How-to
Transformer sizing from the highest leg current on a panel
Short answer
Size the transformer from the highest recorded leg current, never the sum of the legs: 240 V x 50 A is a 12 kVA load, the 1.25 continuous factor points at a 15 kVA standard unit, and the panel main becomes 80 A. First measure line-to-line, because about 240 V confirms a single-phase source while about 208 V means two legs of a wye and a different transformer.
On this page
- Confirm the source type before any kVA math
- Take the leg currents the transformer must carry
- Why the leg currents do not add
- Turn the measured kVA into a transformer order
- Match the overcurrent protection to the new transformer
- Check the panel for wye-only loads
- Verify the split once the new transformer is energized
- Questions asked
Do not add the legs, and do not trust the panel schedule. Size the transformer from the highest recorded leg current: 240 V x 50 A is 12.0 kVA, the 1.25 continuous factor lands at 15.0 kVA, and a 15 kVA, 480 V primary, 120/240 V secondary unit is the selection, with the panel main set at 80 A and the primary device at 40 A.
Before the math, settle the documentation conflict on your panel: one drawing shows the wye notation and the corrected one shows the single-phase notation, and only a measurement decides. A line-to-line reading near 240 V confirms a single-phase center-tapped source and the sizing above; a reading near 208 V means two legs of a three-phase wye, and the transformer type, the formula and the load check all change.
Confirm the source type before any kVA math #
The two documents cannot both be right, and the two systems are different machines. A panel on the single-phase center-tapped system has legs 180 degrees apart, so leg-to-neutral reads about 120 V and the leg-to-leg reading comes out at double that. A panel on the wye has legs 120 degrees apart, so leg-to-leg comes out at 120 x 1.732 = 207.8 V, which meters as about 208 V. Both systems read nearly the same leg-to-neutral, which is exactly why the line-to-leg reading is the only number that settles the question.
Your upstream source agrees with the corrected document: a 112.5 kVA, 480 V single-phase transformer can only produce a single-phase secondary, and no single-phase unit makes a true 208Y/120 panel. Measure anyway, because panels get modified and taps get moved, and drawings record intentions rather than bus bars.
Opening the panel is the first physical step, so do it in order: de-energize, lock out, and test for absence of voltage before the dead front comes off, then take the readings with a true-RMS meter under your plant's energized-work rules and NFPA 70E, 2024 edition, and confirm the local requirements with the authority having jurisdiction.
- Leg A to neutral and leg B to neutral: about 120 V each.
- Leg A to leg B: the doubled value on the single-phase source your corrected document describes.
- A third hot leg, or one leg-to-neutral reading well below the others while leg-to-leg reads the full single-phase value, means a delta source with a high leg, and the sizing path is the one in sizing a padmount transformer for a delta load.
The two systems also share current out between the legs differently, and the load-distribution calculations for 120/208 wye versus 120/240 delta supplies cover that math if you ever need to recompute it by hand. Do not run any kVA arithmetic until the line-to-leg reading and the transformer nameplate agree.
Take the leg currents the transformer must carry #
The 50 A and 25 A readings in your record are one moment of one shift. The transformer has to carry the worst the panel does, so measure with that in mind.
- Clamp each hot leg at the load side of the main breaker during a normal production hour and check the readings against the 50 A and 25 A snapshot.
- Clamp the neutral. On a center-tapped system it should read roughly the difference between the legs, about 25 A with your numbers. A neutral far above that means the source identification is wrong, and the sizing stops until the source is re-identified.
- Fit a recording clamp meter across a full operating cycle, including the heaviest shift. Intermittent machines make a snapshot lie in either direction, and the highest recorded leg current is the number the sizing uses.
- Ignore the 400 A bus rating as a load figure. It is a main and busbar rating, not demand: the heavier leg sits at 12.5 percent of it, and a 400 A panel at this line-to-line service would be 96 kVA, which nothing measured here approaches.
If the recording is flat across shifts, the snapshot and the maximum agree and you can size on them. If it spikes, the peak is the sizing input, and you want the machine behind the spike identified before you order the transformer.
Why the leg currents do not add #
The tempting arithmetic adds the legs and multiplies by the leg-to-neutral value: 120 x (50 + 25) / 1000 = 9.0 kVA. That answers a question the transformer never asks. On this system, a line-to-neutral load burdens one leg and the neutral, a line-to-line load burdens both legs equally, and the neutral carries roughly the difference. The clamp on each leg already reads the true phasor sum of everything on that leg, power factors included; adding currents from an out-of-date schedule produces a number that matches neither the meter nor the winding.
The transformer's limit is thermal, and it applies leg by leg: each secondary half-winding carries its own leg current, so the heavy leg sets the rating. Rebalancing the leg-to-neutral loads moves current between legs without changing what the panel does, which is why the sizing basis treats the light leg as able to reach the heavy leg's reading. The same winding logic decides whether the highest leg is the total draw on a three-phase panel; only the voltage basis differs.
The sizing formula is line-to-line voltage times the highest recorded leg current:
(240 x 50) / 1000 = 12.0 kVA
| Case | Arithmetic | Result | Use it for |
|---|---|---|---|
| Sum of the legs at 120 V | 120 x (50 + 25) / 1000 | 9.0 kVA | A present-load estimate only, never a sizing basis |
| Highest leg carried on both legs, at line-to-line voltage | 240 x 50 / 1000 | 12.0 kVA | The sizing basis for a 120/240 V single-phase transformer |
| Two legs of a 208 V wye, third leg unmeasured | 1.732 x 208 x 50 / 1000 | 18.0 kVA | Only after leg C reads at or below the highest leg; this load needs a 208Y/120 three-phase transformer |
The check that catches bad data: the sizing basis must come out at or above the sum-of-legs estimate, and 12.0 kVA against 9.0 kVA passes. If yours comes out the other way, a reading or the voltage assumption is wrong — go back to the meters before you open a catalog. Treat the number as an estimate of duty: it is only as good as the recording behind it, and the transformer documentation confirms the final selection.
Turn the measured kVA into a transformer order #
The sizing basis is a floor, not a nameplate. A panel that runs a full shift is a continuous load in any practical sense, so apply the continuous factor and step up to the next standard kVA:
12.0 x 1.25 = 15.0 kVA
Fifteen kVA is a standard dry-type single-phase size across manufacturer catalogs, and the decision does not hinge on how the margin is argued: even on the raw measured basis, the next standard size above it is the same unit. Confirm that, and the primary and secondary voltages (480 V primary, single-phase center-tapped secondary), on the datasheet you will actually buy from.
The rated currents come off the same page: 15,000 VA / 480 V = 31.3 A on the primary, and the same kVA over the secondary voltage gives 62.5 A. The heavy leg's recorded reading sits at 80 percent of that secondary rating, which is running margin rather than dead headroom. If the recording shows a rising trend instead of a stable peak, size from the trend, not from today.
Splitting this panel off also frees the upstream unit: its primary is rated 112,500 VA / 480 V = 234 A, and this panel's share drops to about 31 A. The second tapped panel gets its own transformer, sized the same way from its own highest recorded leg — this panel's basis does not carry across.
Match the overcurrent protection to the new transformer #
The main that made sense on the old feed is wrong on the new one. A device sized for the 400 A bus cannot protect a secondary rated 62.5 A; the transformer, not the panel, now sets the limits.
NFPA 70, the National Electrical Code, 2023 edition, Table 450.3(B) gives the maximums for transformers at 1000 V and less: the secondary protective device may be rated up to 125 percent of the rated secondary current, with the next higher standard size permitted, and the primary device answers to the same table — 125 percent where it is the only protection, up to 250 percent where a secondary device is in place. Editions and local amendments move these numbers, so confirm them with the authority having jurisdiction and the transformer datasheet before you buy the devices.
Secondary: 62.5 x 1.25 = 78.1 A, so set or replace the panel main at the next standard size, 80 A, or anything smaller that carries the load; the existing 400 A main comes out.
Primary: 31.3 x 1.25 = 39.1 A, and 40 A is the next standard size, which is the selection here. The table permits up to 250 percent once the 80 A secondary main is in place, so 40 A sits low in the permitted band, with headroom to verify against the manufacturer's inrush data. The device-selection arithmetic for this kind of feed is walked from the breaker side in sizing a three-pole breaker for a single-phase transformer.
The smaller secondary also lowers the fault current the panel can see, which is worth checking on a panel built around the old source: calculating the interrupting current from the transformer impedance gives the figure to compare against the panel's short-circuit rating before it is closed up.
Check the panel for wye-only loads #
If this panel ever actually ran from the wye, every two-pole load has been living at 208 V, and the new single-phase secondary will hand it a factor of 240 / 208 = 1.15, about 15 percent over nameplate. The leg-to-neutral loads do not move. The line-to-line loads are the ones that can cook.
Walk the panel and list every two-pole or line-to-line load with its rated voltage, from the nameplates and equipment manuals rather than from the schedule. Devices marked with dual ranges, such as 208-230 V, accept the new supply. Anything rated for the wye value only is a replace-it item, or a reason to order the transformer with the wye secondary instead. In a panel whose credible history is the single-phase system the survey should find none, as it does here — but the walk-through is what proves it, and it costs half an hour.
Verify the split once the new transformer is energized #
Three readings close the job:
- Leg-to-neutral on both legs, equal and within a few volts of each other.
- Leg-to-leg at the corrected system voltage, matching every two-pole nameplate you surveyed.
- Both hot legs under production load, with the heavy leg comfortably below the secondary rating, in this example at 80 percent of it.
If the heavy leg holds near the secondary rating, the recording missed a load cycle and the answer is the next standard kVA up. Log the final readings and label the panel with its new source: the transformer kVA, both voltages, and the 80 A main that now protects it.
Questions asked
The line-to-leg reading matches the wye. Can I still feed the panel from a single-phase transformer?
No. Matching leg-to-neutral readings with a leg-to-leg value near 207.8 mean two legs of a 208Y/120 three-phase system, not a center-tapped single-phase secondary. A single-phase transformer with the doubled secondary would push the two-pole loads about 15 percent over their nameplates. This load needs a 208Y/120 three-phase transformer, sized from the highest leg: 1.732 times the line-to-leg voltage times the highest leg current in amperes, divided by 1000.
Why does the neutral read about 25 A when one leg carries twice the other?
On a center-tapped 120/240 V secondary, each 120 V load returns through the neutral on its own leg only, so the neutral carries the imbalance between the legs; with the legs at 50 A and 25 A, that is roughly 25 A. Line-to-line loads do not appear in the neutral at all, because their currents cancel between the two legs. A neutral current much larger than the leg difference points to a misidentified source or an unwanted ground path, and it stops the sizing work until it is explained.
Can equipment nameplated for the wye run on the new secondary?
Only what the nameplate or the manual explicitly allows. Dual-range ratings, such as 208-230 V or 200-230 V, accept the higher supply. A device rated for the wye value only sees about 15 percent overvoltage, which shortens insulation and coil life and can trip electronic power supplies. Replace those loads, or order the transformer with the wye secondary and accept the ampere penalty that comes with it.
What if the recorded peak keeps growing month over month?
Then the snapshot from the survey is no longer the sizing input. Re-record a full operating cycle, compare the new highest leg current against the transformer's secondary rating, and act when the heavy leg holds above about 80 percent of it: the next standard kVA up, or a load survey to find what moved in. Log each reading with a date so the trend is provable rather than remembered.