Transformer fault current from percent impedance at the terminals

Protection: breakers, fuses and SCCR Published 5 min read By Current Intel engineering team

Short answer

With the utility modeled as an unlimited source, the maximum symmetrical fault current at a transformer's secondary terminals is full-load current divided by impedance on its own base: 3% impedance gives 33.3 times full-load current. A 667 kVA, 3%Z transformer delivers about 80 kA at 277 V single-phase or about 46 kA at 277 V three-phase, before any utility or conductor impedance is subtracted.

On this page
  1. What percent impedance actually means
  2. The formula
  3. Worked example: 667 kVA transformer
  4. What the infinite-bus result does not include
  5. The decision
  6. Questions asked

You do not need a commercial calculator to get the maximum fault current at a distribution transformer's secondary terminals. With the utility modeled as an unlimited source, the answer is one division: full-load current divided by the transformer's impedance expressed on its own base. A 3%Z transformer limits a bolted three-phase terminal fault to 33.3 times its rated secondary current. For the 667 kVA, 7200/12470-277 V, 3%Z unit in question, that is roughly 80 kA if 277 V is a single-phase voltage, or roughly 46 kA if 277 V is the line-to-line voltage of a three-phase bank — and that figure deliberately excludes every impedance between the utility and the transformer terminals.

What percent impedance actually means #

The %Z value on the nameplate is measured with one winding short-circuited: enough voltage is applied to the other winding to drive rated current around the loop, and that applied voltage, stated as a share of rated voltage, is the percent impedance. A 3%Z transformer needs only 3% of rated voltage to circulate full-load current through its own windings. That same ratio is all that stands between rated current and a bolted short at the terminals, so the terminal fault current is rated current divided by 0.03.

Impedance stated this way is dimensionless: it has the same value referred to either winding, at any voltage level, which is why the arithmetic never involves the primary voltage. One caution on the base convention: a percent impedance is only meaningful on the transformer's own kVA and voltage base, and mixing bases — a common error when single-phase models meet three-phase software — produces wildly wrong source impedances. The article on a single-phase SKM model that returns an enormous utility Z from a wrong base shows what that failure looks like.

The formula #

For a three-phase transformer, with V as the line-to-line secondary voltage:

  • Full-load secondary current: IFL = (kVA × 1,000) ÷ (√3 × V)
  • Maximum symmetrical terminal fault current: Isc = IFL ÷ (%Z ÷ 100)

For a single-phase transformer, drop the √3 and use the voltage across the winding that carries the load:

  • Full-load current: IFL = (kVA × 1,000) ÷ V
  • Isc = IFL ÷ (%Z ÷ 100)

The ratio Isc/IFL is sometimes called the fault-current multiplier. At the 0.03 impedance of the example it is 33.3; at 5%Z it is 20; at 2%Z it is 50. Lower impedance always means higher fault current, and the nameplate %Z carries a tolerance (typically plus or minus 7.5% of the stated value for small transformers under the relevant standards), so treat the nameplate result as the best single number available, not a laboratory measurement.

Worked example: 667 kVA transformer #

The thread that prompted this article named a 667 kVA, 7200/12470-277 V transformer without saying whether the secondary voltage is one leg of a single-phase unit or the line-to-line voltage of a three-phase bank. The two readings give very different answers, so resolve the nameplate connection before you use either result.

Case 1 — 277 V as a single-phase winding voltage. Full-load current is 667,000 VA ÷ 277 V = 2,408 A. Terminal fault current is 2,408 A ÷ 0.03 = 80,265 A, about 80.3 kA.

Case 2 — the same voltage as the line-to-line voltage of a three-phase transformer. Full-load current is 667,000 VA ÷ (1.732 × the line-to-line voltage) = 1,390 A. Terminal fault current is 1,390 A ÷ 0.03 = 46,347 A, about 46.3 kA.

Reading Full-load secondary current Terminal fault current at the nameplate impedance
277 V single-phase 2,408 A 80,265 A
Same voltage, three-phase line-to-line 1,390 A 46,347 A

The difference between the two readings is nearly 34 kA — enough to change a breaker's short-circuit current rating verification and an arc-flash label. Confirm the winding connection on the nameplate before quoting either number.

What the infinite-bus result does not include #

The unlimited-source assumption drives the utility's contribution to zero, so the calculated value is the maximum the transformer alone can deliver at its secondary terminals. Three terms always reduce fault current further downstream:

  • The real utility source impedance behind the primary. The knowledge-base page on calculating utility impedance from fault MVA shows how to convert the utility's available fault duty into an impedance term to add to the transformer's.
  • Primary and secondary conductor impedance. Cable runs of any length pull the value down fast at 277/480 V levels; the article on calculating low-side fault current with source impedance works through the correction.
  • The difference between the first-cycle asymmetrical current and the interrupting-duty current a breaker actually sees; the comparison of bolted fault currents for breaker duty and arc flash sorts out which value belongs on which calculation.

So the infinite-bus number is a ceiling. Use it when you need the worst case the transformer can impose on the equipment bolted directly to its secondary — for example when checking a panelboard's short-circuit current rating — and refine it with source and conductor impedance before applying it to equipment farther out. The article on available fault current versus secondary short-circuit current covers where each figure belongs.

The decision #

  • Maximum symmetrical fault current at a transformer's secondary terminals = full-load current ÷ (%Z ÷ 100), with the utility treated as an unlimited source. At the example's impedance that is 33.3 × rated current.
  • For the example transformer: 80,265 A at the terminals on the single-phase reading, 46,347 A on the three-phase line-to-line reading. Verify the nameplate connection, then use the matching row — nothing between the utility and the terminals makes these values higher, only lower.
  • Treat the result as a terminal-only ceiling for SCCR checks at the secondary; add utility and conductor impedance before applying it downstream.

One safety note: verifying available fault current and inspecting transformer connections are de-energized work. De-energize, lock out, and test for absence of voltage before opening any transformer or switchgear enclosure, following NFPA 70E (2024 edition) and your plant's own procedures.

A spreadsheet is still worth the ten minutes if you do this often: enter kVA, voltage, phase and %Z as separate inputs, and build in both the single-phase and three-phase full-load equations so the voltage-basis mistake cannot happen. For the occasional check, the two divisions above are faster than any calculator you could download.

Questions asked

What does 3 percent impedance mean on a transformer nameplate?

It means that when one winding is short-circuited, 3 percent of rated voltage applied to the other winding drives rated current to flow. That ratio also sets the fault current: the transformer alone limits a terminal short-circuit to rated current divided by 0.03, which is 33.3 times rated current.

Does the infinite-bus fault current include utility and cable impedance?

No. The result assumes zero upstream source impedance, so it is the ceiling at the transformer secondary terminals only. Real fault current at downstream equipment is lower once the utility source, primary conductors and secondary conductors are added; those terms always reduce the number.

Is the number good enough for the NEC 110.24 marking?

It can serve as a conservative starting point for the maximum available fault current marking required at service equipment under NFPA 70 (2023 edition), but the field marking should reflect the supply installation, and the local authority having jurisdiction and the equipment labeling documentation govern the final value.

Keep reading

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR

  • Explainer

    Available fault current vs secondary short-circuit current

    Available fault current and secondary short-circuit current name the same prospective current only when both refer to the same point, fault type and current basis. A supplied value equal to the transformer's full-load current divided by its percent impedance assumes an infinite source: for a 300 kVA, 480 V, 2.0% Z unit that is 361 A / 0.02 = 18,050 A. That number is conservative for equipment duty but not automatically the worst case for arc flash.

    Protection: breakers, fuses and SCCR

  • How-to

    Calculating Transformer Interrupting Current From Impedance

    Use the impedance's own base: 10.2% is stated on the 8,333 kVA self-cooled (OA) rating, so rated current at 5.04 kV is 1,653 A and the transformer-limited secondary fault current is 1,653 ÷ 0.102 ≈ 16.2 kA. That figure sizes a breaker on the secondary bus; a primary breaker's interrupting rating is set by the upstream available fault current, not by the transformer.

    Protection: breakers, fuses and SCCR