Selection guide
Specifying soft starters for high-inertia blowers without curves
Short answer
Torque, not kilowatts, decides the start: at a 400% current limit on a motor with 800% locked-rotor current, torque falls to about 25% of DOL and a 15 s blower start stretches to four times that or stalls. Close the dampers, hold the limit near the square root of the load-torque fraction times the measured inrush (about 500% of full-load current here), buy duty to cover it, or specify a drive.
On this page
- Why can't I size the soft starter from motor kilowatts?
- What should I measure on the existing direct-on-line starts?
- How do I turn a current limit into voltage and torque?
- How long will the blower take to start at a reduced current limit?
- Will the motor stall before it reaches full speed?
- What starter frame and duty rating cover the computed start?
- How do I commission the start when no curves exist?
- When should I specify a drive instead of a soft starter?
- Questions asked
Specify on torque, not kilowatts. On a motor whose measured direct-on-line inrush is 800% of full-load current, a 400% current limit holds the voltage near half and the torque near 25% of DOL, so a 15 s blower start stretches to four times that or longer and can settle short of full speed. Close the dampers before every start, set the current limit from the square root of the blower's load-torque fraction times the measured inrush — about 500% of full-load current in the worked example — and buy a starter whose published duty rating covers that start with margin. Where the utility's written cap falls below that number, specify a drive instead.
Why can't I size the soft starter from motor kilowatts? #
Because kilowatts say nothing about torque: at a 400% current limit on a motor that draws 800% locked-rotor current, applied voltage falls to about half and developed torque to about 25% of direct-on-line, and torque is what decides whether the blower accelerates.
Kilowatts, with voltage and full-load current, fix the starter's continuous frame and the bypass contactor. The start itself is decided by the torque difference T_motor(n) − T_load(n) acting on the rotating inertia. The governing relation is t = J × Δω / T_avg (J in kg·m², ω in rad/s, T in N·m), or t = WK² × ΔN / (308 × T_avg) in lb·ft², rpm and lb·ft. A centrifugal blower is the case this formula bites: low bearing friction, large reflected inertia, and a load torque that climbs with speed on top of the inertia. Calling it high inertia is correct, and the starter is sized on load torque and acceleration together, never on power alone.
A soft starter reduces voltage at supply frequency only, and induction-motor torque at a given speed varies with the square of the applied voltage. That one proportionality produces every number below.
What should I measure on the existing direct-on-line starts? #
Capture one instrumented DOL start per motor: locked-rotor current, time from contactor close to full speed, and voltage dip at the supply point the utility cares about — those three numbers replace the missing curves for every calculation in this selection.
Record motor current and voltage against time, with the voltage channel at the agreed supply point and a second channel at the motor terminals where possible; a terminal-only reading cannot separate local feeder drop from disturbance on the wider supply. The current trace gives locked-rotor current at the actual applied voltage — if the bus sagged, scale it as I_LRC ≈ I_measured × V_nominal / V_measured — but it gives no torque information. Locked-rotor torque is a separate quantity that no current measurement produces.
NFPA 70E, 2024 edition, sets out electrical safe work practices: put the starter cubicle in an electrically safe state — de-energized, locked out, tested for absence of voltage — before fitting recording instruments, then restore power for the recorded start, and use meters rated for the measurement location. Confirm local enforcement and the equipment documentation with the authority having jurisdiction. Where the upstream impedance is known rather than measured, the dip can be calculated instead; the method in motor starting voltage dip calculation on an 11 kV bus works the same way at low voltage.
How do I turn a current limit into voltage and torque? #
Divide the current limit by the measured locked-rotor current to get the voltage ratio, then square it: torque at any speed scales with the square of that ratio, so a 400% limit against 800% inrush gives 0.5² = 25% of DOL torque.
Worked example, all inputs stated (hypothetical but realistic for this class): 335 kW, 400 V, 50 Hz, 2-pole blower motor; nameplate full-load current 585 A; measured DOL inrush 4680 A (= 8.0 × 585 A); measured DOL acceleration 15 s free-venting; measured 8% dip at the supply point.
Convert any percentage limit to amps with I_limit = %/100 × FLA: 400% × 585 A = 2340 A. The voltage ratio is u = I_limit / I_LRC = 2340 / 4680 = 0.50, and the torque ratio is u² = 0.25. The nameplate amps are the base — motor kW alone cannot give them, because voltage, efficiency and power factor all sit in between. When the supply authority states its limit in kVA instead of amps, convert to current at the system voltage first; the steps are in converting a 350 kVA soft-start limit to starting current.
How long will the blower take to start at a reduced current limit? #
At least the DOL time divided by the squared voltage ratio: at half voltage that is four times, so the 15 s DOL start becomes a 60 s floor — and the blower's load torque stretches the real start beyond that floor.
The 1/u² rule is the zero-load-torque special case of the acceleration formula, and the unknown inertia cancels in the ratio, which is why it works with no mechanical data at all. It is a floor, not an estimate: a blower's aerodynamic torque rises roughly with speed squared, so it eats the accelerating torque just where speed is building, and the starter raises voltage through the start to hold the current limit, making locked rotor — your u² point — the worst spot on the curve.
Heating does not improve either. Line-side I² × t at 2340 A for 60 s is 5.48 × 10⁶ A² × 60 s = 3.29 × 10⁸ A²·s, exactly the (4680 A)² × 15 s the DOL start dissipates. Limiting current does not make the start easier on the motor; it makes it longer, and against load torque it makes it hotter.
Will the motor stall before it reaches full speed? #
It will against an open air path: a free-venting blower needs roughly 100% of full-load torque near full speed, and no reduced-voltage start delivers that, so the dampers or shutters must close the air path before every start.
Without curves, run the check at the full-speed end. At rated slip the motor develops full-load torque by definition, so the torque available there under a limit is u² × 1.0, and the start is only guaranteed when u² ≥ L, the blower's load-torque fraction at full speed. Closed dampers put a centrifugal blower near L = 0.40 of full-load torque; free-venting is L ≈ 1.0, which forces u = 1.0 — no reduction at all. For the example: u_min = √0.40 = 0.632, so I_limit = 0.632 × 4680 A ≈ 2960 A, which is 2960 / 585 = 506% of nameplate.
Field experience on similar fans often finishes below this number, because the current limiter releases near full speed and the voltage reaches 100%. Without the motor's current-versus-speed curve you cannot verify that, so hold the conservative limit for the buying decision and let commissioning find the working value. Get the closed-damper figure from the blower manufacturer; 0.40 is a typical starting point, not a property of your machine. Decision for this class: a 300-400% specification is not achievable with a soft starter — plan for at least 506% capability with dampers closed.
What starter frame and duty rating cover the computed start? #
Pick the frame whose published duty pair covers the computed start with margin — for the worked example that means covering roughly 40 s at 500-600% of full-load current, which a typical 30 s at 600% duty pair does not quite reach.
Duty ratings are current-and-time pairs; a common heavy-duty pair in this class is 30 s at 600% of full-load current. Thermal capability scales roughly with current squared times time: 30 s × 6.0² = 1080 %²·s, which at 500% (25 %²) supports about 1080 / 25 = 43 s — enough for the 37.5 s floor at the 506% limit with nothing left for the longer real start. Take 1.5 times the computed floor as the selection number (an engineering margin, not a standard value): 57 s at 506%, call it 60 s at 500%.
| Current limit | Line current | Scaled torque | Start-time floor | Duty to select (1.5× floor) | Verdict, dampers closed (L = 0.40) |
|---|---|---|---|---|---|
| 300% FLA | 1755 A | 14% of DOL | 107 s | 160 s | No: 14% torque cannot clear a 40% load |
| 400% FLA | 2340 A | 25% of DOL | 60 s | 90 s | No: stalls on the guaranteed curve, exceeds common duty |
| 506% FLA | 2960 A | 40% of DOL | 38 s | 57 s | Minimum: clears the load exactly, zero margin |
| 550% FLA | 3220 A | 47% of DOL | 32 s | 48 s | Select here or above |
| 600% FLA | 3510 A | 56% of DOL | 27 s | 40 s | Best torque margin, highest supply dip |
A larger frame adds semiconductor duty — time, repetition, cooling — and never motor torque: at the same current limit the same voltage appears at the motor terminals whatever the frame. Feed the starter's motor thermal model from the nameplate, and settle the protection question as covered in setting overload relays for high-inertia motor starts. Check the frame's starts-per-hour and consecutive-start limits against the process. All figures here are selection estimates; confirm the final choice against the starter's documentation and the governing supply rules.
How do I commission the start when no curves exist? #
Start at the computed minimum plus margin with dampers closed, and step the limit up in 25-50% of full-load current, watching current and speed: falling current means acceleration; current pinned at the limit while speed stops rising means an equilibrium crawl that will not finish.
- Prove the dampers closed, and interlock them so the starter refuses a start with the air path open.
- Enter the nameplate data into the starter's motor thermal model; set the current limit to 550% and the duty and acceleration envelope to the selected values.
- Perform the first recorded start: a healthy trace holds current at the limit while speed climbs, then current falls toward full-load as the blower reaches speed.
- If speed plateaus with current at the limit, raise the limit one step, let the starter and motor cool per the starts-per-hour rating, and repeat.
- Record the final limit, start time and dip at the supply point, and check the dip against the utility's written limit. Expect dip to scale with current through the fixed impedance: 8% × (6.0 / 8.0) = 6% at a 600% limit.
- Log winding or frame temperature after each trial; starts that get progressively slower across trials are a thermal warning, not a trend to accept.
When should I specify a drive instead of a soft starter? #
When the utility's written current limit sits below the computed minimum — below about 500% of full-load current in the worked example — or the blower must start free-venting, only a variable-frequency drive delivers the torque at a current the supply accepts.
A drive controls frequency as well as voltage, so it holds flux and produces accelerating torque near full-load current instead of locked-rotor multiples; the same inertia accelerates on a ramp with defined current and no equilibrium stall point. For the parameter-level setup on this exact load class, see configuring VFDs for high-inertia squirrel cage blowers. Decision for the example plant: dampers closed, capability to 550-600% of full-load current, duty of about 60 s at 500%, thermal model from the nameplate, commissioned by the steps above — and if the authority holds the cap at 400%, stop spending on soft starters and move the budget to drives.
Questions asked
Can one soft starter handle several blowers?
Yes, with a bypass contactor per motor: the starter accelerates one blower, the bypass closes around it, and the starter is free for the next. Every start draws down the same semiconductor thermal budget, so the duty rating must cover the starts per hour multiplied by their duration, and interlocks must keep two motors off the starter at once. Sequential starts also spread the supply dips apart.
How do I estimate locked-rotor current when no DOL trace exists?
Check the nameplate for a locked-rotor kVA code letter, which bounds inrush between two multiples of full-load current; older plates may carry none. Otherwise, induction machines of this class commonly draw six to eight times full-load current at locked rotor, and a two-pole machine sits toward the top of that band. Design on the high end until a real start is recorded.
Can I just extend the starter's acceleration-time setting?
That setting is a timer, not extra capability. Lengthening it lets the start run longer only if the frame's published duty covers the longer time at the limited current and the motor's thermal limit, modelled in the starter's motor protection, still has margin. Extending the timer past both limits trades a trip for cooked semiconductors and a hot motor.
How many starts per hour should the design allow for?
Use the process's realistic worst case, not its average: the binding event is usually a tripped blower that must restart immediately, and a hot motor has less thermal margin than the cold-start figures suggest. Set the starter's starts-per-hour limit to force spacing between attempts, and count every commissioning trial as one of those starts.