Troubleshooting
Why a VFD DC bus overvoltage fault appears at random
Short answer
One ~670 V DC sample sitting between steady ~570 V readings in a 400 V drive's fault log is the fingerprint of a regenerative spike lasting a few milliseconds. An overhauling load through a high-ratio gearbox pumps energy back faster than V/Hz control and the brake chopper can absorb it. Move the drive to sensorless vector control, run auto-tune, lengthen the decel ramp and raise the regen power limit.
On this page
- What does the DC bus voltage normally read on a 400 V VFD?
- Why does one 670 V sample between 570 V readings mean a spike?
- Why can't the HMI log or a multimeter catch the excursion?
- What is pumping energy back into the drive?
- Why doesn't the brake resistor stop the bus from tripping?
- Could the fan drive sharing the supply be causing it?
- Which settings stop a random DC bus overvoltage fault?
- How do you prove the spike is gone?
- Questions asked
When a 400 V drive trips on DC bus overvoltage at random — during acceleration, at constant speed, mid-reversal — and its 250 ms fault log shows nothing but one 670 V sample between steady 570 V readings, trust the log: it is telling you the spike is real and shorter than the sampling. In the reported case behind this article, a 90 kW drive on a net-washing drum was being overhauled by its own load through a 240:1 gearbox, and V/Hz speed control was too slow to reject the pulse. The fix that cleared it was sensorless vector control with a proper auto-tune, a longer decel ramp and a higher regen power limit. Here is the voltage arithmetic, why the HMI and a multimeter both miss the event, and the settings to change in order.
What does the DC bus voltage normally read on a 400 V VFD? #
A 400 V three-phase drive rectifies the line to about 1.414 × 400 V = 566 V DC with no load, and healthy running readings sit between roughly 540 and 580 V DC, so the steady ~570 V samples in this log are normal.
The bus is the line-to-line peak held by the DC link capacitors, and it moves with the supply: a line running 5% low pulls the reading down by roughly the same 5%, so a slow morning supply shows up on the bus display without anything being wrong with the drive.
Trip logic is different from logging. An overvoltage fault means the bus crossed the drive's threshold once — the comparison is instantaneous, with no averaging window to smooth a spike over. For 400 V class drives the software trip value typically sits between about 780 and 820 V DC; treat 800 V DC as the working figure and read the drive's own trip value from its documentation before planning anything against it.
Why does one 670 V sample between 570 V readings mean a spike? #
A single ~670 V DC sample stranded between steady ~570 V readings is the log catching the tail of an excursion that peaked above the trip threshold and decayed back between two samples, which puts the whole event on a millisecond scale.
Read the drive's own fault history first, then work the timeline forwards. The pulse arrives, the bus climbs past the trip value within a few milliseconds, the drive declares the fault instantly and stops modulating, and the bus bleeds back down through the braking unit and the capacitors. The sampler fires somewhere in that decay and records 670 V — consistent with a bus settling back through the braking unit's regulation band — and every later sample reads normal again. Had the peak really been 670 V, a drive tripping near 800 V would never have tripped at all.
The single-sample pattern is the fingerprint. A sustained supply-side overvoltage shows several elevated samples in a row, not one. The erratic DC ripple warnings logged alongside point the same way: the bus was oscillating before the trip, which a per-revolution load disturbance produces and a steady supply fault does not. The reported case also saw the bus readout start stepping with every drum revolution a minute or two before each trip — the same class of symptom traced in why a drive-controlled motor runs unstably and how to trace it, and a strong hint the disturbance is mechanical.
Why can't the HMI log or a multimeter catch the excursion? #
An HMI polling at 4 Hz takes one sample every 250 ms, so an excursion that starts and ends within 5 ms fits inside the gap between two samples up to fifty times over, and a handheld multimeter averages the same way at a slower rate.
Put the numbers side by side. The samples sit 250 ms apart and the event lasts 2 to 5 ms, so the chance of the sampler landing inside any one excursion is 5 ms ÷ 250 ms = 0.02, about 2%. A log holding hundreds of clean readings and exactly one intermediate value is not a glitch; it is the expected statistical picture of a short spike plus one lucky catch.
The multimeter fails twice over. Across two input phases it reports an RMS line reading that updates a few times per second, while the disturbance lives on the DC link for single-digit milliseconds. The clean line reading at trip time is still worth having — it weighs against a line swell — but it cannot see this event.
What is pumping energy back into the drive? #
The pump is the load itself: as the drum contents bunch into one cohesive mass, the mass rides up the drum wall, loses grip and free-falls, and through the 240:1 gearbox each fall and slam reaches the motor shaft as a torque reversal playing out over 12 to 20 ms.
Follow one revolution of a clumped load:
- The mass rides up with the drum wall and adds torque the motor must carry.
- At a high point it loses grip and drops, and the load vanishes in an instant.
- It strikes the bottom of the drum, and for that moment the drum is driving the motor.
The last step is the one that trips drives. When the load drags the machine above its reference speed, slip goes negative and the motor becomes a generator: power flows from the shaft, through the inverter, onto the DC bus. The input rectifier is a one-way street, so that energy cannot return to the line — it charges the DC link capacitors until the braking unit or the trip deals with it. The rectifier, DC bus and inverter chain behind this is laid out in how a VFD's rectifier, DC bus and inverter stages work.
The gearbox hides the speed of it. At 50 Hz the drum turns at 50 ÷ 240 rev/s, a period of about 4.8 s, and a drum period in the 3 to 5 s range maps to 12 to 20 ms at the motor shaft — a slow, heavy swing at the drum arrives at the drive as a millisecond torque step.
Nothing electrical changed over the fault's first month. The nets did: loose material coalesced into one mass and turned a smooth torque into sign-changing impulses.
Why doesn't the brake resistor stop the bus from tripping? #
The brake resistor only helps if the chopper connects it before the bus passes the trip threshold; a pulse that arrives faster than the chopper's turn-on and current ramp lands in the DC link capacitors, which is exactly the millisecond event this log shows.
A braking unit turns on near its regulation band and then needs a few milliseconds to switch and build current in the resistor. Energy delivered faster than that has already reached the capacitors, which is why a generously sized, cool-running resistor says nothing about the peak.
Drives also cap the power they will command into the braking unit — the regen power limit. Power above that limit has nowhere to go but the DC link, whatever the resistor could theoretically take. An oversized resistor behind a conservative limit is a brake being starved of work, and the limit is the lever to move.
Worked example, with illustrative inputs; read the real capacitance and trip value from the drive's documentation:
- Raise a DC link from 570 V to an 800 V trip and you must add E = ½ × C × (Vtrip² - Vbus²), where C is the DC link capacitance. Take an illustrative 12 mF for a drive of this class: E = 0.5 × 0.012 F × (800² - 570²) V² = 0.006 × (640,000 - 324,900) J = 1,891 J, about 1.9 kJ.
- Delivered in 5 ms, that is 1,891 J ÷ 0.005 s = about 378 kW of instantaneous braking demand — far beyond the continuous duty a chopper of this size shunts, which is why the resistor stays merely warm.
- The mechanics supply it easily: a 200 kg clump falling 1 m releases 200 kg × 9.81 m/s² × 1 m = 1,962 J, about 2 kJ. One fall is one trip.
Could the fan drive sharing the supply be causing it? #
Treat the fan drive as a suspect only until you line the timestamps up: the logged single-sample signature is a DC-side regen event, and a multimeter held across two input phases at one trip read clean, which points away from a shared-supply cause.
Two drives on one feeder and one protective earth bar interact through the line impedance, not through each other's DC links; a small drive's switching dents the line a little but does not inject volts into a 90 kW DC link. The cheap test is already in the records: pair every trip timestamp with the cycle's fan-enable window. Trips spread across acceleration, reversal and steady running on both sides of that window — as the reported case shows — exclude the fan on the evidence.
Line-side causes are real and worth clearing properly: utility switching, power-factor correction capacitors and a loose or corroded line terminal all produce genuine overvoltage trips, usually as repeated elevated readings rather than one stray sample. Torque-check the drive's line terminals with the panel locked out, and watch whether anything else on the same feeder misbehaves at trip times. The line-side route to this fault — what it looks like when no motor is connected at all — is walked through in why an overvoltage fault can appear with no motor connected.
Which settings stop a random DC bus overvoltage fault? #
Switch the control mode from V/Hz to sensorless vector speed control, run the drive's auto-tune so the speed estimate is honest, lengthen the decel ramp, and raise the regen power limit until the oversized resistor actually carries the pulses.
Change them in this order, so each step's effect is attributable:
- Record the baseline: control mode, decel times, regen power limit, braking unit setpoint.
- Run the drive's auto-tune, or motor identification, exactly as its manual prescribes — it measures stator resistance, leakage inductance and magnetizing current, and sensorless vector control is only as good as the motor model underneath it.
- Switch the control mode to sensorless vector speed control. The speed loop then pulls a load step back within a few milliseconds instead of the tens to hundreds of milliseconds a V/Hz characteristic needs, trimming frequency before the bus has time to climb. This is the change that ended the trips in the reported case.
- Lengthen every decel ramp in the cycle. The inertia energy at each stop is fixed, and the peak braking power falls roughly in proportion to the ramp you give it, so doubling the ramp halves the peak. The same lever clears spikes elsewhere: it is how a spindle regeneration voltage spike was traced to a decel parameter and fixed.
- Raise the regen power limit within the braking resistor's documented thermal rating, so the oversized bank carries the pulses instead of watching the capacitors take them.
- If the drive offers a decel overvoltage or stall-at-limit function, switch it on — it extends the ramp automatically when the bus starts to rise.
After the control-mode change, the reported case's bus display stopped stepping with every drum rotation, and the trips stopped.
How do you prove the spike is gone? #
Confirm the fix by logging the DC bus at 10 ms or faster through the drive's communications port, or by a triggered capture on the bus itself, and require a full shift of running with no excursion above the mid-600 V range before calling it closed.
Three sources of fast data, in rising order of effort. First, the drive itself: many models keep a fast fault trace at trip time plus minimum and maximum bus registers since the last reset — check what the manual documents and read those counters after each test run. Second, communications logging at 10 ms or faster over the drive's fieldbus: for capture that runs unattended across whole shifts instead of waiting for trips, a fanless industrial mini pc logging the bus voltage from the drive's comms port keeps the continuous record a trip log never will. Third, a triggered oscilloscope with a differential probe rated above 1 kV DC, triggered a little below the drive's own trip value so it catches sub-trip steps too.
One safety note, because this is the step that puts hands near the bus: connecting anything across an energized DC link is energized electrical work. NFPA 70E, the 2024 edition, governs energized work and puts de-energizing, locking out and verifying absence of voltage ahead of any exposure — make your connections with the panel dead, wait the capacitor discharge interval the drive manual states, confirm with a meter rated for the voltage, and clear the details with your authority having jurisdiction.
Decision: the fix is proven when a full shift of fast logging shows the bus holding in its normal band with no per-revolution steps above the mid-600 V range. If steps remain but stay below the trip value, lengthen the decel further, raise the regen limit again, and log another shift.
Questions asked
Can aging DC link capacitors cause random overvoltage trips?
They can contribute. Aged capacitors lose capacitance, so the bus ripples more and absorbs a regen pulse with a higher peak, and many manufacturers publish a service life for the DC link that you can check against the drive's run hours. In the reported case the capacitors were a possible secondary contributor, not the driver, because the control-mode change ended the trips. If excursions return after the settings work, test or replace the DC link per the manufacturer's documentation.
Does a longer decel ramp fix every DC bus overvoltage trip?
No. A longer ramp addresses trips during commanded deceleration and reversal, where the drive must absorb the inertia you are asking it to slow. Trips at constant speed come from the load overhauling the motor, and the levers there are speed-loop stiffness and the regen power limit. The reported case had both trip types, so it needed the control-mode change as well as the ramp change.
Why does the brake resistor stay cold if the drive is regenerating hard?
Because the pulse is over before the chopper delivers much of it. The braking unit needs a few milliseconds to turn on and build current in the resistor, and energy arriving faster than that stays in the DC link capacitors. A cold resistor on an oversized bank is therefore the expected picture in this fault, not proof the braking circuit is dead. Check the resistor's ohmic value and its wiring with the drive locked out and verified de-energized.
How long should you wait before touching a drive's DC bus terminals?
Wait the discharge interval stated in the drive's installation manual for that frame size, then verify the bus with a meter rated for the voltage before any contact. Never treat a blank display or a stopped cooling fan as proof of discharge; a large DC link can hold a lethal charge with the drive switched off and nothing running.