Explainer
SKM ANSI breaker library fields: SC rating, parting time, speed
Short answer
In an ANSI breaker library, Rated SC Rating (kA) holds the symmetrical interrupting current for any breaker rated from about 1964 onward, Parting Time (Cyc.) runs from fault inception to contact parting, and Speed (Cyc.) is the total clearing time including arcing. IEC and AS 62271.100 datasheet values must be mapped by definition, because the IEC opening time begins at trip-coil energization, not at the fault.

On this page
In the SKM PTW ANSI breaker library, Rated SC Rating (kA) is a symmetrical rms current, Parting Time (Cyc.) is the interval from fault inception to contact parting, and Speed (Cyc.) is the total clearing time from that same zero, arcing included. The trip signal arrives inside the parting interval, not at its beginning. An IEC or AS 62271.100 datasheet therefore cannot be transcribed field by field, because IEC times run from a different zero. What follows is the basis for each field, a worked example with the arithmetic shown, and the mapping that puts each datasheet quantity in the right place.
What each field answers #
A fault, a trip and an interruption happen in sequence, and each library field describes one step of that sequence against its own time zero.
| Library field | What it holds | Counted from |
|---|---|---|
| Rated SC Rating (kA) | Symmetrical rms interrupting capability at rated voltage | Not a time |
| Parting Time (Cyc.) | Protection response plus opening travel, up to contact parting | Fault inception |
| Speed (Cyc.) | Parting time plus arcing, up to current extinction | Fault inception |
Each field answers a different question about the same event, so a value moved between fields corrupts the study in a specific direction, and a trip-based time in a fault-based field is the error the software will not catch. Convert cycles to milliseconds before comparing with a relay or an IEC datasheet: milliseconds equal cycles divided by frequency, times 1000, so one cycle is 16.7 ms at 60 Hz and 20 ms at 50 Hz.
Why Rated SC Rating is a symmetrical current #
Breakers rated from about 1964 onward carry symmetrical-current ratings, and anything manufactured after 1970 can be treated that way without exception. IEEE C37.04-2018 defines the rating structure for AC high-voltage circuit breakers above 1000 V, and its application guide, IEEE C37.010-2016, is written for breakers rated on a symmetrical current basis: the interrupting capability is a symmetrical rms current, and the asymmetry the breaker must interrupt is carried by the rating structure and its test duty, not by the number typed into the field.
The duty comparison therefore never puts the DC offset in this field. The study's interrupting-time network gives the symmetrical current at the contact-parting instant, and that value is compared with the capability — the basis covered in which bolted fault current to use for breaker duty and arc flash.
A breaker still on the older total-current basis is the exception: do not enter its nameplate figure, because the field will read it as symmetrical. Obtain the manufacturer data for that frame and year and convert by the method that document states; the multiplying factors involved are those of total-current versus symmetrical method for asymmetrical fault calculations. Confirm the edition in force for the unit, and any rating the study relies on, with the manufacturer data and the authority having jurisdiction before the study is used for compliance.
Why Parting Time counts from fault inception #
The field's zero is the fault itself, so the interval contains the protection response and then the opening travel: relay or trip-unit operating time first, mechanism time to contact separation second. Entering a trip-to-part interval instead makes the model part the contacts earlier than they part in service, and two results move. The time-current curve clears the fault too early, which flatters coordination and lowers calculated incident energy, and the duty is evaluated at an instant with less DC decay, which overstates what the breaker must interrupt.
The size of that decay follows the system X/R: after n cycles, the fraction of the initial DC offset still present is e^(-2πn/(X/R)), which is why the same fault looks different to a fast and a slow breaker on the same bus.
Why Speed includes the arc #
Speed ends at current extinction, not at contact separation. The arc burns from parting until a current zero extinguishes it, typically 0.5 to 0.75 cycles for a healthy interrupter, so Speed is Parting Time plus that arcing time, and it is the clearing time that coordination and arc-flash runs should see. The mechanical opening time is neither a parting time nor a clearing time.
PTW's arc flash evaluation reads trip time from the protective-device curve and adds the breaker time, with a default maximum arcing duration of 2 seconds — the mechanism behind why SKM reports an 18-inch arc flash boundary and 2 seconds. An understated speed clears faults on paper faster than the breaker ever will, lowering incident energy and hiding coordination gaps. An arc-flash label printed from a model whose clearing time is a guessed speed is not a basis for choosing PPE, so verify the entry before the study is issued.
Worked example: checking a 60 Hz entry end to end #
Hypothetical inputs, all stated: a three-phase 60 Hz bus; a 15 kV class breaker with a Rated SC Rating (kA) of 20, symmetrical; Parting Time (Cyc.) 3; Speed (Cyc.) 3.5; an X/R of 17 at the bus; and an interrupting-network duty of 17.8 kA symmetrical from the short-circuit study.
- Internal consistency: Speed minus Parting is 0.5 cycle of arcing, inside the typical band, so the pair describes a plausible interrupter.
- Time conversion: the parting interval is 3 ÷ 60 × 1000 = 50 ms, total clearing is 3.5 ÷ 60 × 1000 = 58.3 ms, and the arc takes the 8.3 ms between them.
- DC decay at parting: e^(-2π × 3 ÷ 17) = e^(-1.109) = 0.33, so 33 percent of the initial offset remains when the contacts part. An X/R of 17 is the value the symmetrical rating structure is built around — a DC time constant of 17 ÷ (2π × 60) = 45 ms — so the tested capability already covers that remaining offset.
- Duty check: 17.8 ÷ 20 = 0.89, meaning the bus demands 89 percent of the symmetrical capability, and the entry passes with an 11 percent margin.
- Sensitivity check: replace the parting time with a 1.5-cycle trip-to-part figure and both results move — the offset remaining rises to e^(-2π × 1.5 ÷ 17) = 0.57, and the curve clears 25 ms early. When editing one time field moves duty and clearing together, the error is the time base, not the fault current.
The result is an estimate: the duty comes from the study's network and the rating from the manufacturer's data, so both are checked against the governing code and the breaker's documentation before the finding is issued.
Filling the fields from an AS 62271.100 or IEC datasheet #
AS 62271.100 adopts IEC 62271-100, whose 2021 edition applies to current datasheets, and its quantities are defined against different zeros than the ANSI fields. Map each one by definition:
- Rated short-circuit breaking current is a symmetrical rms value, so it enters Rated SC Rating (kA) unchanged, at the voltage it is stated for.
- Opening time runs from energizing the opening release to contact separation — trip to part — so it is shorter than Parting Time by exactly the protection response. Add that response first: a 1-cycle relay ahead of a 2-cycle opening time gives a parting time of 3 cycles.
- Break time is opening time plus arcing time, so it equals Speed only after the same protection response is added.
- Rated short-time withstand current and its duration serve the carried-current and close-and-latch duties, not these three fields.
The calculation side carries the same split — why the MVA method tracks ANSI but not IEC 60909 — because the two standards define fault quantities differently, and matching labels across them produces a study that is precise and wrong.
The decisions #
- Breaker rated 1964 or later, including every unit made after 1970: enter the symmetrical rms capability in Rated SC Rating (kA) and keep the DC offset out of the field.
- Pre-1964 rating basis: do not enter the total-current nameplate figure; convert it with the manufacturer's stated method for that frame first.
- Parting Time (Cyc.): fault inception to contact parting. If the document gives only a trip-to-part time, add the protection response before entering it.
- Speed (Cyc.): parting plus arcing, used — not the opening time — as the clearing time in coordination and arc-flash runs.
- IEC or AS 62271.100 datasheet: breaking current maps to the kA field directly; opening time and break time convert to the ANSI zeros by adding the protection response.
- A duty result that passes only through an asymmetrical entry, or that swings when one time field is edited alone, is a library error, not a finding about the breaker: fix the entry and rerun.
Questions asked
How do the cycle fields convert at 50 Hz instead of 60 Hz?
Divide the cycle count by the system frequency and multiply by 1000. At 50 Hz, 2 cycles is 40 ms and 5 cycles is 100 ms; the same counts at 60 Hz are 33 ms and 83 ms. A datasheet time quoted in milliseconds therefore becomes a different cycle count depending on the study frequency, so set the frequency before converting anything.
The nameplate gives interrupting capability in MVA. How do I get the kA value?
Divide the MVA figure by the square root of three times the rated kV. A 1500 MVA capability at 15 kV is 1500 divided by 25.98, about 57.7 kA. Use the voltage the MVA figure was stated at, and confirm the value is on a symmetrical basis before it goes into Rated SC Rating (kA).
If Parting Time already includes the relay, where does relay time go in the coordination model?
Nowhere else. Because the field runs from fault inception, adding the relay's operating time again as a separate clearing interval double-counts the protection, and the model clears the fault later than service will. Draw the device curve from fault inception and let the software combine that curve with the library breaker time once, as the arc flash evaluation does when it reads trip time from the curve.
Can I leave the library's generic parting time in place for an old breaker?
No. A generic value is not the frame's published time, and the duty result moves with it: a long entry lowers the DC offset at interruption and flatters the duty check, while a short entry clears the curve early and makes the breaker look overworked. Pull the manufacturer's contact-parting time for the frame and year before any duty or arc-flash result leaves the office.