What a current transformer reads on TECK cable armor

Power quality and harmonics Published 10 min read By Current Intel engineering team

Short answer

A window CT reports the vector sum of everything through its aperture, not the conductor alone. On a single-conductor TECK cable with the armor grounded at both ends, induced armor current — reported up to 90 A in published MV studies — can leave the meter tens of percent low. One-end grounding reads load current correctly but not fault return current, and a zero-sequence CT is right only with the jacket bond routed back through its window.

On this page
  1. Does TECK cable armor itself disturb a current transformer?
  2. What does the CT window actually measure?
  3. Does single-conductor or multi-conductor cable change the answer?
  4. Why does armor grounded at both ends corrupt a metering CT?
  5. Does grounding the armor at one end fix the reading?
  6. How should the jacket ground be routed for a zero-sequence CT?
  7. How do you verify what the CT is really reading?
  8. Which standards govern TECK armor bonding and grounding?
  9. What is the decision for each case?
  10. Questions asked

A current transformer does not care that a cable is armored; it cares what passes through its window. A window CT reports the vector sum of every current through its aperture — the phase conductor, plus any longitudinal current the armor carries, plus any bonding conductor routed through it. That one fact settles every TECK question: on a single-conductor cable with the armor grounded at both ends, induced armor current skews the reading; with the armor grounded at one end, load-current metering reads true until a ground fault returns through the jacket; and a zero-sequence CT on a multi-conductor cable is right only when the jacket ground lead comes back through the window. The sections below give the arithmetic for each case and the checks that separate a bonding problem from a CT or meter problem.

Does TECK cable armor itself disturb a current transformer? #

No — the armor has no effect while no longitudinal current flows in it; the error appears only when induced or fault-return current travels along the armor and through the CT window, adding itself vectorially to the conductor current the CT is meant to see.

The steel around the conductors is not magnetic shielding, and proximity to steel does not by itself shift a toroidal CT's output. What matters is enclosed ampere-turns: with no net current along the armor, the CT sees the conductor alone and reads as well as it would on bare cable. The armor becomes a measurement variable the moment it carries longitudinal current — induced by the conductor's own field, or carrying fault return current — because that current is inside the aperture too. That is why the same cable meters correctly in one installation and reads wrong in another: the difference is bonding and current paths, not the armor.

What does the CT window actually measure? #

A window CT produces an output proportional to the vector sum of all ampere-turns passing through its aperture, so conductor current, armor longitudinal current and any bonding conductor routed through the window add algebraically before the CT sees the load at all.

The secondary output follows the net flux, and the net flux comes from the net primary ampere-turns. The CT cannot tell which path inside the aperture carried each ampere; only the sense each path takes through the window matters. Paths in opposite senses cancel; in the same sense they add. Ground-fault sensing uses this deliberately: a zero-sequence sensor is a CT arranged so balanced load cancels and only residual current survives, which is exactly what the article on what a zero-sequence CT does in ground fault protection walks through. Metering one conductor is the same physics pointed at a different purpose — you want one path's ampere-turns alone, so anything else inside the window is error.

Does single-conductor or multi-conductor cable change the answer? #

Yes — construction decides what the window encloses: a single-conductor cable puts one load current in the window with the armor around it, while a multi-conductor cable in one window cancels balanced load and leaves residual current, so the bonding must match the intended measurement.

On a multi-conductor cable all phases share one window, balanced load sums toward zero, and the CT is by construction a residual device — wrong for reading one phase's load current, right for ground-fault sensing. On single-conductor cables, one CT per cable reads that phase's current and each phase's armor encloses its own window, so the bonding question applies phase by phase. If the choice between the two constructions is still open on your project, the knowledge-base comparison of single-core and multi-core MV cable selection covers the electrical trade-offs; for the meter, the consequence is simply what each construction leaves inside the window.

Arrangement Currents inside the window What the CT reports
Single-conductor, armor grounded at one end Load conductor only; no closed armor loop Load current — correct for metering
Single-conductor, armor grounded at both ends Load conductor plus circulating armor current Vector sum — reads low or high, or phase-shifted
Multi-conductor, bond landed outside the window All phases plus the jacket's fault return Residual driven toward zero as the return cancels it
Multi-conductor, jacket bond passed back through the window All phases plus the returning bond current True residual current

Why does armor grounded at both ends corrupt a metering CT? #

Because armor grounded at both ends closes a loop in which the conductor's field drives a circulating current — a published MV study reported up to 90 A at a 1 ohm ground resistance — and that current passes the CT window against the conductor, so the meter reads the net, not the load.

Both terminations at ground potential close a conductive loop around the cable's own field. The conductor's alternating field induces a longitudinal voltage in the armor, and current circulates along the armor and back through the grounding path. The magnitude follows the loop impedance: it grows with load current and run length, falls as termination and ground-path resistance rise, and it is never a constant offset, because the conductor's field drives it. Calling the CT a metering unit changes its accuracy class, not the physics; a station metering point deserves the same scrutiny as a protective one.

Worked example (illustrative inputs): a 250 A load on a single-conductor feeder, armor grounded at both ends, with 90 A of circulating armor current enclosed by the window against the conductor — the magnitude that study reported at a 1 ohm ground resistance. The CT's net primary input is 250 A − 90 A = 160 A. On a 250:5 CT the secondary is 160 × 5 ÷ 250 = 3.2 A instead of 5 A, so the meter shows 160 ÷ 250 = 64% of true load, 36% low. The loop's resistance and reactance set the actual angle, so armor current of that size can also read high or appear mainly as a phase-angle error; the antiphase case above sets the scale of what is at stake. Relocating the CT along the same armored run changes nothing — the same conductor and the same armor still pass through the aperture.

Does grounding the armor at one end fix the reading? #

One-end grounding removes the closed loop, so no circulating current flows and a metering CT reads load current correctly — but it stays correct only until a phase-to-ground fault returns through the jacket, which then adds its own ampere-turns inside the window.

With a single ground point the induced voltage still exists but has no return path, so the metering CT reports the conductor alone; that is the arrangement to prefer for load metering on single-conductor runs. The catch is faults: the return travels along the armor through the window against the fault current, so a meter reads low and a protective sensor under-reaches by whatever the jacket carries. One-end bonding also leaves the far-end termination sitting at the induced voltage relative to earth, one of the trade-offs the grounding design weighs. The two bonding patterns and where each belongs are laid out in the knowledge-base page on TECK cable shield and armor grounding under IEEE 575. Do not re-bond a cable to improve an indication; bonding sets fault paths and touch voltage, so change the CT arrangement instead.

How should the jacket ground be routed for a zero-sequence CT? #

Bring the jacket ground connection back through the CT window: jacket and bond currents then pass the aperture in opposite senses and cancel, leaving the true residual — with a 2000 A example fault, the relay sees 2000 A instead of zero.

All three phases through one window cancel at balanced load; on a ground fault the faulted phase rises and the surplus is the residual the relay must see. When that residual returns along the jacket it passes the window against the phase current and subtracts: without the corrected bond, the arithmetic for that fault is 2000 A − 2000 A = 0 A, a relay blind to a real fault. Passing the termination's ground connection back through the window adds the return term in the compensating sense: 2000 A − 2000 A + 2000 A = 2000 A, and the relay sees the fault. On TECK this means the whole ground connection at the termination — the armor bond and the bare bonding conductor inside the cable — passes back through the aperture.

Route it exactly as the relay's connection diagram shows, keep the sensor's polarity mark where the drawing puts it, and prove the complete trip path with the injection test the manufacturer documents, feeder de-energized. How much residual exists in the first place depends on the source: a grounded-wye winding supplies ground-fault current and a delta does not, as the article on grounded wye versus delta ground fault current explains.

How do you verify what the CT is really reading? #

Compare the CT indication with an independent true-RMS clamp on bare conductor: an error fixed as a percentage with the phase angle unchanged is ratio or scaling, while a shifted power factor or an error that varies between cable runs points to armor current inside the window.

Clamp the bare conductor only — a clamp around the finished jacketed cable repeats the same vector-sum error instead of revealing it. Take reference readings at more than one load level, note the phase angle or power factor if the meter provides it, and record the cable type, CT position and orientation, every armor bond, and every conductor crossing the aperture. Use a clamp rated for the circuit's measurement category under IEC 61010, and treat the reference as the independent clamp reading plus the CT's own nameplate ratio — not a code limit.

Before any work that opens a termination or moves a CT, de-energize, lock out and verify absence of voltage: NFPA 70E, the standard for electrical safe work practices, 2024 edition, requires energized work to be justified and the absence of voltage to be proven, and the authority having jurisdiction and your site procedure set the details. Never lift an armor bond as a live experiment — diagnose from load and angle behaviour instead. If the check does land on the sensor itself, the selection guide for split-core current transformers for power meters covers ratio, burden and accuracy class.

Which standards govern TECK armor bonding and grounding? #

Type TECK 90 cable is certified under CSA C22.2 No. 131, IEEE 575 (2014 edition) is the guide covering bonding of metal sheaths and shields of single-conductor power cables, and both the cable standard and the local code govern how the armor is bonded.

IEEE 575's subject is precisely this decision on single-conductor cables: bonding at both ends with its circulating current, bonding at one end with the standing voltage at the floating termination, and the way each changes fault and touch-voltage behaviour. TECK installations in Canada fall under the Canadian Electrical Code (CSA C22.1) and US installations under NFPA 70, the National Electrical Code, 2023 edition, with local amendments on top — so confirm the bonding clauses in force where the cable runs with the authority having jurisdiction and the cable documentation, which have the final word. The CT's ratio, burden and accuracy class come from its nameplate and the connected meter's documentation, not from the cable standard.

What is the decision for each case? #

Meter a single-conductor TECK feeder with its armor grounded at one end and trust the reading; treat a both-ends-grounded run as unverified until an independent clamp comparison passes; pass the jacket bond back through the window on every zero-sequence installation.

  • Metering a single-conductor run with armor grounded at one end: accept the reading; the residual errors are the ordinary nameplate ones — ratio, burden and class.
  • Metering with the armor grounded at both ends: treat the indication as unverified until an independent clamp comparison agrees, and apply no correction factor, because the armor current tracks the load and shifts phase.
  • Ground-fault sensing on a jacketed cable: trace the return path through the window before trusting the scheme, and prove the trip path by injection with the feeder de-energized.
  • Zero-sequence sensing on a multi-conductor TECK cable: pass the termination's ground connection back through the window per the relay diagram, and the sensor reports true residual current.

Questions asked

Does the length of the run change the size of the armor-current error?

Yes, in one direction. The induced voltage along the armor grows with run length, while the loop impedance grows more slowly because only the armor's own resistance scales with length, so the circulating current increases as the run gets longer and settles toward a limit set by that resistance. Long single-conductor runs are where the metering error shows up first.

Can the steel armor itself upset the CT core even with no current in it?

No separate effect needs correcting. A window CT's output is set by the net ampere-turns inside the aperture, so steel sitting around the conductor adds nothing while it carries no longitudinal current. The instrument errors that remain are the ordinary ones on the CT nameplate — ratio, burden and accuracy class — checked against the connected meter's documentation.

Can I subtract a fixed correction for the armor current instead of fixing the bonding?

No, and it will not hold. Circulating armor current is driven by the conductor's own field, so it changes with load current, with the run's length and with the resistance of the terminations and ground path. A correction set at one load point fails at another, and it cannot remove the phase-angle shift a power meter will report.

Is grounding the armor at only one end always the better choice?

Not always. It is the right pattern for accurate metering, but the ungrounded end floats at the induced voltage during operation, both-end bonding gives lower-impedance return paths for fault and surge current, and the grounding design may require it. Bonding is chosen for safety and fault performance; the metering CT is then arranged around whatever bonding the design fixed.

Keep reading

  • Troubleshooting

    When a CT reads correct volts and the meter reads zero amps

    A current transformer with a 0.333 VAC output collapses to near zero when landed on a power monitor's low-impedance current input; the meter is healthy. Fit a conventional 5 A secondary CT sized just above the circuit maximum, or use the meter variant whose current inputs expect a 0.333 VAC signal. Never open a 5 A CT secondary while the primary carries current.

    Power quality and harmonics

  • Explainer

    Why a three-CT power meter shows neutral current on I5, not I4

    I4 is the meter's fourth physical current input, so with no neutral CT it correctly reads 0 A. The neutral current appears on I5, the calculated residual I1 + I2 + I3 + I4, which equals the neutral current on a four-wire system only while no ground current flows. The PM8000 series has no setting that declares a fourth CT absent, so wire I4 per the 3CT diagram and read the neutral on I5.

    Power quality and harmonics

  • Troubleshooting

    Why two class 0.2 billing meters differ by 3 percent

    A steady 3% kWh difference between two class 0.2 meters on one transformer is a metering-chain error — a wrong ratio or multiplier, excess CT burden, or current transformers operating below their class floor at light load. The recorded 0.6 A primary differential current is 0.2% of the 300 A rating and nearly all quadrature, so it cannot move real energy; keep both tank earths connected and sort the gap interval by interval.

    Power quality and harmonics