Using a 575 volt motor as a rotary phase converter

Motors and motor starters Published 8 min read

Short answer

Yes, a 20 hp, 575 V three-phase motor makes a workable rotary converter idler on a 575/600 V single-phase supply, provided the run capacitors are rated at least 895 VAC, the start bank at least 575 VAC, and the start relay is fed through a 575:240 control transformer. On 240 V the same motor carries only about a 7.5 hp load, so match the idler to the supply.

On this page
  1. Can the 575 V motor serve as the idler?
  2. The supply decides the design
  3. What 240 V does to a 575 V winding
  4. Capacitor ratings a 575 V system forces
  5. Worked example: capacitor banks for the 20 hp idler
  6. The start circuit: relay through a transformer
  7. Balance it under real load
  8. The decision
  9. Questions asked

Yes — a 20 hp, 575 V three-phase induction motor will serve as a rotary phase converter idler, and it is a generous one: at matched voltage, plan on a 10 hp largest load motor. Two conditions govern everything else. The single-phase supply must be 575/600 V class; fed at 240 V, the same windings keep only (240/575)² ≈ 17 % of rated torque and the converter drops to about a 7.5 hp unit. And every component must carry the system voltage: run capacitors at a minimum of 895 VAC, start capacitors at 575 VAC, with the start relay fed through a 575:240 control transformer. Here is how those numbers are built.

Can the 575 V motor serve as the idler? #

Any healthy three-phase induction motor can generate the third leg. Read the nameplate first: voltage, frequency, full-load amperes (FLA) and the winding connection. That FLA is the converter's operating limit — the idler works as long as it starts unaided, keeps spinning, and the generated-leg (B) current stays below nameplate FLA.

Sizing rule of thumb: the idler should be at least twice the largest load motor. A 15 hp idler running two 5 hp direct-on-line motors is a documented example of that rule in practice, and running loads ease later starts. NFPA 70 (the National Electrical Code, 2023 edition) covers phase-converter supply circuits in Article 430, Part IX — size the single-phase feeder, disconnect and overcurrent protection from the idler rating as that part requires, and confirm the application with the authority having jurisdiction.

The supply decides the design #

Nothing about the motor changes; the incoming single-phase voltage sets the whole component list. Measure the actual line-to-line voltage before buying anything. The three realistic paths:

Supply available Load to run Path Decision
575/600 V single phase Motors to match This converter: 20 hp idler, run and start banks as sized below, transformer-fed relay Build it — the motor fits
240 V single phase Motors to match the supply Fit an idler of that class at 2× the largest load motor Replace the idler, keep the design
The same 240 V supply One 575/600 V machine Step the supply up to 575/600 V single phase with a power transformer, then this converter Converter for several motors, drive for one

The third row's transformer must be a power unit sized for the converter's starting demand — the control transformer in the start circuit cannot do double duty, and a marginally sized step-up transformer collapses the generated leg during load starts. For one machine only, sizing a drive for a three-phase motor on single-phase input is usually the cleaner build, and powering a high-voltage three-phase machine from the low-voltage supply works through the transformer route at system level. A static converter is not in the table on purpose: why a static phase converter won't start a lathe motor is the same physics that disqualifies it here — no properly generated leg under load.

What 240 V does to a 575 V winding #

At the same frequency and winding connection, induction-motor torque at a comparable operating point scales with the square of the applied voltage:

Torque ratio = (V₂ / V₁)² = (240 / 575)² = 0.4174² = 0.174

Inputs: V₁ = 575 V nameplate, V₂ = 240 V supply, 60 Hz, winding unchanged. The motor keeps about 17 % of its torque capability; that is a physics estimate for the winding, not a converter horsepower rating. Field results reported with this design class: a 10 hp, 480 V idler fed from that same lower voltage struggled above a 5 hp load, while a 10 hp, 240 V idler carried a 7.5 hp load. Extrapolated to this 20 hp idler on the lower supply, plan on about a 7.5 hp load and verify it the only honest way — B-phase current against nameplate FLA and real load starts.

Decision: on the low-voltage supply, do not build a 20 hp converter around this motor. Treat it as a 7.5 hp-class converter at most, and keep it for a matched-voltage application instead.

Capacitor ratings a 575 V system forces #

The run banks sit between a supply line and the generated leg, and tuning can push the generated leg well above the line voltage. The working minimums: run capacitors at least 895 VAC, start capacitors at least 575 VAC. The run figure follows the rule of thumb of √3 × line voltage ÷ 1.1: 575 × 1.732 / 1.1 ≈ 905 V, quoted in practice as an 895 V minimum.

Catalogue voltage classes force series construction: motor run capacitors commonly come in 370, 440 and 600 VAC ratings, motor start capacitors in 250 and 330 VAC. Two identical capacitors in series double the voltage rating and halve the capacitance, so every position needs two units of twice the target microfarads. Match the pairs — series units share AC voltage by impedance, and a mismatched pair over-voltages the smaller unit. Two 440 V run units in series give 880 V, accepted in practice as close enough to the 895 V minimum, and two 600 V units give 1200 V if you want margin. Two 330 V start units in series give 660 V against the start-side requirement.

Worked example: capacitor banks for the 20 hp idler #

The sizing rule of thumb gives 1, 2, 3 and 30 µF per quarter-horsepower of idler at 240 V: 1 µF across the two incoming supply lines (A–C) for power-factor correction, 2 µF C–B and 3 µF A–B feeding the generated leg B, and 30 µF of start capacitance switched out after acceleration. Capacitance scales inversely with voltage squared, because the same reactive support at higher voltage needs fewer microfarads.

  • Quarter-horsepower units: 20 hp ÷ 0.25 hp = 80
  • Voltage scaling: 0.174, carried from the torque calculation above
  • Combined multiplier: 80 × 0.174 = 13.9
Bank Per-quarter-hp rule × 13.9 Rounded Minimum AC rating Series build
A–C power-factor 1 µF per quarter-hp 13.9 µF 14 µF 895 V two 440 V units, 28 µF each
C–B run 2 µF per quarter-hp 27.9 µF 28 µF 895 V two 440 V units, 56 µF each
A–B run 3 µF per quarter-hp 41.8 µF 42 µF 895 V two 440 V units, 84 µF each
Start 30 µF per quarter-hp 418 µF 420 µF 575 V eight series pairs of 330 V start capacitors

These are starting values, not answers — tune A–B and C–B under the real load as described below. A worked example sizing a 7.5 hp idler and its capacitors shows the same arithmetic without any series strings.

Start bank build: with 108–130 µF, 330 VAC start capacitors, two in series rate 660 V and deliver 54–65 µF per pair. Eight pairs in parallel give 8 × 54 = 432 µF minimum, or 432–520 µF across the tolerance band, covering the 418 µF target at sixteen capacitors. Sizing surplus start capacitors for a 10 hp idler walks the same series-parallel logic for a smaller bank.

The start circuit: relay through a transformer #

The usual potential relay is a 240 V machine: its pickup and drop-out thresholds and its contact ratings are set for lines of that class. Two fixes work. Use a fully adjustable potential relay rated for the circuit, or feed the standard relay — the Steveco 90-66 is the usual candidate — from a small 575:240 control transformer connected across the generated leg, so the relay sees 240 V-class voltage whatever the primary is doing. Confirm the relay's pickup, drop-out and contact ratings against its datasheet either way.

Watch the ratio: if a 600:240 transformer is what you can get, 575 V on the primary gives 575 × 240 / 600 = 230 V at the relay rather than the nominal secondary. Translate the relay's thresholds through the measured secondary voltage before trusting the transition point.

The relay does not switch the bank directly: it drives the coil of a separate start contactor, and that contactor must make and interrupt the 420 µF bank's capacitive current — size it generously. When a load motor starts, the generated-leg voltage sags; if it sags below the relay's hold-in point, the start contactor pulls back in to help, which is useful behaviour and one more reason it needs a repeated-duty rating.

Balance it under real load #

Before changing any capacitor connection: lock out the single-phase supply, test for absence of voltage at the idler terminals, and discharge every bank, since series pairs can hold charge divided across the units. Live tuning readings are energized work — follow your site's safe-work program, governed in the United States by NFPA 70E (2024 edition), and take readings with covers on wherever meter points allow.

Tune with the largest load motor running: add or subtract microfarads on A–B and C–B until the three output line-to-line voltages sit within about 5 % of one another, then tighten toward 2 %. The imbalance your load motors tolerate, and the derating they take beyond it, is covered in setting voltage imbalance limits on a 480 V phase monitor; the same limits apply to converter output. Acceptance is unchanged: B-phase current below the idler's nameplate FLA, every load motor accelerating clean without the start bank chattering. Reversing the idler is a two-lead swap — why any two phase swaps reverse a three-phase motor — but re-check the balance afterward, because the banks are tuned per side.

The decision #

Three cases, three answers. On a 575/600 V single-phase supply: build it — this motor is the right idler for up to a 10 hp largest load motor, with the run and start banks and the transformer-fed relay sized exactly as above. On the low-voltage supply with motors to match: fit an idler of that class at twice the largest load and keep this motor for a matched-voltage job — the reduced-voltage arrangement caps out around the 7.5 hp figure computed above. On that same supply with one 575/600 V machine: step up through a power transformer and this converter when several motors justify it, or drive the single machine from a drive rated for single-phase input.

Questions asked

Which load motor should start first on a rotary converter?

Start the largest motor first while the others are off. Once a load motor is spinning it generates as well and acts as a second idler, so every later start sees a stiffer converter. If the biggest motor will not come up alone, the idler or its start bank is too small for that machine; fix that before adding smaller loads to the line-up.

Why does the start-capacitor contactor pull back in when a load motor starts?

That is the relay doing its job. Below roughly 165 V at the relay coil the start bank reconnects to help accelerate the load. Fed through the 575:240 sensing transformer, that 165 V corresponds to 165 × 575 / 240, about 395 V on the generated leg, so the contactor must be rated for repeated capacitive making and interruption duty, not a single start per hour.

Does the idler have to be bolted down?

Mount the idler on rubber and do not rigidly bolt it to the structure, because an unloaded idler transmits vibration straight into the foundation. Mechanical isolation is not electrical isolation: the frame still requires its equipment grounding conductor, bonded back to the supply ground, so a fault has a path to clear. Isolate the mount, never the ground.

What idler speed runs quietest?

A 1700 to 1800 rpm four-pole idler runs noticeably quieter than a 3600 rpm two-pole machine doing the same job. Speed does not need to match the load motors, since the idler spins unloaded and only supplies the generated leg, and at 60 Hz any common synchronous speed will generate. Choose the slower machine for noise.

Keep reading

  • Explainer

    Running a three-phase motor on single-phase 208 V

    Yes — a spinning three-phase motor fed across two terminals regenerates the third leg, but winding heating caps it near 30-40% of rated horsepower, so it is a bench trick, not a supply. For real loads, use a rotary phase converter with an idler at least the next size above the largest motor, or a single-phase-input VFD for motors only — never a drive for amplifiers or power supplies.

    Motors and motor starters

  • How-to

    Wiring a three-phase coolant pump starter from a 120 V signal

    Run the machine's 120 V coolant output through the overload relay's normally closed contact to a contactor with a 120 VAC coil, and set the overload dial to the pump's nameplate full-load current — 1.8 A on a typical 1/2 HP three-phase pump, inside a 1.3–2.1 A adjustable range. Then bump-test rotation and swap any two motor leads if the pump runs backward.

    Motors and motor starters

  • Explainer

    Why any two phase swaps reverse a three-phase motor

    Swap any two of the three supply conductors — A and B, B and C, or A and C — and a three-phase induction motor reverses identically, because every two-conductor exchange flips the phase sequence to its mirror; no pair changes timing. Heat after a reversal traces to voltage unbalance above NEMA MG-1's 1.0% limit, load, or a one-directional cooling fan.

    Motors and motor starters