Why a 22 kW motor oversped to 75 Hz does not guarantee 25 kW

Variable frequency drives Published 5 min read By Current Intel engineering team

Short answer

At 75 Hz a 22 kW, 380 V, 60 Hz motor reaches 27.5 kW only while it holds rated torque, which needs the drive voltage to rise with frequency: 480 V at 75 Hz keeps the ratio at 6.40 versus the base 6.33 V/Hz. On a supply capped near 380 V the same motor gives about 22 kW there, so a 25 kW load needs the 30 kW frame.

On this page
  1. Why the 75/60 multiplication is an assumption
  2. What rated torque at the higher speed requires
  3. What the drive must supply: current, not kilowatts
  4. Worked example: a 22 kW, 380 V, 60 Hz, 6-pole motor on a 480 V drive at 75 Hz
  5. The decision for each case
  6. Questions asked

A 22 kW, 380 V, 60 Hz motor does not promise 25 kW at the shaft just because a VFD is set to 75 Hz. The frequency change multiplies speed by 1.25, so the familiar 27.5 kW figure is real only while the motor keeps making rated torque at the higher speed. That holds when the drive voltage rises with frequency — a 480 V-class output — and fails when the output caps near the motor's base voltage, where the same machine gives roughly its base power. Here is how to tell which case you are in before ordering a drive or cutting a gear ratio.

Why the 75/60 multiplication is an assumption #

Shaft power is torque times speed. An induction motor keeps rated torque above base frequency only while volts per hertz stays at its base value, which requires the drive output voltage to climb in step with frequency. Once the output voltage stops climbing — at the drive maximum or the supply limit — flux falls, and the torque the motor can deliver at rated current falls with it. As a working approximation, torque capability tracks the flux: 20% less flux leaves about 80% of rated torque, which puts usable power back near the base rating. This is the standard field-weakening region and it is well understood; the trap is assuming a constant-torque stretch that the supply cannot fund. Frequency without voltage headroom gives speed without torque — the same mechanism behind a VFD showing low output voltage while the motor has no torque.

What rated torque at the higher speed requires #

Four conditions have to hold at once:

  • Voltage headroom. The drive's guaranteed continuous output voltage at the raised frequency must reach about 1.25 times the motor's base voltage — here, 480 V against a 380 V base. A voltage-source drive cannot make more AC voltage than its DC bus holds, so the supply decides: an industrial 460 V service can fund it, an urban service sitting at the base voltage cannot. Read the maximum continuous output voltage from the drive's data sheet, not from its model name.
  • Insulation cleared for the voltage and the speed. For inverter-fed motors, NEMA MG-1 Part 31 defines how the rated voltage applies to the highest fundamental voltage the motor sees across its rated speed range. Editions change, so read the edition your motor was certified to and confirm the rating with the maker's documentation and your authority having jurisdiction.
  • Mechanical speed. Six poles give 1200 rpm synchronous at base frequency and 1500 rpm at the raised one — 25% over. Bearings, balance and rotor construction set the ceiling, and the maker's stated maximum speed decides, not the nameplate frequency.
  • Cooling and duty. Above base speed the shaft-mounted fan moves more air, so cooling improves on its own; a separately powered fan is the fix for low speed with full torque, not for overspeed. What remains is duty: hard acceleration cycles load the drive and the reducer, and the gear must accept the faster input shaft.

What the drive must supply: current, not kilowatts #

Select the drive on output current and let the motor's nameplate FLA at base voltage set that number — never the kilowatt label. At rated torque the stator current at the raised frequency sits close to the current at base: the magnetizing share drops as flux eases and the torque-producing share carries the load, so a drive matched to the nameplate current covers the overspeed run too. Set the motor overload protection from that same nameplate FLA, as the page on why a VFD motor overload current setting takes nameplate FLA explains, and check the drive's overload class against the acceleration duty. Before sizing around torque at speed, work through VFD rated current vs motor full-load starting torque, because peak torque demand, not the continuous figure, is what usually forces a drive size up.

Worked example: a 22 kW, 380 V, 60 Hz, 6-pole motor on a 480 V drive at 75 Hz #

The case as posed: a 22 kW, 6-pole induction motor with base data of 380 V, 60 Hz (1200 rpm synchronous), driven by a VFD whose data sheet gives 480 V continuous output at 75 Hz (1500 rpm), against a 25 kW continuous load.

The rule: shaft power in kilowatts equals torque in newton-metres times speed in rpm divided by 9550, and the overspeed rating exists only if torque stays at rated while speed climbs.

The arithmetic: rated torque T = 9550 × 22 / 1200 = 175 N·m. With torque held at that value, P = 175 × 1500 / 9550 = 27.5 kW. The voltage check says whether torque holds: base ratio 380 / 60 = 6.33 V/Hz; drive ratio at the raised speed 480 / 75 = 6.40 V/Hz, about 1% above base, so flux and available torque stay essentially at rated. Spare capacity is 27.5 - 25 = 2.5 kW, about 10% of the load.

Result: 27.5 kW of shaft power at 1500 rpm, valid only while the drive genuinely makes 480 V at that frequency and the motor is cleared for the voltage and speed. The decision this leads to: with full voltage headroom the load fits on the 10% margin; if the output caps near the base voltage instead, the ratio drops 20% below base, torque capability follows, and usable power collapses to about the base rating — 3 kW short of the load.

The decision for each case #

Case 1 — the drive's data sheet guarantees full voltage at the raised frequency and the motor maker clears the voltage and speed: the overspeed rating is real, it carries the load on the margin shown above, and the drive is selected on the motor's nameplate current with its overload class matched to the duty. Confirm the gear accepts the faster input shaft.

Case 2 — the supply or the drive caps the output near the motor's base voltage: usable power stays at the base rating, about 3 kW short of the load, and no setting, fan or filter recovers it. Buy the next standard frame — 30 kW here — and run it at its own rated point; that also buys back the acceleration reserve the overspeed scheme spends.

Case 3 — the process runs at one fixed speed: skip the overspeed idea. Efficiency differences between the frames are tenths of a point while the drive adds losses every running hour, so the larger frame at its rated point is the cheaper machine to own and to protect.

Questions asked

What happens if the drive output caps near the motor's base voltage?

The ratio falls to about 5.07 V/Hz against the base 6.33, so flux and the torque available at rated current drop about 20%, leaving usable shaft power near the base rating of 22 kW. Against a 25 kW continuous load that is roughly 14% uncovered, a deficit no duty cycle repays. The next standard frame, 30 kW, is the decision.

Can a dual-voltage motor connected in delta stretch the voltage limit?

On paper yes: 380 V across the 220 V delta connection needs 1.73 times base frequency, about 104 Hz, to restore the same volts-per-hertz. Whether the motor tolerates it is separate: winding insulation, rotor balance and bearing speed limits all get a vote, and the maker's terminal diagram decides. Before moving any links, de-energize the circuit and verify absence of voltage at the terminal box.

Does a separately powered cooling fan buy anything at 75 Hz?

Nothing at overspeed. The shaft-mounted fan moves more air as speed rises, so cooling improves above base frequency on its own. A forced fan earns its place at low speed with full torque, where the shaft fan starves. It does nothing for torque lost to a voltage cap, for the rotor's mechanical speed ceiling, or for the drive's current rating.

Is the overspeed scheme a way to save energy against a larger standard motor?

No. Between roughly 75% and full load these frames change efficiency by only tenths of a point, and the drive adds losses of its own every running hour. At one fixed speed the larger frame is usually cheaper to own and simpler to protect. The overspeed trick pays only when the process genuinely needs the extra speed or the smaller frame avoids a special size.

Keep reading

  • How-to

    Running a 15 HP motor on a 30 kW VFD safely

    Yes — a 15 HP motor runs without harm on a 30 kW VFD in V/Hz duty, because the drive delivers only the current the motor draws. Before start, verify the electronic overload can be set down to the nameplate current, keep sensorless vector off this pairing unless the manual's permitted motor range covers it, and reform the DC-link capacitors if the drive sat unpowered for years.

    Variable frequency drives

  • Troubleshooting

    Spindle VFD hums but won't turn: fixing wrong motor data

    A spindle that hums without turning on a VFD usually has wrong motor data, not a wiring or supply problem. In the reported case the rated speed was entered one-tenth of the nameplate. Enter the complete nameplate set, rerun autotune with the shaft uncoupled, and confirm the drive's label allows single-phase input.

    Variable frequency drives

  • Explainer

    VFD rated current vs motor full-load starting torque

    Yes, a 4.3 A drive can start this motor at full load, but the decision is torque, not the ampere ratio. It needs a constant-torque duty rating, a 150% overload reserve, and sensorless vector or direct torque control to hold about 7.5 Nm against a 5 Nm load from standstill.

    Variable frequency drives