What an ohmmeter test finds on a three-phase cable
Short answer
An ohmmeter proves conductor continuity on a three-phase cable: with a jumper at the far end, three loop readings solve each conductor's resistance and expose opens, solid shorts and a damaged leg. It cannot certify insulation — anything voltage-dependent needs a 500 V megohmmeter with the cable isolated at both ends, and in a gassy mine only after the methane check the mine's procedures require.

On this page
An ohmmeter is the right tool for exactly three findings on a three-phase cable: an open conductor, a solid short, and a leg with far more resistance than its two neighbours. It proves continuity, nothing more. Compare three loop readings taken with a jumper at the far end and the arithmetic names the bad conductor. What it cannot do is certify insulation: a meter running on a 9 V battery cannot see a defect that only conducts at 480 V. Anything voltage-dependent needs a megohmmeter with the cable isolated at both ends, and in a gassy mine no test lead connects before the methane check the mine's procedures require. De-energize, lock out and verify absence of voltage first; every reading below starts there.
What the ohmmeter actually measures #
A handheld meter's resistance range drives the circuit from its internal battery, a few volts at most. On a continuity check that current takes one path: out one lead, along a conductor, across the temporary jumper at the far end, back along a second conductor and into the other lead. Both conductors, both terminations, the jumper and the leads sit inside that loop, and all of them are in the displayed number.
A conductor-to-ground reading takes a different path. With both ends disconnected, the only return left is leakage through the insulation, across surface contamination, or through anything still tied to the cable: motor windings, surge arresters, shields, a parallel run, the ground grid. Voltage-dependent defects live exactly there. Carbonized tracking, moisture paths and partly broken-down insulation walls stay open-circuit at a meter's few volts and break down at service voltage. That gap is what the megohmmeter closes later in this article.
Set up the test before any reading #
- De-energize the circuit, lock it out and verify absence of voltage at both cable ends with a meter proven on a known source immediately before and after the check. NFPA 70E, 2024 edition, calls this establishing an electrically safe work condition, and it is the prerequisite for opening a panel, a terminal box or a cable end; confirm the details with your authority having jurisdiction and the site's procedures.
- Disconnect both ends completely: motor leads, transformer connections, surge protection, control wiring, shields and any parallel runs. Each one is a return path the meter will happily count as your cable.
- Identify the conductors at both ends and tag them. Swapped identification turns a healthy cable into an apparent open leg.
- Baseline the meter. Probe tips together gives the lead resistance; leads apart must show a true open. Dirty clips, weak spring pressure and long temporary leads add more ohms than a short power conductor contains.
- In a mine, take the methane reading the mine's procedure requires before connecting anything that can make a spark. Methane is explosive in air between 5 and 15 percent; under MSHA's rule for metal and nonmetal mines, 30 CFR 57.22232, methane at 0.25 percent requires ventilation changes and immediate notification to MSHA, and coal mines answer to their own MSHA standards in 30 CFR Part 75.
Three loop readings solve each conductor #
Jump any two conductors together at the far end and read the loop at the near end. Repeat for all three pairs and subtract the lead-and-jumper baseline from every reading. Call the corrected loops R_AB, R_AC and R_BC: each conductor sits in exactly two of the three loops, so each solves by subtraction.
R_A = (R_AB + R_AC - R_BC) / 2
R_B = (R_AB + R_BC - R_AC) / 2
R_C = (R_AC + R_BC - R_AB) / 2
The equations hold only when each loop contains just the two named conductors and the baseline was truly removed. A negative result means measurement error, a drifting clip or an unremoved parallel path — re-measure instead of explaining it.
Worked example, every input stated: a 250 ft run of #10 uncoated copper; standard copper tables and the field rule of thumb agree at about 1.0 Ω per 1000 ft at 20 °C; lead set plus far-end jumper measures 0.3 Ω. Each conductor should then show 0.25 Ω one way and each two-conductor loop 0.5 Ω. Near-end measurements: 2.55 Ω across A-B, 0.80 Ω across A-C, 2.55 Ω across B-C. Corrected for the baseline: 2.25 Ω, 0.50 Ω, 2.25 Ω. Then:
Expected loop: 2 x 250 ft x (1.0 Ω / 1000 ft) = 0.5 Ω
R_A = (2.25 + 0.50 - 2.25) / 2 = 0.25 Ω
R_B = (2.25 + 2.25 - 0.50) / 2 = 2.0 Ω
R_C = (0.50 + 2.25 - 2.25) / 2 = 0.25 Ω
Phases A and C land on the handbook expectation and B solves to eight times their resistance. That is a broken strand bundle, a resistive splice or a corroded lug on B: remake that termination under the site's maintenance procedure and measure again from both ends. Heat moves copper's resistance up about 20 percent at a 75 °C conductor temperature, so judge a warm cable by the balance between phases rather than against a cold table.
The baseline is also the honesty check on short runs: 0.3 Ω of lead against an expected 0.5 Ω loop means the comparison between the three loops is the trustworthy finding, and a four-wire low-resistance meter is the upgrade when absolute values matter. Treat the solved numbers as a screening estimate to confirm against the conductor tables and the equipment documentation.
Reading patterns and what each points to #
- One loop reads open, the other two read normal. The conductor common to the two open loops is the open one; move the far-end jumper once to confirm which leg it is.
- All three loops read open. Missing or misplaced jumper, wrong cable end, poor clip contact, or more than one open conductor. Prove the meter and jumper on a short wire first.
- One loop reads far above the other two. The worse of its two conductors is the problem: broken strands, a resistive splice, a corroded termination. The worked example above is exactly this pattern.
- Low ohms between phases with both ends fully disconnected. A solid phase-to-phase short or conductive contamination bridging the insulation. Re-verify that nothing external is still connected before condemning the cable.
- Low ohms from a phase to ground or to the shield. Either a hard ground fault or a bonding path still attached. If the cable is verified isolated and the reading persists, hand the run to a fault-location procedure such as locating a ground fault on a resistance-grounded 480 V system.
- The reading starts low and climbs. Cable capacitance charging from the meter's battery. Let it settle, reverse the leads, and compare all three phases at the same polarity; only imbalance that survives settling counts.
- Everything balanced, but the load still trips or blows fuses on energization. Continuity is proven and insulation is not. That pattern is the voltage-dependent failure described in why a motor meggers good but trips the breaker on start.
Why a clean result says nothing about insulation #
The meter proves metal, not insulation. A defect that conducts at service voltage — carbonized tracking, a moisture path with contamination dissolved in it, a partly broken-down wall — can read fully open at a few volts, and the error runs both ways: a multimeter can also show a fault-like number on cable the megohmmeter proves healthy. One reported case makes the split visible: on a 3.3 kV cable, an ordinary multimeter showed 80 Ω phase-to-earth while a megohmmeter read 660 MΩ on the same conductors. The instruments did not disagree about one number; they drove different voltages through different paths. Moisture has no single ohmmeter value either — the reading depends on where it entered, what is dissolved in it, conductor spacing and temperature.
Classify the ohmmeter result honestly: continuity proven, hard short screened, insulation condition unknown. If the failure mode was a ground trip or an energization breakdown, the next instrument is a megohmmeter, not another pass with the ohmmeter.
The 500 V megohmmeter test that finishes the job #
Same setup, no exceptions: cable isolated and verified de-energized at both ends, all equipment disconnected, shields noted and handled as the cable's construction requires. Apply the instrument between each conductor and ground, then between each pair of conductors, holding each reading for one minute. For 480 V-class cable, 500 V DC is the standard instrument class; on new installations, use the test voltage the cable documentation or the job's acceptance specification calls out.
Read the result against a stated basis, not a hunch. Healthy low-voltage cable insulation reads in the megohms and keeps climbing as absorption current decays. Two documented benchmarks bracket the call: one acceptance specification for new electrical work requires 100 MΩ minimum, conductor-to-ground, after one minute, and one utility practice treats cable measuring below 100 kΩ per kilometre as an immediate replacement. The committed decision on a 480 V feeder: kilohm-range readings mean a failed cable, do not re-energize it; hundreds of megohms and still climbing passes the screening; the exact acceptance figure for a new pull is whatever the governing acceptance specification and the authority having jurisdiction fix for that installation.
Where you measure from changes what the reading includes: at the switchgear the reading includes everything downstream, at the motor terminals only the cable. That choice is laid out in insulation resistance testing from switchgear vs motor terminals.
Discharge every conductor to ground when the test is done and before anyone touches the cable: the same capacitance that bent the ohmmeter readings holds the megohmmeter's charge after the leads come off.
The decision for each case #
- Load will not start, breaker will not reset, or a fuse is open with the load disconnected. Run the three-loop ohmmeter test. It finds the open leg, the solid short and the high-resistance termination, and the imbalance between the loops names the conductor. Remake or replace, then re-test.
- Ground trips, leakage, or failure on energization with balanced ohmmeter readings. The ohmmeter has answered everything it can. Isolate both ends and run the megohmmeter, conductor-to-ground and phase-to-phase. Kilohms is a failed cable; megohms that climb is a pass.
- A fault must be localized along a long run. The ohmmeter proves a defect exists but gives no distance. That is a job for a time-domain reflectometer or a resistance bridge, instruments that convert the cable's electrical length into distance to an open or a short; the ohmmeter result tells you which fault class you are locating.
- The work is in a gassy mine area. No spark-capable instrument connects until the methane check the mine's procedure requires is taken and passed. MSHA's standards govern the atmosphere, the equipment and the people doing the work, and they decide before any field habit does.
The ohmmeter answers where the metal is broken or bridged. Everything about the insulation belongs to the megohmmeter, and in a mine, to the mine's own testing procedures first.
Questions asked
Can I use the continuity beeper instead of reading ohms?
Not for a power cable. The beeper only confirms the loop is below the meter's beep threshold, and a corroded splice adding a few ohms beeps exactly like clean copper. Read the numeric ohms value on all three loops and judge by the difference between them; the imbalance between phases is the finding, not the audible pass.
The far end of the run is unreachable. What can I still test?
Insulation, not continuity. With the far end safely disconnected, megohmmeter readings from one end — each conductor to ground and phase to phase — are still valid, and a low reading still fails the cable. An open conductor cannot be proven without a loop through the far end, and neither test gives distance to the fault; that needs a time-domain reflectometer or a resistance bridge.
What does moisture in a cable look like on a megohmmeter?
Low, flat readings. Dry insulation climbs steadily through the test minute as charging and absorption currents decay; wet or contaminated insulation stays low and nearly constant, and usually shows an imbalance between the three phases. Record the value at the end of the test minute every time so the trend is comparable with the cable's last test.
Can I leave the motor connected while I test the cable?
No. The motor's windings are a near-short between phases and from phases to the frame at the meter's test voltage, so every loop reads like the motor instead of the cable, and a real cable fault hides behind it. Disconnect and separate both ends, test the cable alone, and test the motor as its own measurement if you need it.