example Class J, 400 A. Different classes with the same amp rating let through very different energy.

Do not use these four numbers #

Each of these produces a wrong cable size:

  • Pre-arc I²t as the cable's fault energy. It understates the heating because the current keeps flowing through the arc after the element melts. Reject it for cable work.
  • Total I²t read at the fuse's maximum rated voltage for a lower-voltage circuit. That adds arcing energy that your circuit cannot deliver.
  • Total I²t read at the top of the prospective-current range instead of at your calculated fault current.
  • A time-current curve reading alone for a high-current fault. When the fuse clears in a fraction of a cycle, the curve cannot resolve the event well enough to replace an I²t comparison. The curve is still fine for overload-range checks.

Set the fuse rating against load and ampacity #

Rating comes before let-through. The fuse's rated current must sit above the normal load current and at or below the cable's ampacity under the actual installed conditions: ambient temperature, grouping and installation method, not the free-air table value. For the worked case, NEC Table 310.16 (NFPA 70, 2023 edition) gives 430 A for 500 kcmil copper at 75 °C before corrections, and the 400 A Class J fuse sits between the load limit and that ampacity, so this gate passes. Confirm your corrected ampacity and any local amendments with the authority having jurisdiction and the cable documentation.

Check voltage drop at full load #

Calculate voltage drop at full-load current over the actual run length. On long runs this gate sizes the cable up regardless of fault energy, and a cable that is large for its fault withstand for that reason is correct, not a calculation error. Record which criterion actually sets the size: ampacity, voltage drop or fault withstand. That tells you whether a let-through result that looks generous is an error or simply not the governing limit.

Calculate the cable's adiabatic withstand #

For a fault cleared in seconds or less, treat conductor heating as adiabatic: no heat leaves the conductor during the event. IEEE Std 242, the Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, gives the conductor short-circuit temperature relation in its conductor-protection chapter. In kcmil and kiloamperes it takes this form:

I = CM × sqrt( 0.0297 × log10( (Tf + 234.5) / (Ti + 234.5) ) / t )

CM is conductor area in kcmil, Tf the final short-circuit temperature, Ti the initial operating temperature, t the duration in seconds, I the permissible current in kA. Rearranged, the withstand energy is independent of t:

I²t withstand = CM² × 0.0297 × log10( (Tf + 234.5) / (Ti + 234.5) )

Worked example, stated as an example: CM = 500 kcmil, Tf = 250 °C, Ti = 90 °C, t = 0.01 s.

  • log10(484.5 / 324.5) = log10(1.4931) ≈ 0.1741
  • I = 500 × sqrt(0.0297 × 0.1741 / 0.01) = 500 × sqrt(0.5171) ≈ 359.5 kA
  • I²t withstand = 359,500² × 0.01 ≈ 1.29 × 10⁹ A²s

Take Tf and Ti from your cable's insulation data and the edition of the standard you design to, not from these example temperatures. Keep the result in A²s, the same unit as the fuse datasheet.

Compare the fuse total I²t against the withstand #

Open the manufacturer's let-through data for the exact class and rating, and read the total clearing I²t at your system voltage and your prospective fault current. The pass rule is:

Total clearing I²t ≤ cable I²t withstand

If it fails, increase the conductor size or select a fuse class with lower let-through. If a current-limiting fuse is what brings the energy down, the interaction in the piece on when a current-limiting fuse protects a circuit breaker shows the same let-through logic applied to equipment ratings instead of cable.

Scale check for the example. Without current limiting, 10 kA flowing for the full 0.01 s would deliver 10,000² × 0.01 = 1.0 × 10⁶ A²s, about 1,300 times below the 1.29 × 10⁹ A²s withstand. The 500 kcmil copper sits far from its thermal limit at this fault level, so fault energy did not force that conductor size; ampacity or voltage drop did. A real current-limiting fuse clears well inside 0.01 s, so the actual let-through is smaller still. For the comparable exercise on a metric-sized XLPE conductor, the knowledge-base page on 50 mm² XLPE cable inrush withstand works the same k²S² arithmetic.

Confirm the result end to end #

Run the whole chain once and record the outcome of each gate:

  1. Load current below the fuse rating.
  2. Fuse rating at or below the corrected cable ampacity.
  3. Voltage drop within your design limit at full load.
  4. Fuse total clearing I²t, at the correct voltage and fault current, less than or equal to the cable withstand.
  5. All values in matching units, A²s on both sides.

A gate that fails names its own fix: a failing ampacity or voltage-drop gate takes a larger conductor; a failing energy gate takes a larger conductor or a lower-let-through fuse. If a temporary like-for-like replacement has to go in tonight, keep the same fuse class, rating and conductor size, and complete the full chain above before any permanent change. This is an estimate built on tabulated constants and datasheet data; check the final numbers against the governing code edition and the manufacturer documentation for your fuse and cable.

For a deeper treatment of the short-circuit data feeding step 1, the recommended practice behind the withstand formula is IEEE Std 242 and its companion short-circuit calculation practice; both repay the reading if you do this comparison regularly.

Questions asked

Why does using total clearing I²t make the cable look oversized?

Two reasons. Total clearing I²t includes the arcing phase, so it is always larger than the pre-arc value. And datasheet tables are often published at the fuse's maximum rated voltage, where arcing energy is highest. Read the value at your actual system voltage and your calculated prospective fault current, then confirm which criterion sets the conductor size. For most feeders the answer is ampacity or voltage drop, not fault energy.

When is pre-arc I²t the right number?

Pre-arc (melting) I²t is the energy that melts the fuse element before the arc forms. It is the working value for semiconductor fuse selection, where the device being protected must not melt before the fuse, and for coordinating a smaller downstream fuse against a larger upstream one. Cable heating during a high-current fault uses the total clearing I²t, because the conductor absorbs energy during both the melting and the arcing intervals.

The fuse datasheet gives I²t in kA²s and my withstand is in A²s. How do I compare?

Convert before comparing: 1 kA²s equals 10⁶ A²s, so a datasheet value of 90 kA²s is 9.0 × 10⁷ A²s. A frequent error is comparing kA²s directly against an A²s withstand or forgetting to square the kA figure. Write both numbers in A²s, then apply the pass rule: the fuse total clearing I²t must be less than or equal to the cable adiabatic withstand.

Keep reading

  • Explainer

    When a current-limiting fuse protects a circuit breaker

    A downstream current-limiting fuse protects a circuit breaker only where the manufacturer has tested and listed that exact breaker–fuse pair as a series combination for the voltage and available fault current. A peak let-through value is not that approval: crest and rms are different test quantities, the breaker-to-fuse span sees the full prospective current, and three-pole ratings were not tested for single-pole ground duty. On a 110 kA bus with a 75 kAIC breaker, demand the tested combination rating in writing or change the design.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Setting 50 and 87 functions on a fused medium voltage motor starter

    On a NEMA Class E2 fused starter the current-limiting fuses are the short-circuit interrupter, so the phase 50 element defaults to alarm-only or disabled unless the coordination study and the contactor's interrupting rating support tripping. The 87 element follows the same test through its differential zone. Ground fault is separate: on an HRG 4.16 kV system with a core-balance CT and about 25 A or more of available ground-fault current, set 50G.

    Protection: breakers, fuses and SCCR

  • Selection guide

    When a Class L fuse actually cuts arc flash energy

    A current-limiting Class L fuse reduces arc flash incident energy only when the calculated arcing current at the fuse exceeds its current-limiting threshold, roughly 20 to 50 times its rating for large time-delay sizes. Below that threshold the fuse clears on its time-delay curve and can leave incident energy far above a static-trip breaker, so fuse size, arcing current and coordination get checked separately.

    Electrical safety and codes