Explainer
Why SKM reports an 18-inch arc flash boundary and 2 seconds
Short answer
No, do not change them. SKM's 18-inch boundary is the calculated distance where incident energy falls to 1.2 cal/cm², and its 2 seconds is the IEEE 1584 duration cutoff, not a device clearing time. The NFPA 70E 4-foot boundary and 0.033-second clearing time apply only to the table method when no arc flash analysis is performed.

On this page
- Which method are you actually using: calculation or table?
- Why does SKM show an 18-inch boundary?
- Why does SKM cap the arc duration, and when is that legitimate?
- What conditions does the 4-foot table default carry?
- What is the worked check on this panelboard?
- What goes on the label and in the report?
- What is the decision for each case?
- Questions asked
No, you do not change the 18-inch arc flash boundary or the 2-second duration in SKM. The 18 inches is a calculated result: the distance from the arcing point at which incident energy drops to the 1.2 cal/cm² threshold you told the software to report. The 2 seconds is the IEEE 1584 duration cutoff, not a protective-device clearing time. The 4-foot boundary and 0.033-second clearing time in NFPA 70E belong only to the table method for cases where no arc flash analysis is performed, and you are performing one.
Which method are you actually using: calculation or table? #
You are performing a calculated analysis, so the NFPA 70E table defaults do not apply to this panelboard. NFPA 70E (the Standard for Electrical Safety in the Workplace; the 2009 edition is the one you were reading, and the 2024 edition is current) offers two paths: an analysis performed according to IEEE 1584, or a table of PPE categories with fixed conditions. The 4-foot arc flash protection boundary and the 0.033-second clearing time are embedded assumptions of the table path, not requirements that a calculated study must reproduce. Once you build a system model and run it, the calculation method governs, and NFPA 70E accepts an incident-energy analysis in place of the tables. Confirm the edition and any local amendments with your authority having jurisdiction, but the two-path structure has been stable across editions.
Why does SKM show an 18-inch boundary? #
The 18 inches is the distance at which your calculated incident energy curve crosses 1.2 cal/cm², the energy NFPA 70E and OSHA publications use to define the arc flash boundary: the approach limit at which a worker without PPE could receive a second-degree burn. With a small 75 kVA transformer at 208 V, the available fault current is low, so the incident energy falls off quickly with distance and the boundary lands close to the equipment. That is a legitimate outcome of the IEEE 1584 incident-energy calculation with your working distance, gap and fault-current inputs. Do not force 4 feet into the model to match the table: the table's 4 feet assumes a specific fault current and clearing time that your calculated case does not have.
Why does SKM cap the arc duration, and when is that legitimate? #
The duration cap is justified by the assumption that a worker can move away from the arc within that time. IEEE 1584 guidance explains that most people can leave the arc region in less time than the cap allows, but could be slowed by obstacles, equipment layout or restricted escape routes. In SKM the setting acts as a maximum: where the modeled protective device clears faster than the cap, the device's own clearing time from its time-current curve is used; where it clears slower, the study caps the duration at that maximum. Apply the cutoff only when escape is genuinely possible at that equipment, and document that judgment in the report. Where a worker would be boxed in, keep the longer calculated clearing time instead.
What conditions does the 4-foot table default carry? #
The 4-foot default boundary is not unconditional even within the table method. It carries limitations on available short-circuit current and clearing time, including a stated product limit of 1667 amp-seconds, plus requirements on equipment type, voltage and task. A 208 V panelboard fed by a 75 kVA transformer sits at the edge of the table's low-voltage conditions, and whether the installation meets every stated condition must be verified from the actual fault-current and device data, not assumed. That is exactly why the table method cannot simply overwrite your calculated result: it is a different method with its own entry conditions.
What is the worked check on this panelboard? #
Take the example as modeled: a 208 V panelboard fed by a 75 kVA transformer. Suppose the modeled available bolted fault current at the panel is 6 kA and the upstream device clears in 0.5 seconds, with a working distance of 18 inches and an 18-inch gap setting per the model. IEEE 1584 gives incident energy that scales roughly with fault current times duration in the low-voltage range; with these inputs the software computes, for example, about 3 cal/cm² at the working distance and the point where the falling curve reaches 1.2 cal/cm² lies at roughly the reported 18-inch boundary. Arithmetic sanity check on the cutoff: 0.5 seconds is less than the 2-second cap, so the device time governs and the cap does nothing here. Had the device cleared in 3 seconds, the study would substitute the capped duration and the report must say so. The point is the direction of the logic: inputs and device curves produce the boundary; the boundary is never an input you tune toward 4 feet.
What goes on the label and in the report? #
Report the calculated values, not the table defaults. The equipment label carries the incident energy at the working distance, the arc flash boundary (your 18 inches), the voltage and the PPE category from the analysis. The study report behind it should state the method (IEEE 1584), the available fault current, the protective device and its clearing time from the time-current curve, whether the duration cutoff was applied and why escape is possible at that location. Where you are deciding which upstream device actually sets the clearing time, read article:which-breaker-sets-mcc-arc-flash-duration; if the model reports an implausible fault current at the bus instead, article:why-skm-shows-zero-fault-current-on-the-480-v-bus covers that modeling error.
What is the decision for each case? #
- Calculated study, escape possible: keep the 18-inch boundary and apply the duration cutoff, documenting the escape assumption. That is your case.
- Calculated study, escape restricted: keep the boundary but remove the cutoff and let the full device clearing time drive the incident energy.
- No analysis performed at all: then the NFPA 70E table method applies, with its 4-foot boundary, 0.033-second assumption and the 1667 amp-second and equipment conditions verified against the actual system before use.
- Model inputs wrong (fault current or device curve): fix the inputs; the boundary follows. Never edit the boundary itself.
One safety note: producing or changing this study does not authorize energized work. Any inspection that opens the panelboard or a transformer terminal box comes after lockout, testing for absence of voltage and the PPE the study itself calls for.
Questions asked
Should I change the SKM clearing time from 2 seconds to 0.033 seconds?
No. The 0.033 seconds (2 cycles at 60 Hz) is an assumption built into the NFPA 70E table method for equipment where no analysis was performed. In a calculated study the clearing time comes from the modeled protective device's time-current curve; the 2 seconds is a maximum duration cutoff, not a device time.
When does the 2-second cutoff become wrong?
When a worker cannot step away from the equipment in about 2 seconds, for example at a bucket with obstacles in front of it or a cramped space behind a closed door. IEEE 1584 guidance says the cutoff assumes escape is possible; document that the location allows it, or keep the longer calculated clearing time.
Can SKM display 1.2 cal/cm2 without a real arc flash calculation?
The software can be configured to report that threshold, but the number on the label must trace to an IEEE 1584 calculation with the actual available fault current and device clearing time. Otherwise it is a default assumption, and the label should say the table method, not a calculated result, was used.
What must the report show to defend an 18-inch boundary?
The report should list the modeling method (IEEE 1584), the working distance, the available bolted fault current at the panel, the protective device and its clearing time from the time-current curve, and whether the duration cutoff was applied. A reviewer should be able to reproduce the boundary from those inputs alone.