Current IntelPower LibraryShop main store

Explainer

VFD rated current vs motor full-load starting torque

Variable frequency drives Published 6 min read By Current Intel engineering team

Short answer

Yes, a 4.3 A drive can start this motor at full load, but the decision is torque, not the ampere ratio. It needs a constant-torque duty rating, a 150% overload reserve, and sensorless vector or direct torque control to hold about 7.5 Nm against a 5 Nm load from standstill.

On this page
  1. What the current ratio actually decides
  2. Why the 11.55 A locked-rotor figure never enters the ramp
  3. The torque budget: a worked example
  4. What the drive datasheet must confirm
  5. Setting up the drive for the start
  6. Prove the start before signing off
  7. Questions asked

Yes, a drive rated 4.3 A output will start this motor at full load, but not because 4.3 A is 2.6 times the motor's rated current. The start is decided by whether the drive can hold roughly 150% torque from standstill through the whole speed ramp, which takes a constant-torque duty rating and sensorless vector control or direct torque control. The 11.55 A locked-rotor current on the nameplate belongs to direct-on-line starting and never appears during a drive ramp.

What the current ratio actually decides #

The drive's continuous output of 4.3 A is 2.6 times the motor's nameplate current of 1.65 A, so the drive has ample thermal headroom on its own side. What the oversize buys you is overload reserve: a constant-torque duty rating at this frame size typically permits 150% of rated output current for 60 seconds, which is 1.5 × 4.3 A = 6.45 A. The current this motor needs to make 150% torque sits well inside that envelope, so the ampere question is answered before the drive is even connected.

A drive sold only for fans and centrifugal pumps carries a lighter duty rating and a smaller overload reserve. It is the wrong part for a loaded start even when its continuous amperes look generous, because it cannot hold the torque this start demands.

Why the 11.55 A locked-rotor figure never enters the ramp #

The nameplate start-to-rated current ratio of 7.0 describes one event: full rated voltage at rated frequency applied to a stationary rotor. High slip drives a large rotor current, and 7.0 × 1.65 A = 11.55 A flows until the machine spins up. That figure is the baseline for a contactor start and for setting instantaneous protection, which is why motor start peaks cannot be compared directly with breaker instantaneous settings, as covered in the article on motor starting current peaks versus breaker settings.

A variable frequency drive does the opposite. It commands an output frequency near zero and raises it as the rotor accelerates, so slip stays small throughout the ramp and the current needed for a given torque stays far below the locked-rotor value. If you also protect the motor against a genuine stall elsewhere in the system, the physics behind that is the same as in this knowledge-base article on protecting motors against locked-rotor failures.

The torque budget: a worked example #

Example inputs, all stated so you can substitute your own: a three-phase motor rated 0.75 kW, 400 V, 50 Hz, rated torque 5 Nm; a load that demands full rated torque at breakaway; total inertia reflected to the motor shaft of 0.02 kg·m²; a drive with constant-torque duty, sensorless vector control, and the standard 150% for 60 seconds overload rating; a four-pole machine at roughly 149 rad/s at rated speed.

  1. Torque target for a strong start: 1.5 × 5 Nm = 7.5 Nm, the drive's specified low-speed torque figure.
  2. Accelerating margin at breakaway: 7.5 Nm − 5 Nm = 2.5 Nm.
  3. Angular acceleration: 2.5 Nm ÷ 0.02 kg·m² = 125 rad/s².
  4. Time to rated speed: 149 rad/s ÷ 125 rad/s² ≈ 1.2 s, far inside the 60 second overload window. The inertia and ramp arithmetic is the same as in the article on motor starting time, torque margin and inertia.
  5. Current check: torque-producing current near 1.5 × 1.65 A ≈ 2.5 A, against the drive's 6.45 A overload limit.

Treat the 150% references as screening values. Motor current contains a magnetizing component as well as a torque-producing one, so current does not convert to torque at a fixed rate, and the exact figure depends on the motor, the control mode and the quality of the motor identification. The number to trust is the starting-torque capability the drive's own datasheet states, not a conversion.

What the drive datasheet must confirm #

  • A constant-torque duty rating with 150% output current for 60 seconds, plus the stated recovery interval before the reserve is available again.
  • Sensorless vector control or direct torque control with a published starting-torque figure. Not every drive labelled sensorless delivers full torque right at zero speed; speed estimation degrades as speed approaches zero, so read the fine print and the permitted duration of low-speed running.
  • Motor-identification and motor-thermal adjustment ranges that include a motor this small. A drive 2.6 times oversized on current is fine electrically, but if 0.75 kW falls below the range floor, the drive cannot model the motor or protect it correctly.
  • Supply and output voltage matching the three-phase 400 V connection shown on the motor terminal diagram. An ample current rating establishes nothing about voltage compatibility.

Setting up the drive for the start #

Before touching terminals or running motor identification, de-energize the panel, lock out, and test for absence of voltage; NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers those safe-work practices, and you should confirm the details with your authority having jurisdiction and the equipment documentation. Some identification routines rotate the shaft, so clear the load or confirm it may turn first. Then:

  1. Enter the nameplate data exactly: the 400 V, 50 Hz, rated current and rated speed values, and anything else the identification routine requests. Read missing values from the nameplate rather than estimating them.
  2. Run the manufacturer's motor identification or tuning procedure for the selected control mode.
  3. Select sensorless vector or direct torque control, not V/Hz, for a full-load breakaway. Plain V/Hz lets stator resistance consume too much of the applied voltage at low frequency, and flux and torque collapse before the load moves.
  4. Set the motor thermal model and electronic overload from the motor's own rated current, never the drive's rating; the reasoning is the same as when you set an overload relay from nameplate full-load current.
  5. Set the current limit and acceleration ramp so the demanded torque stays inside both the motor's capability and the drive's overload curve.

Prove the start before signing off #

Record commanded speed, output current, current-limit status and drive thermal state during a loaded start. A good start accelerates through the whole speed range without parking at the current limit, without stalling, and without exhausting the permitted overload duration. A ramp longer than 1.2 s reduces the inertia torque demand, but no ramp fixes a load whose breakaway torque exceeds what the motor can produce.

Separate the two failure modes. A stall at low speed points at torque production, mechanical binding, motor connection or tuning; a trip after the second or third start points at duty cycle and heat, because shaft-mounted cooling falls with speed and the overload reserve shrinks on a hot drive. One successful cold start is not acceptance: validate repeated starts and any sustained low-speed running against the motor's cooling requirements and the drive's overload curve before the machine goes into service.

Questions asked

Why doesn't the drive need the locked-rotor current the nameplate implies?

The nameplate's 7.0 ratio describes what happens when rated frequency hits a stationary rotor. A drive never does that: it commands a low output frequency and raises it as the rotor accelerates, so slip stays small and the torque-producing current stays near 2.5 A in this example. Only a direct-on-line contactor start draws the full 11.55 A.

Will plain V/Hz control start a motor at full load?

Usually not reliably. At low output frequency, stator resistance consumes a large share of the applied voltage, so airgap flux and torque collapse before the load breaks away. Some drives offer enhanced low-speed modes or closed-loop operation with an encoder for sustained torque near zero speed; check the drive's own documentation for what its control modes are specified to deliver.

Is a drive 2.6 times the motor current too big?

Electrically it is fine, and the reserve is useful. The real risk is that a motor this small falls outside the drive's motor-identification and thermal-protection adjustment ranges; if it does, the drive cannot model the motor properly or trip it at the right level. Confirm both ranges in the drive's rating tables before selecting it on continuous amperes alone.

How long can the drive hold its overload output?

A constant-torque rating is typically 150% output current for 60 seconds, then the drive requires a recovery interval at or below continuous load before the reserve is fully available again. The overload counter is usually thermal, so a hot motor and hot drive from previous starts have less reserve than a cold one; check the drive's overload curve for the hot-start figure.

Keep reading

  • Explainer

    Running a 450 kW DOL motor on a VFD: what to verify first

    A 3.3 kV, 450 kW motor will start and run on a correctly sized medium-voltage drive, but the Class F VPI insulation is not proven inverter-duty, so get the manufacturer's written withstand against the drive's output before connecting. On DOL, two motors draw 186 A running, 651 A with one starting, 1,116 A with both starting.

    Variable frequency drives

  • Troubleshooting

    Spindle VFD hums but won't turn: fixing wrong motor data

    A spindle that hums without turning on a VFD usually has wrong motor data, not a wiring or supply problem. In the reported case the rated speed was entered one-tenth of the nameplate. Enter the complete nameplate set, rerun autotune with the shaft uncoupled, and confirm the drive's label allows single-phase input.

    Variable frequency drives

  • Troubleshooting

    Why a VFD DC bus overload fault appears when a soft starter starts

    When a soft starter starts on the same feeder, its current-limited start current still sags the supply at the VFD's input terminals, and the drive's DC bus follows within a few cycles — the dip, not a spike, is the likely cause of the trip. Read the exact fault code, calculate the sag from the transformer impedance and the starter's current limit, and confirm with a power-quality record taken at the drive terminals during a coordinated start before changing any setting.

    Variable frequency drives