Current IntelPower LibraryShop main store

How-to

Second motor starting voltage drop calculation

Motors and motor starters Published 9 min read

Short answer

The second motor's dip is √3·I·(R cosφ + X sinφ) through the shared source-and-feeder impedance, with I the phasor sum of the running motor's load current and the starting motor's locked-rotor current. The running motor supplies none of the start; it adds to the drop. Iterate once on the reduced terminal voltage, then judge by torque, which falls with the square of voltage.

On this page
  1. Inrush is not starting current
  2. The formula the second start obeys
  3. Step-by-step calculation
  4. Worked example: 75 kW second start on a 1000 kVA transformer
  5. Why a lower starting current is not a smaller problem
  6. Measuring to confirm the number
  7. The decision for each case
  8. Questions asked

Starting the second motor while the first one runs is the same dip calculation as any motor start, plus one term: the current through every shared impedance is the phasor sum of the starting motor's locked-rotor current and the running motor's load current. The running motor supplies none of the start — it deepens it.

Use ΔV_LL ≈ √3 · I · (R·cosφ + X·sinφ) on the shared path with that summed current, correct once for the reduced terminal voltage, then judge the start on torque, which falls with the square of terminal voltage. In the worked example below, a 75 kW motor started on a 1000 kVA transformer while its loaded twin runs dips the bus 8.5%: it clears a 90% motor-terminal limit, fails a 7% network-operator limit, and passes that limit at 3.6% with a star-delta starter.

Inrush is not starting current #

Inrush is the magnetizing transient that flows for a few cycles when voltage is first applied to a winding. Starting current is the locked-rotor current the motor draws through the whole acceleration — seconds rather than cycles — and it is what depresses the bus while the second motor comes up to speed. Take the locked-rotor current and its power factor from the motor data sheet, not from a peak captured over a few cycles. The same split matters when you estimate voltage sag from motor inrush current on a single motor: the few-cycle peak and the sustained starting current produce different dips and different decisions.

The formula the second start obeys #

For one balanced three-phase impedance section:

ΔV_LL ≈ √3 · I · (R·cosφ + X·sinφ)

I is the RMS line current in that section, R and X its per-phase resistance and reactance, and φ the angle of the combined current in it. The angle matters twice: it weights R against X inside the bracket, and it is why the two motor currents must be added as phasors rather than as magnitudes — locked-rotor current at a power factor near 0.35 and a running motor near 0.85 do not line up.

The impedance chain is the source plus every conductor the two motors share. A transformer contributes from its nameplate as Z = (uk/100) · V_LL² / S, using secondary line voltage and three-phase kVA. If the source is a generator, use its transient reactance from the data sheet for the acceleration period and credit the excitation boost only as documented; a sagging frequency is a separate problem the voltage arithmetic cannot see. Cable R and X come from the manufacturer or from IEC 60228 conductor resistance values corrected to operating temperature. Downstream of the last shared busbar, each branch carries only its own motor's current. With nothing else running, the calculation collapses to the single-motor case — the motor starting voltage dip calculation on an 11 kV bus walks that version.

Step-by-step calculation #

  1. Collect the inputs: transformer or generator data (kVA, voltage, uk or reactances), feeder size, length and per-phase impedance, both motors' nameplate full-load currents, the starting motor's locked-rotor multiple and power factor, and the running motor's measured load current and power factor.
  2. Convert the source: Z_base = V_LL² / S in ohms, then X_source = (uk/100) · Z_base for a transformer.
  3. Add the shared path: series R and X of transformer plus every shared cable section, per phase.
  4. Split each current into components: real part I·cosφ, reactive part I·sinφ, using each motor's own power factor.
  5. Add the components of all motors on the shared path, then form I = √(Σreal² + Σreactive²) and the combined cosφ = Σreal / I.
  6. Apply the formula for ΔV_LL; the dip in percent is ΔV_LL / V_rated × 100.
  7. Correct: scale the starting current by (V_rated − ΔV_LL) / V_rated, redo steps 4 to 6, and stop when the dip changes by less than about one percent.
  8. Judge: torque factor = (V_terminal / V_rated)², compared against the load's torque demand, and the dip compared against the governing limit, before deciding on the starter.

Worked example: 75 kW second start on a 1000 kVA transformer #

Illustrative inputs, every one replaceable with your own:

  • Transformer: 1000 kVA, 420 V secondary, uk = 6%.
  • Shared feeder: 80 m of 95 mm² copper 3-core, R = 0.245 Ω/km and X = 0.080 Ω/km at operating temperature.
  • Motor 2 (starting): 75 kW, 400 V, 135 A full-load; locked-rotor current 6 × 135 = 810 A at power factor 0.35 (sinφ = 0.937).
  • Motor 1 (running): same rating, measured 110 A at power factor 0.85 (sinφ = 0.527).

Impedances per phase: Z_base = 420² / 1,000,000 = 0.1764 Ω, so X_T = 0.06 × 0.1764 = 0.0106 Ω. Feeder: R = 0.245 × 0.080 km = 0.0196 Ω, X = 0.080 × 0.080 = 0.0064 Ω. Shared path totals: R = 0.0196 Ω (transformer resistance is worth about a volt here and is left out), X = 0.0106 + 0.0064 = 0.0170 Ω.

First pass #

Motor 2 components: 810 × 0.35 = 283.5 A real, 810 × 0.937 = 759.0 A reactive. Motor 1: 110 × 0.85 = 93.5 A real, 110 × 0.527 = 57.9 A reactive. Sum: 377.0 A real, 816.9 A reactive, so I = √(377.0² + 816.9²) = 899.7 A at cosφ = 377.0 / 899.7 = 0.419.

ΔV_LL = 1.732 × 899.7 × (0.0196 × 0.419 + 0.0170 × 0.908) = 1.732 × 899.7 × 0.02365 = 36.9 V, which is 9.2% of 400 V and leaves 363 V at the motor.

For comparison, motor 2 alone on the same system: ΔV_LL = 1.732 × 810 × (0.0196 × 0.35 + 0.0170 × 0.937) = 32.0 V, or 8.0%. The running twin costs about 1.2 percentage points of extra dip, and it supplies none of the start.

Voltage correction #

At 363 V the starting current is not 810 A but 810 × 363/400 = 735 A. Redo the sum: 735 × 0.35 = 257.3 A real, 735 × 0.937 = 688.7 A reactive; with motor 1 that is 350.8 A real and 746.6 A reactive, so I = √(350.8² + 746.6²) = 825 A at cosφ = 0.425.

ΔV_LL = 1.732 × 825 × (0.0196 × 0.425 + 0.0170 × 0.905) = 1.732 × 825 × 0.02372 = 33.9 V, or 8.5%, leaving 366 V at the motor.

Case Current on shared path Dip Motor-2 terminal Torque factor
Motor 2 alone, first pass 810 A 8.0% (32.0 V) 368 V 0.85
Motor 1 running, first pass 899.7 A 9.2% (36.9 V) 363 V 0.82
Motor 1 running, corrected 825 A 8.5% (33.9 V) 366 V 0.84

A third pass moves the answer less than half a volt, so 8.5% stands. The result is an estimate — balanced conditions, one cage characteristic through the start, and the inputs as stated — to be checked against the governing code and the equipment documentation before it drives a purchase.

Why a lower starting current is not a smaller problem #

The corrected current, 735 A instead of 810 A, is simply full voltage no longer being there, and what the voltage took from the current it took from the torque twice over. Starting torque scales with the square of terminal voltage: at 366 V the motor delivers (366/400)² = 0.84 of its full-voltage starting torque. If the load needs 60% of that torque, the net accelerating torque is 24 points instead of 40, and the start takes roughly 40/24 = 1.7 times longer, with locked-rotor current flowing for every extra second and the running motor sitting at 366 V through the same window. Judge the second start on acceleration time and thermal duty, never on the peak current reading alone.

Measuring to confirm the number #

Meter at the motor terminals, not only at the panel: the panel bus can look healthy while the branch feeder, starter contacts and motor leads carry their own drop. Record three-phase RMS line voltage before the start, its minimum through acceleration, and its recovery; record the starting current and the time to rated speed on the same trace; record the source voltage at the transformer or generator simultaneously so the drop lands on the right section. All connections are made with the circuit de-energized, locked out and verified absent of voltage before the start — a recording instrument installed beforehand, never a hand-held meter at live terminals during the event.

The decision for each case #

IEC 60034-1:2022, the rating-and-performance standard for rotating electrical machines, defines the voltage variation zones a machine must tolerate; its Zone B spans roughly ±10% of rated voltage for limited operation with deviations in performance, which is where the common working floor of 90% of rated voltage during acceleration comes from.

IEC 60034-12:2024 defines starting performance — locked-rotor current and torque — for eight designs of single-speed three-phase 50/60 Hz cage motors up to 1000 V intended for direct-on-line and star-delta starting under duty S1, and it is against that standard's data-sheet figures that a starting-current multiple belongs; one high-voltage supplementary specification to IEC 60034-1 places declared locked-rotor current between 4 and 6.5 times rated, and low-voltage designs commonly sit a little above that. In Australia and New Zealand, network operators' connection rules alongside AS/NZS 3000:2018, the wiring rules, commonly allow a 7% starting voltage variation for infrequent starts (under one per hour) and 4% for frequent ones, with the local operator's figure governing. Confirm each limit with the authority having jurisdiction and the equipment documentation.

Basis Limit Example result Decision
Motor terminal, IEC 60034-1 Zone B floor ≥ 360 V (90% of 400 V) 366 V Start direct-on-line; the load must accelerate on 84% of full-voltage torque — fans and centrifugal pumps do, loaded compressors and belts need the torque-speed curve checked
Network dip, infrequent starts 7% 8.5% Fails — change the start or stiffen the source
Network dip, frequent starts 4% 8.5% Fails — change the start or stiffen the source
Star-delta on motor 2 — 3.6% dip Passes both network limits; requires a load that accelerates on about 31% of full-voltage starting torque

The star-delta fix, same arithmetic: line current at start falls to about 735/3 = 245 A; with motor 1 running, the shared current is 339 A at cosφ 0.53, and ΔV_LL = 1.732 × 339 × (0.0196 × 0.53 + 0.0170 × 0.85) = 14.6 V, or 3.6%. Torque falls to a third of the direct-on-line value at the same voltage — about 31% of full-voltage torque here — and the open-transition spike is a current and torque transient the driven machine must tolerate.

If the starter is not the lever you want, stiffen the source: the effect of closing the bus tie on motor starting shows how the shared impedance moves when the sections join, and where large, frequent starts are the norm, sizing a transformer for a 200 HP across-the-line motor start is the cleaner fix.

Carry the method, not a rule of thumb: a second start is a first start plus the running load, added as phasors on every shared section, corrected once for the terminal voltage it causes, and judged on torque squared before anyone calls a lower current a win.

Questions asked

Does the motor already running feed part of the second motor's starting current?

No. A running induction motor is a load, not a source; its current keeps flowing from the same source and adds to the drop across every impedance the two motors share. The one way the first motor truly helps is mechanical: when both motors drive a single shaft, the first accelerates the machine so the second connects at part speed instead of standstill, which lowers its starting current. That is a shaft arrangement, not an electrical effect.

How many iterations does the voltage correction take?

Two passes settle it in almost every case. The first pass assumes rated voltage at the starting motor's terminals; the second scales the locked-rotor current by the terminal-voltage ratio the first pass produced. In the worked example the dip moved from 36.9 V to 33.9 V, and a third pass shifts it less than half a volt. Stop when the dip changes by under one percent and take that number to the torque and limit checks.

Why did the second start measure less current than the first?

Three usual reasons: the bus was already depressed by the running motor, so the second motor saw less voltage and drew proportionally less locked-rotor current; the two motors share a shaft and the second connected at speed; or the starters differ in setting or condition. Lower current alone is not an improvement, because torque fell with the square of that lower voltage, so compare acceleration time against the first start before calling the second start better.

What changes when the source is a generator?

Replace the transformer impedance with the generator's transient reactance from its data sheet for the acceleration period, and credit the excitation system only for the boost it is documented to deliver and how quickly it delivers it. Subtransient reactance shapes only the first few cycles. A sagging frequency is a separate problem the voltage arithmetic cannot see: if frequency drops well below rated during the start, motor torque and the voltage-zone tolerance both move against you.

Can the two motor currents simply be added together?

Add them as phasors, not magnitudes. Both lag, but at very different angles: locked-rotor current at a power factor near 0.35, the running motor near 0.85, so the phasor sum lands below the arithmetic sum. In the first pass of the worked example, 810 A plus 110 A is 920 A arithmetically but 899.7 A as a phasor sum, about 2 percent less. Straight addition overstates the dip.

Keep reading

  • How-to

    Motor starting voltage dip calculation on an 11 kV bus

    A starting medium-voltage motor dips the bus in proportion to its locked-rotor kVA against the source's short-circuit strength. Screen it as dip ≈ 100 × S_start/S_sc at the point of common coupling, then refine with ΔV = I_start(R cosφ + X sinφ) per phase. In the worked 11 kV, 1.5 MVA chiller example a direct-on-line start gives 3.6% at the PCC and 4.0% at the plant bus, failing a 3% limit; a 65% tap autotransformer or a soft starter limited to 3× rated current holds both points under 2%.

    Motors and motor starters

  • Explainer

    Effect of closing the bus tie on motor starting

    No. With the tie open, the motor on one bus sees only that bus's incomer, so energizing the second incomer changes nothing in its circuit; closing the tie while the motor's own incomer stays closed changes nothing either. The tie only eases a start when it actually parallels two live sources onto the motor bus, roughly halving the source impedance — at the cost of higher fault current.

    Motors and motor starters

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters