Fixing AC contactor chatter on a loaded 80 HP motor start

Motors and motor starters Published 7 min read

Short answer

Chatter with the motor connected but a clean pull-in with the motor disconnected is the supply sagging under locked-rotor current; the 750 VA and external-outlet tests already cleared the control transformer. At 6x the 81 A label the start draws about 486 A on a 271 A transformer, so limit the start to roughly 270 A with a soft starter and verify the coil holds above 102 V.

On this page
  1. What the evidence already rules out
  2. The coil numbers that decide the case
  3. Worked example: the start against the 225 kVA bank
  4. Capturing the event once, correctly
  5. Decision table
  6. The fix for this installation
  7. Installation findings to close out
  8. Questions asked

Chatter that appears only with the motor connected is the supply sagging under locked-rotor current, and the tests already run clear the control transformer: the starter pulls in cleanly with the motor disconnected, and the chatter survived both a 750 VA control transformer and a 124 V feed taken from a building outlet. The 120 V coil is falling through its pickup floor while about 486 A of starting current loads a bank rated 271 A on that side. Stop repeated start attempts now and disable the compressor's automatic restart while you diagnose: every chatter cycle interrupts locked-rotor current and destroys contact material. The fix is reducing the starting current, not swapping control transformers.

What the evidence already rules out #

Three substitution tests, each decisive on its own:

  • With the motor disconnected, the IEC contactor pulls in and holds: the coil, armature and control wiring can seal with no power-side load.
  • A 750 VA control transformer changed nothing: control capacity was more than doubled and the chatter was identical.
  • A 124 V outlet away from the machine changed nothing: the control source is not the limiting impedance, because that outlet sags with everything else on the service.
  • Building lights flicker during attempts: the dip originates on the 208 V service, upstream of the 225 kVA step-up bank.

The contactor is releasing as the bus collapses under starting current and reclosing as it recovers. Each release also re-applies locked-rotor current to a motor that has not accelerated, the repeated-stall condition that motor protection against locked-rotor failures is designed to catch.

The coil numbers that decide the case #

The coil is marked 95–180 VAC; confirm in the starter documentation whether that range is pickup, operation, or an electronic coil interface. Listing practice, as Eaton's engineering reference summarizes it, requires AC contactor coils to pick up at 85% of rated voltage and permits dropout anywhere from 20% to 75%. For a 120 V coil the pickup floor is 0.85 × 120 V = 102 V, with hold possible between 24 V and 90 V once sealed — but an armature that never seats never reaches that sealed state.

The handheld multimeter read 100–105 V during attempted pickup. That reading decides nothing in either direction: it updates a few times a second and averages, while the troughs that release the armature last milliseconds. It also shows a coil drawing open-gap pickup inrush through the control wiring, not the true minimum at the terminals.

Decision rule: capture the real minimum directly across the coil terminals during one clean start attempt. At or above 102 V with the armature still releasing, the fault is the coil identity or contactor mechanics. Below 102 V, the sag is confirmed and the fix belongs on the power side.

Worked example: the start against the 225 kVA bank #

Inputs, all from this installation:

  • 225 kVA, three-phase, 208:480 V step-up transformer
  • Motor package label: 81 A (80 HP)
  • Locked-rotor estimate: 6 × full-load current, a mid-range design value; the nameplate code letter tightens it if recorded
  • Impedance carried as an assumed 5% until the nameplate is read

The arithmetic, with units:

  • Rated secondary current: 225,000 VA ÷ (√3 × 480 V) = 225,000 ÷ 831.4 = 271 A
  • Rated primary current: 225,000 VA ÷ (√3 × 208 V) = 225,000 ÷ 360.3 = 625 A
  • Locked-rotor current: 6 × 81 A = 486 A, which is 486 ÷ 271 = 1.8 times the bank's rating
  • Reflected to 208 V: 486 A × 480 ÷ 208 = 1,121 A, about 560 A through each of two parallel 200 A breakers if they share equally

At the assumed 5% impedance the bank alone drops 1.8 × 5% ≈ 9% during the start, before the parallel 250 kcmil run and the service impedance add theirs. The measured control dip — 130 V at rest to 105 V during the attempt, about 19% — fits that chain. This is an estimate from stated inputs, to be checked against the nameplate values and the governing code. The same source-impedance method at distribution voltage is worked through in motor starting voltage dip calculation on an 11 kV bus.

Decision: the bank is generous for running, 271 A of rating against 81 A of load, and cannot deliver an across-the-line start without 1.8× rated current. The sag is structural, and no control-side component removes it.

Capturing the event once, correctly #

Open panels and make connections only with the equipment de-energized, locked out and verified dead. Live recording inside an energized enclosure is energized work under NFPA 70E, 2024 edition, which governs safe work practices and protective equipment; do it only under the site's energized-work procedure with a meter and probes rated for the panel.

Then, in one captured event, record:

  1. Voltage directly across the coil terminals, at 1 ms resolution or better.
  2. The control transformer secondary voltage in the same event, for comparison.
  3. All three high-side line-to-line voltage pairs at the starter line side.
  4. The 208 V service voltage during the same start.
  5. Motor current with an instrument that captures the inrush, noting whether it reports peak or RMS.
  6. Voltage across each commanded-closed series contact — pressure switch, interlocks, overload contact — where voltage across a closed device marks a control-path drop.

Decision table #

What the recording shows Fault direction Deciding check
Command stays solid while coil voltage and the high-side bus fall together as current rises Supply sag under starting current Compare the 208 V service and high-side traces against the current trace
Command drops before the coil voltage falls Control path: pressure switch, interlock, output Voltage across each series device during the event
High-side bus holds while coil-terminal voltage falls below the secondary reading Control transformer or control wiring impedance Secondary reading versus coil-terminal reading
Coil voltage within limits, armature still releases Coil mismatch, worn poles, mechanical bind Verify the coil part number and inspect the contactor

The fix for this installation #

A soft starter or drive limiting the start to about 270 A on the high side. The number is derived, not chosen: the bank's 625 A primary rating reflects to 625 × 208 ÷ 480 = 271 A at the motor voltage, and 271 ÷ 81 = 3.3 times full-load current. At that limit the transformer carries about rated current during the start instead of 1.8× it, and its internal drop falls from about 9% to about 5% at the assumed impedance, with the service impedance unloading proportionally.

Current limiting trades torque: at 3.3× instead of 6×, available torque is roughly (3.3 ÷ 6)² ≈ 30% of across-the-line, which an unloaded compressor start normally accelerates on. If it stalls, raise the limit in steps and re-record the coil minimum each time. The same current-limit arithmetic on another size limit is worked through in converting a 350 kVA soft start limit to starting current.

Ranked alternatives:

  • DC coil with rectifier: listing practice allows DC coils to pick up at 80% of rated voltage and drop out between 10% and 75%, so they ride dips an AC coil releases on. It stops the chatter but leaves the motor accelerating on a sagging service, so accept it only after measuring the sag and confirming acceleration.
  • Control power from a small UPS on the control transformer primary: stops the chatter symptom, changes nothing for the motor.
  • A bigger transformer: making the start equal rated current takes √3 × 480 V × 486 A ≈ 404 kVA, doubling the bank to fix a start that lasts seconds. Not the answer.

Installation findings to close out #

  • The 60 A fuses in the machine disconnect sit below the package's 81 A label and have survived only because chatter never lets current persist. Record the fuse class and check it against the compressor documentation's specified protection; NFPA 70 (National Electrical Code), 2023 edition, Article 430 covers motor branch-circuit conductor and short-circuit/ground-fault protection, and the arrangement should be confirmed with the documentation and the authority having jurisdiction.
  • Two 200 A breakers in parallel feeding parallel 250 kcmil conductors: confirm the paralleling is a listed, permitted arrangement, because about 1,121 A of starting current, roughly 560 A per breaker, flows through it on every across-the-line attempt.
  • The secondary tapped to 497 V: re-tap toward nominal once the start is fixed. Running above nameplate raises motor running current, covered in why motor current rises when voltage exceeds nameplate.

Questions asked

Why does the contactor pull in fine with the motor disconnected but chatter when it is connected?

Disconnected, there is no power-side load, so the service stays up and the coil sees full voltage. Connected, the draw jumps to roughly 486 A, the 208 V service sags, and the coil voltage falls through its pickup floor, releasing the armature; the bus recovers, the contactor recloses, and the cycle repeats. That load dependence is the signature of supply sag, not a defective coil.

Would a DC coil and rectifier stop the chatter?

Often yes, and it is the cheaper retrofit when a soft starter cannot be added, because DC coils ride dips an AC coil releases on. The supply sag is still there, so confirm the motor still accelerates and that the starting current still suits the transformer and feeder.

The meter read 105 V and the coil is marked 95 V, so why is voltage still the problem?

Two reasons. A handheld multimeter updates a few times a second and averages, while the troughs that drop the armature last milliseconds, so the displayed 105 V is not the minimum the coil actually saw. And the 85% listing pickup floor for a 120 V coil is 102 V, which the reading is barely above even before those unseen troughs are considered.

How much damage can chatter do if we keep trying to start?

Every chatter cycle closes on and interrupts locked-rotor current, which transfers contact material, and holds the motor at stall current with no cooling airflow. Inspect the main contacts for erosion or welding before any loaded retest, replace a pitted contact set, and keep the compressor's automatic restart disabled until the real fix is installed.

What soft-starter current limit should we set on this compressor?

Start near 270 A, about 3.3 times the 81 A label, which reflects to the 625 A primary rating of the 225 kVA bank. If the motor stalls unloaded, raise the limit in steps and re-record the coil-terminal minimum each time; the right limit is the one that keeps that minimum above 102 V while the motor still accelerates.

Keep reading

  • Explainer

    Converting a 350 kVA soft start limit to starting current

    A 350 kVA soft start limit is about 421 A of line current at 480 V: divide 350,000 VA by √3 × 480 V. The figure is apparent power, so no power factor enters the conversion, and it carries no duration — that comes from the torque-speed margin. The 12.5 kV fuse is a coordination problem; motor protection belongs at 480 V.

    Motors and motor starters

  • Selection guide

    Specifying soft starters for high-inertia blowers without curves

    Torque, not kilowatts, decides the start: at a 400% current limit on a motor with 800% locked-rotor current, torque falls to about 25% of DOL and a 15 s blower start stretches to four times that or stalls. Close the dampers, hold the limit near the square root of the load-torque fraction times the measured inrush (about 500% of full-load current here), buy duty to cover it, or specify a drive.

    Motors and motor starters

  • How-to

    Motor starting voltage dip calculation on an 11 kV bus

    A starting medium-voltage motor dips the bus in proportion to its locked-rotor kVA against the source's short-circuit strength. Screen it as dip ≈ 100 × S_start/S_sc at the point of common coupling, then refine with ΔV = I_start(R cosφ + X sinφ) per phase. In the worked 11 kV, 1.5 MVA chiller example a direct-on-line start gives 3.6% at the PCC and 4.0% at the plant bus, failing a 3% limit; a 65% tap autotransformer or a soft starter limited to 3× rated current holds both points under 2%.