Troubleshooting
Why a VFD DC bus overload fault appears when a soft starter starts
Short answer
When a soft starter starts on the same feeder, its current-limited start current still sags the supply at the VFD's input terminals, and the drive's DC bus follows within a few cycles — the dip, not a spike, is the likely cause of the trip. Read the exact fault code, calculate the sag from the transformer impedance and the starter's current limit, and confirm with a power-quality record taken at the drive terminals during a coordinated start before changing any setting.
On this page
The soft starter is not putting a spike on the bus — the opposite is far more likely. A soft-started motor still draws several times its full-load current for the seconds of acceleration, and through the impedance of the shared transformer and feeder that current sags the voltage at the drive's input terminals. The DC bus inside a VFD follows its input within a few line cycles, so a dip that a panel meter checked after the fact never saw can pull the bus below its limit and trip the drive. Read the exact DC bus fault code from the drive's fault history, calculate the sag the start should produce on your feeder, and capture one coordinated start with a power-quality recorder at the drive input terminals. Then fix the branch the evidence points to.
Match the exact fault code before picking a cause #
A display line that reads as a DC bus overload can stand for more than one trip, and each has its own correction. Open the drive's fault history, read the exact fault code stored at the event, and match it to that model's fault table: a bus overvoltage code, a bus undervoltage code and a drive thermal or charging-circuit overload are distinct documented conditions with distinct limits. Record the timestamp too. A trip that lands within a couple of seconds of the soft starter's start command, on every start, points at the shared supply; a trip that lands at random has its own causes, covered in why a VFD DC bus overvoltage fault appears at random. The mains reading the manual asked for only proves the supply was healthy at a moment when nothing was starting — it cannot clear or convict a disturbance that lasts a few seconds.
How a start on a shared feeder moves the drive's DC bus #
Current through source impedance is the link between the two cabinets. A soft starter does not remove starting current: it trades the across-the-line peak for a limited, ramped value that is still several times the motor's full-load current, which is exactly why the starter barely improves the utility voltage dip it was meant to soften. Compute the current your feeder sees from the motor nameplate and the starter's limit setting, or convert the starter's kVA rating to a starting current.
Behind the drive's input bridge, the bus sits near 1.35 times the line-to-line rms voltage under load, because the six-pulse rectifier conducts continuously and the bus tracks its input within a few cycles. The capacitors decouple the bus only briefly at load, so a sag lasting the seconds of a soft start reaches the bus as a real drop. Which limit the dip crosses decides the code: undervoltage when the bus falls; overvoltage when the bus rises — and it rises when the running motor is driven by its load, which a second machine engaging on the same mechanical line can do for a moment. That is the same regeneration that makes a VFD overvoltage fault show with no motor connected. A thermal overload code has a third path: during the dip the running drive raises its output current to hold speed and torque, its thermal model accumulates, and the trip lands at the very start that caused it.
This is also why each machine runs fine on its own: alone, neither loads the feeder hard enough. The fault needs both at once, so independent operation proves nothing about the shared path.
Worked example: a 496 A start against a 150 kVA, 4% feeder #
The reported case gives the topology — two machines, one feeder — but no measurements, so every number below is an example value; read yours from the transformer nameplate, the motor nameplate and the starter setting before you trust the result.
- Supply at the shared bus: 480 V, three-phase.
- Shared feeder transformer: 150 kVA with a nameplate impedance of 4%.
- Soft-started motor: 124 A full-load current on its nameplate.
- Starter current limit: 4 × 124 A = 496 A, held through acceleration.
- Upstream impedance: neglected, small next to the transformer.
The method: convert the transformer's impedance percentage to ohms, multiply by the start current for the per-phase drop, divide by the line-to-neutral voltage for the sag fraction, and put the sagged line-to-line voltage into the 1.35 factor for the bus.
- Base impedance: 480 V squared ÷ 150,000 VA = 230,400 ÷ 150,000 = 1.536 Ω.
- Transformer impedance: 0.04 × 1.536 Ω = 0.0614 Ω per phase.
- Drop during the start: 496 A × 0.0614 Ω = 30.5 V per phase.
- Line-to-neutral voltage: 480 V ÷ 1.732 = 277 V, so the sag is 30.5 ÷ 277 = 11.0%.
- Bus during the start: the sagged line-to-line voltage is 427 V (480 × 0.890), and 1.35 × 427 ≈ 577 V DC, against about 648 V DC healthy — roughly 71 V of margin gone for the seconds of the start.
What moves the number: each additional 100 A of start current through this transformer adds about 11 V of line-to-line drop, near 2.2 points of sag; a 300 kVA transformer halves the impedance and the sag to about 5.5%; a limit of 6 × full-load current pushes the sag to about 16.5% and the bus near 541 V DC. The estimate ignores X/R and upstream impedance, so treat it as an estimate to check against the record — it is the same divider arithmetic used in a second motor starting voltage drop calculation for any other start in the plant.
Decision: if this model's fault table puts its bus undervoltage threshold above roughly 577 V DC, an 11% dip on every start is enough to trip a loaded drive, and the cause is the start current on the shared feeder — cut the peak, repair the feeder, or separate the starts. If the recorder shows a smaller dip than this, the difference is connection resistance upstream of the recorder; find and repair it under lockout rather than tuning the drive around it.
Capture the event at the drive input terminals #
A handheld meter reading answers a different question: it samples the supply between events, usually upstream of the feeder impedance that matters, and averages what it sees. The disturbance exists only while the starter ramps. IEEE 1159, the 2019 edition, is the reference here — it classifies short-duration rms variations, sags reaching between 10% and 90% of nominal and lasting from half a cycle to about a minute, exactly the class of event a once-a-second reading never shows. Confirm the monitoring you need against the drive documentation and the standard's current edition.
One safety note before any connections: de-energize the feeder, lock out and verify absence of voltage under the site's procedure and NFPA 70E, the 2024 edition; if the capture requires the feeder live, connect under the documented energized-work controls, and never probe the drive's internal DC bus with ordinary test equipment.
Then capture one coordinated start:
- A three-phase power-quality recorder at the drive's input terminals, connected by qualified personnel, logging all phase-to-phase voltages.
- The soft starter's output current, measured where the instrument and starter manuals say to measure it — measuring VFD and soft starter current with the right meter matters, because an ordinary clamp averages the distorted waveform.
- The drive's own record over the same window: bus voltage, output current, speed, operating state, plus the fault code and timestamp from the fault history, saved before anything is reset.
- The starter's start command, as the timing reference for all four traces.
If the dip at the drive terminals matches the calculated sag and the fault timestamp, the shared supply is the cause. If the input voltage barely moves while the bus fault fires, look at the mechanical load on the running motor and the control wiring instead.
What to fix in each branch #
Fix what the record shows, one change at a time, and leave the drive's protection where the fault table and the motor nameplate put it — raising a trip setting to make a trip disappear treats the symptom, the same reason raising a magnetic overload setting won't fix a hard start.
- Bus undervoltage at every coordinated start. The record confirms the dip. Cut the peak: lower the starter's current limit as far as the load still accelerates, verify and retorque the shared feeder connections under lockout, check what else on that transformer starts at the same time, and if the feeder is simply too soft for two machines, separate the starts with a time-delay interlock or give the drive its own feed.
- Bus overvoltage. Energy came up from the motor side or from a recovering supply. Check what the running machine's load did at the trip instant — a shared conveyor, chain or hydraulic that the second start unloads or back-drives — then review the drive's decel ramp and its documented braking options before selecting hardware.
- Thermal or motor overload. The running drive's current climbed through the dip to hold speed. Correct the load change the second start causes on the running machine; if the running motor sits near its limit anyway, set its protection from the nameplate full-load current.
- No disturbance on the record. Treat it as a control-state event: chase the start and stop commands, shared control power and the drive's digital inputs against the same timestamp before touching the power circuit.
One capture usually ends the argument: the fault code, the bus voltage, the starter current and the timestamps on the same record name the branch, and the branch names the fix.
Questions asked
Can a soft starter send a voltage spike that trips a VFD?
A spike is the unlikely direction. The starter limits current to a ramped value that is still several times the motor's full-load current, and the shared transformer and feeder impedance turn that current into a sag at the drive's input terminals, not a surge. The recorded trace decides it: a swell or transient on the record points to something else switching on the supply, such as capacitor banks or contactor transitions, and that has its own correction.
Will a longer acceleration ramp on the soft starter stop the VFD trip?
Not by itself. The ramp sets how quickly voltage to the starter's motor rises; the current limit sets the peak the shared feeder sees. If the drive trips on a bus undervoltage code, lowering the current limit shrinks the sag, while stretching the same peak over more seconds may only lengthen the disturbance. Check the starter documentation for how its limit and ramp interact, and confirm the load still accelerates at the lower current.
Is sequencing the two starts a legitimate fix?
Yes, when the record shows the sag is the cause. A time-delay interlock that lets the soft-started motor reach speed before the second machine runs, or that blocks the starter's command while the drive-fed machine is loaded, removes the overlap that produces the dip. It is a control fix, not a suppression: the drive's protection stays where its fault table and the motor nameplate put it, and the interlock must respect the machine's own safety and process requirements.
What DC bus voltage should a drive show on a healthy 480 V supply?
On the common six-pulse input, the bus sits near 1.35 times the line-to-line rms under load — about 648 V DC — and nearer 1.41 times that value with the input lightly loaded. The trip thresholds on either side of that band are model-specific and live in that drive's fault table. The worked start in this article pulls the loaded bus to about 577 V, and whether that trips depends on the drive's documented undervoltage threshold.
Why does the manual's mains voltage check miss the problem?
The check is taken when the supply is healthy, at a point usually upstream of the feeder impedance that matters, and a handheld meter averages what it samples. An 11% sag lasting the seconds of a soft start is invisible to that reading but fully reaches the drive's bus, because the input rectifier conducts continuously. Only a recorder capturing during the start, at the drive's own terminals, shows the event the fault history is complaining about.
Do I need to change any drive parameter to fix this?
Usually none until the record is in. The settings that matter live on the soft starter, in the supply path and in the start sequence, not in the running drive. Save the drive's fault history and active settings before any reset, change one item at a time, and repeat the coordinated capture after each change to confirm the dip shrank rather than the trip merely moving.