Explainer
Which starting current to use for motor short-circuit contribution
Short answer
For an IEC 60909 short-circuit study of a motor fed through a wye-delta starter, estimate the machine's reactance from its full-voltage starting current — the 7×In locked-rotor ratio — never the reduced wye current. The starter changes how the machine starts, not what it feeds a fault. Enter the 50 m and 5 m cables as separate segments and give each fault case only the runs between contributor and fault.
On this page
The starting current that belongs in the short-circuit study is the motor's full-voltage value — the 7×In locked-rotor ratio on the machine's data — not the reduced figure the wye-delta starter draws during acceleration. IEC 60909-0, 2016 edition, the standard that succeeded the IEC 363 method some projects still cite, builds the machine's short-circuit impedance from that ratio, because the fault contribution is a property of the machine and the starter inserts nothing that limits it. The wye connection changes how the machine starts; it does not change what the machine feeds a fault. The two cable runs in the one-line — 50 m ahead of the starter, 5 m behind it — are not one 55 m entry either: which run lies between contributor and fault changes from case to case. Below are the method, a worked example, the cable cases sorted, and the screening figure for the desk check.
The starting current the method is built on #
IEC 60909-0 defines a motor's starting current as the rms current the machine draws with the rotor locked, at rated voltage and rated frequency, and it estimates the machine's subtransient reactance from that ratio: on the motor's own base, roughly one divided by the locked-rotor ratio. The ratio belongs to the machine, not to the starter. A wye-delta starter accelerates the machine in wye, where each winding sees the line voltage divided by the square root of three, and the starting line current drops to about a third of the full-voltage value — a fact about the starting connection, not about the machine.
The reduced figure is therefore the wrong reactance input: entered in its place, it sets the machine's calculated impedance high by the starter's own ratio, and the fault contribution comes out low by the same factor. The starting current itself, reduced or not, is not a fault current either — it is the machine accelerating against its load, the distinction that matters when motor start peaks are compared against instantaneous breaker settings. For the fault study the locked-rotor ratio is the reactance input, and the contribution is a separate result the network solution produces.
Example: motor contribution from a 7×In machine behind a wye-delta starter #
Inputs, each with its source:
- Machine: the wye-delta-fed motor on the project one-line, rated current In from the nameplate. Every result below comes out as a multiple of In, and the nameplate amperes convert them at the end.
- Locked-rotor ratio at full voltage: 7, the machine's figure on the project data.
- System: 400 V, 50 Hz, three-phase, held within ±6 percent — the common low-voltage case for this starter; the ratio arithmetic itself does not depend on the voltage.
- Voltage factor for the maximum calculation: c = 1.05, the value IEC 60909-0 assigns to a 400 V system in that tolerance band.
- Fault point: the starter's incoming terminals, so both cable runs sit between machine and fault.
Rule, in words: on the machine's own base, the subtransient reactance is roughly one over the locked-rotor ratio, and the machine's contribution at its terminals comes back as the voltage factor times the locked-rotor current, before any series cable impedance trims it.
Arithmetic: z = 1/7 = 0.143 per unit. Contribution ≈ c × 7 × In = 1.05 × 7 × In = 7.35 × In. At the chosen fault point, the drop and the feeder sit in series with the machine, so the figure delivered to the fault lands slightly under 7.35 × In; enter both runs as separate segments and let the study net them — with no cable data to hand, the terminal figure is the ceiling.
Result: the machine feeds about 7.35 × In — 7.35 times the nameplate rated current, converted to amperes once In is substituted.
Decision: the study basis is the full-voltage ratio, nothing reduced. The same calculation fed the wye-reduced current gives 7/3 ≈ 2.33 × In, then 1.05 × 2.33 ≈ 2.45 × In — the machine's fault feed reported at about a third of its real size. This is a hand estimate for orientation; the signed value comes from the network solution, checked against the governing code and the machine documentation.
Which cable run belongs to which fault case #
The one-line shows 50 m of feeder from the switchboard to the starter and 5 m of drop from the starter to the motor. Both runs belong in the study; what changes by case is which of them lies between the contributing source and the fault.
- Fault at the starter's incoming terminals, the feeder's far end: the machine's path is the drop, the starter contacts and the feeder back up to the fault — all 55 m of it. The network's path is the feeder plus the upstream impedances, which come from converting the supply's prospective short-circuit current as in calculating source impedance from prospective short-circuit current.
- Fault at the motor terminals: the machine's own path is the drop alone, while the network's path is the feeder, the drop and everything upstream of it.
- Fault on the switchboard bus: the machine's path crosses both runs and continues into the upstream impedances; the network's path is only those upstream impedances.
The combined 55 m is therefore the machine-side path length only where both runs sit between machine and fault — never a blanket entry. Keep the two runs as separate segments with the starter junction between them: one lumped length hides the junction and makes the motor-terminal case impossible to build.
Confirming the runs against the installed cables means opening panels and gutters, so de-energize, lock out and test for absence of voltage first; NFPA 70E, 2024 edition, covers those safe-work practices, and the authority having jurisdiction and the equipment documentation carry the final requirements.
Where motors count, and where they don't #
IEC 60909-0 counts asynchronous motors in the maximum short-circuit calculation and discards them in the minimum one. The maximum sizes switchboards, breakers and bus bracing; the minimum exists to prove that each protective device still sees the smallest fault it must clear, and counting running machines there would flatter the trip check.
The machines move the peak as well as the symmetrical value: their feed is almost purely inductive, so it raises the X/R ratio at the point of connection and, with it, the asymmetrical current the equipment has to close and latch — which is exactly the subject of short-circuit study: X/R ratio impact on breaker ratings.
One connected machine changes the premise instead of the arithmetic: a motor behind a variable frequency drive does not feed the bus the way a directly connected machine does, because the drive sits between the two. analysis of how a VFD reduces a motor's short-circuit contribution works that case through.
A screening figure for the desk check #
When the question is only whether motors move the bus number at all, Eaton's short-circuit current calculation guide carries the standing shortcut: multiply the total connected motor full-load current in amperes by four, with values from four to six commonly accepted. Treat it as a screening number. The study value comes from the network solution, with the machine reactance and every cable segment in their places.
What to enter, case by case #
| Question | What goes into the study |
|---|---|
| Machine reactance basis | Full-voltage locked-rotor ratio from the machine data |
| Wye-reduced starting current | Nothing — it belongs to the starting study, not the fault study |
| Maximum calculation | Motors included, per IEC 60909-0 |
| Minimum calculation | Motors excluded |
| Cable runs | Separate segments; each fault case takes the runs on its own contributor paths |
| Desk check before the study | Total connected motor full-load current times four (four to six accepted) |
Commit three things in the study record and the report reviews itself: the machine's reactance basis, the per-case cable segmentation and the max/min treatment of motors. Get those right and the wye-delta starter appears in the fault study as what it is — a starting method, not a fault-current limiter.
Questions asked
Does the contribution change if the fault hits while the starter is still in wye?
For the study and the equipment ratings, no. The maximum calculation models the machine at its full-voltage reactance, and the run connection is the bounding state: the wye position lasts only the first seconds of an acceleration while protection clears in cycles. Through the wye connection the machine does present roughly three times the impedance, so a special during-start study would model the starter connection explicitly, but that case does not lower the duty basis for the switchboard or the starter.
The motor data sheet only gives the wye starting current — what do I enter?
Multiply the wye figure by three, the fixed ratio of a wye-delta starter at the same terminal voltage, to recover the full-voltage value, then confirm it against the machine's locked-rotor data or the manufacturer's documentation before the study is signed. If only a NEMA locked-rotor code letter exists, its kVA-per-horsepower range gives the locked-rotor ratio instead.
Why do motors drop out of the minimum calculation?
The minimum case exists to prove that each protective device still sees and clears the smallest fault it must handle, and running machines feed the fault, raising it. IEC 60909-0 includes asynchronous motors in the maximum calculation and excludes them from the minimum, so the trip check is not carried by the very machines that help it operate.
How does the starting ratio go into the study tool?
Enter the ratio of locked-rotor current to rated current at full voltage and let the tool derive the machine's per-unit reactance as roughly one over that ratio. A reduced starting current typed into that field sets the reactance high by the same factor, and the machine's contribution comes out correspondingly low. The starter never appears in the model as a current-limiting element.