Explainer

Effect of closing the bus tie on motor starting

Motors and motor starters Published 8 min read

Short answer

No. With the tie open, the motor on one bus sees only that bus's incomer, so energizing the second incomer changes nothing in its circuit; closing the tie while the motor's own incomer stays closed changes nothing either. The tie only eases a start when it actually parallels two live sources onto the motor bus, roughly halving the source impedance — at the cost of higher fault current.

On this page
  1. Does closing the bus tie make motor starting easier?
  2. What does the motor actually see when it starts?
  3. When does closing the tie put the motor behind the other bus's load?
  4. How much starting torque does a voltage dip cost?
  5. Does paralleling both sources really help a hard start?
  6. What has to be checked before paralleling the two sources?
  7. Which incomer should feed the motor bus when the tie is open?
  8. How do I put numbers on my own lineup?
  9. Questions asked

No — and the argument settles on one fact: a starting motor sees the impedance of everything connected to its bus, not the count of closed breakers in the lineup. In a secondary-selective arrangement with the tie open, the motor on one bus is fed through that bus's incomer alone; the other energized incomer sits behind an open tie and is electrically not there. Close the tie while the motor's own incomer stays closed and its circuit is still unchanged — the tie merely back-feeds the other section. One lineup change genuinely helps: both mains and the tie closed, putting two live sources in parallel on the motor bus and roughly halving the source impedance. That one comes with fault-current and circulating-current checks attached, covered below with numbers.

Does closing the bus tie make motor starting easier? #

No. With the tie open, the motor sees only its own incomer's impedance, and closing the tie while that incomer stays closed leaves the motor's circuit unchanged; the tie becomes an improvement only when it puts two live sources in parallel on the motor bus.

The two lineups in the argument are not two source conditions — they are one source condition with a different number of closed breakers. "Both incomers connected, tie open" means each bus has its own supply and the two buses are separate nodes. "One incomer connected, tie closed" means the motor's bus is still supplied by its own incomer, with the tie back-feeding the section that lost its incomer. In both, the path from source to motor terminals is the same, so the dip, the current and the accelerating torque are the same. Your colleague's conclusion — the impedance is unchanged — is the right one for the lineup as described.

What does the motor actually see when it starts? #

The motor sees one series path: upstream source impedance at the main switchgear (the grid feed and the synchronized generators), the transformer and feeder down to its bus, the bus itself, and the motor cable.

An open tie is an open switch: no current crosses it, so whatever is energized on the far side contributes nothing to the motor's circuit and nothing to its dip. What does contribute is the strength of the source at the far end of the motor's own path — and the load already running on that path when the start begins. Breaker count never enters the calculation; the connected network does.

When does closing the tie put the motor behind the other bus's load? #

When the incomer that opens is the motor's own, the motor is then fed through the tie from the other bus — that adds tie and bus-run impedance to its path and puts both sections' running load on the one source that is left.

That is the one tie-closed arrangement that changes the motor's supply path, and it changes it for the worse twice over. The tie and cross-bus run add impedance, which deepens the dip slightly at the motor. The bigger cost is loading: the single remaining source now carries the combined pre-start load of both sections, so the voltage is already pulled down before the locked-rotor current arrives. Lineups designed to run with the tie normally closed — one main open — live in this state, and every large motor started in that mode starts against the combined load. Of the arrangements compared here, this is the hardest start.

How much starting torque does a voltage dip cost? #

Induction-motor torque tracks the square of the applied voltage, so 90% voltage at the terminals leaves 0.90² — 81% of the starting torque the motor would deliver at full voltage.

The exponent is what makes a modest dip expensive. Accelerating torque is motor torque minus load torque, and on a loaded start that margin can be a small fraction of locked-rotor torque; losing 19% of motor torque at 90% voltage can consume most of the margin. The motor then accelerates slowly or stalls, and a long acceleration keeps roughly six-times current flowing through the same impedance, holding the bus down longer and heating the machine. The square law is an approximation across the accelerating region of a standard induction machine; for a real decision, use the motor and load torque-speed curves.

Does paralleling both sources really help a hard start? #

Yes, and it is the only lineup change that does: closing both mains and the tie puts the two supply legs in parallel, and with two identical, independent legs the effective source impedance halves, cutting the dip roughly in half.

Worked example with stated inputs. Motor: 1000 HP, 4.16 kV, 130 A nameplate full-load current, locked-rotor current taken at 6 × FLA = 780 A. Starting kVA = 780 A × 4.16 kV × √3 ≈ 5.6 MVA. The system study gives 60 MVA short-circuit capacity at the motor bus on its own incomer. With pre-start voltage at 1.0 pu on a mostly reactive source, the bus voltage during the start follows V = V_pre × SC / (SC + LR_kVA):

  • Tie open, motor on its own incomer — one incomer energized or both, the network to the motor is the same: V = 60 / (60 + 5.6) = 60 / 65.6 = 0.915 pu. The bus dips 8.5% and torque falls to 0.915² = 0.837, or 84% of the starting torque at full voltage.
  • Motor fed through the tie, 55 MVA on that path: V = 55 / 60.6 = 0.908 pu. Dip 9.2%, torque 82%.
  • Both mains and tie closed, two identical legs paralleled, SC = 120 MVA: V = 120 / 125.6 = 0.955 pu. Dip 4.5%, torque 0.955² = 0.913, or 91% — about 9% more accelerating torque than the tie-open case (0.913 / 0.837 = 1.09).

These are estimates from the stated inputs, to be verified against the governing study and the equipment documentation; the IEEE 3002 series of recommended practices for industrial power systems covers how formal motor-starting studies are run. The decision from the numbers: paralleling is the only lineup change that moves the dip materially.

What has to be checked before paralleling the two sources? #

Three things: fault duty, circulating current, and the interlock scheme — paralleling two identical legs roughly doubles the available fault current at the bus, and every breaker and bus section in the parallel path must be rated for it.

  • Interrupting ratings and bus bracing: compare each breaker's interrupting rating and the switchgear's short-circuit rating with the paralleled available fault current from the study, not the open-tie figure.
  • Circulating current: if the two incomers come from one synchronized system — generators running in parallel with the grid — closing the secondary tie parallels two branches of one system, with no synchronizing operation involved. Current still circulates between legs when the transformers sit on different taps or have different impedances or X/R ratios, so check the resulting loading. If any operating mode can leave the two incomers on separate systems, the tie closure becomes a synchronizing operation and needs check-sync relaying.
  • Interlocks: secondary-selective lineups are commonly interlocked so the tie cannot close with both mains closed, because avoiding that parallel is the point of the arrangement. Never defeat an interlock to force a start.

NFPA 70E, 2024 edition, which covers electrical safety-related work practices, treats switching energized equipment like these breakers as work on energized systems: qualified persons, the documented procedure, and the protective equipment that procedure calls for. Confirm the requirements with the local authority having jurisdiction and the equipment documentation.

Which incomer should feed the motor bus when the tie is open? #

The stiffer one. With the tie open, the motor bus inherits the strength of whichever upstream path feeds it, so put the large motors on the section fed from the bus where the grid and the generators run in parallel, not the section behind the weaker path.

Extend the example: if the grid-plus-generation side raises the short-circuit capacity at the motor bus from 60 MVA to 80 MVA, V = 80 / (80 + 5.6) = 80 / 85.6 = 0.935 pu. Dip 6.5% instead of 8.5%; torque 0.935² = 0.874, or 87% instead of 84%. That gain comes from choosing the stronger incomer — the same open tie, the same breakers, a different bus. It is the lineup decision that actually moves the number.

How do I put numbers on my own lineup? #

Take the short-circuit capacity at the motor bus for each lineup from your system study, compute locked-rotor kVA from the nameplate current, and apply V = V_pre × SC / (SC + LR_kVA) — the standard quick estimate behind every starting-voltage check.

The arithmetic is the one used in estimating voltage sag from motor inrush current, and the bus-side version is worked through in motor starting voltage dip calculation on an 11 kV bus.

Lineup Dip at the motor bus (example) Starting torque Decision
Tie open, motor on its own incomer; second incomer open or closed 8.5% 84% Baseline. Energizing the second incomer buys nothing.
Tie open, motor on the stronger upstream bus 6.5% 87% The switching decision that helps; use it for the hard starts.
One incomer closed, tie closed, motor on the fed bus 8.5% 84% Same motor dip; the source carries both sections, so less margin left.
One incomer closed, tie closed, motor behind the tie 9.2% 82% Hardest start of the four; avoid it for large motors.
Both mains and tie closed (paralleled) 4.5% 91% Easiest start; use only after the fault-duty and circulating-current checks pass.

If the motor still will not accelerate in the best lineup available, the fix is on the current side — reduced-voltage starting or a drive — or in stiffening the supply itself. More breaker switching will not move the number.

Questions asked

If both incomers come from the same upstream bus, does closing the tie still halve the impedance?

No. The two transformer and feeder legs parallel, but the shared upstream impedance stays in series with that pair, so the total drops by less than half. The stiffer the shared source, the smaller the gain from closing the tie.

How does generator supply change the dip during a start?

A steady-state impedance calculation assumes the source regulates instantly. On a generator bus, the excitation system needs cycles to respond, so the first cycles of a start can dip deeper than the calculation shows. Depth moves with regulator response and pre-start loading, so keep extra margin on generator-fed starts.

What should be measured to confirm which lineup starts the motor better?

Record motor-terminal voltage rather than bus voltage alone, plus motor current and acceleration time through the whole start, the closed-incomer and tie states, and the loads already running. Keep the motor, load and starting method identical between tests, and only measure on lineups the switching procedure permits.

Does a soft starter fix a hard start without changing the lineup?

Usually, yes. A soft starter or a drive cuts the current drawn from the bus, so the dip shrinks whichever incomer feeds the motor. When the source is the limit and switching options are exhausted, reducing starting current is the direct fix — verify the load still accelerates on the reduced torque curve.

Keep reading

  • How-to

    Motor starting voltage dip calculation on an 11 kV bus

    A starting medium-voltage motor dips the bus in proportion to its locked-rotor kVA against the source's short-circuit strength. Screen it as dip ≈ 100 × S_start/S_sc at the point of common coupling, then refine with ΔV = I_start(R cosφ + X sinφ) per phase. In the worked 11 kV, 1.5 MVA chiller example a direct-on-line start gives 3.6% at the PCC and 4.0% at the plant bus, failing a 3% limit; a 65% tap autotransformer or a soft starter limited to 3× rated current holds both points under 2%.

    Motors and motor starters

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Troubleshooting

    Fixing AC contactor chatter on a loaded 80 HP motor start

    Chatter with the motor connected but a clean pull-in with the motor disconnected is the supply sagging under locked-rotor current; the 750 VA and external-outlet tests already cleared the control transformer. At 6x the 81 A label the start draws about 486 A on a 271 A transformer, so limit the start to roughly 270 A with a soft starter and verify the coil holds above 102 V.