Variable frequency drives Published 7 min read

Short answer

With the motor disconnected, no energy returns to the drive, so an overvoltage fault can only mean the DC link is being charged past its trip level from the line side. Measure all three line-to-line voltages: sustained high input, a capacitor-switching transient, or a failed sensing board are the remaining causes, in that order of testing.

On this page
  1. Why deceleration settings and braking resistors cannot fix it
  2. What the DC link reads when the motor is off
  3. The three causes that remain
  4. Work safely before the measurements
  5. The measurement sequence that decides it
  6. Worked example: 236 V feeder, trips at 07:02 and 15:01
  7. The fix for each finding
  8. Questions asked

A drive that reports an overvoltage fault with the motor disconnected has eliminated the usual suspect in one move: nothing is spinning, so nothing is regenerating. On the Mitsubishi FR-F720 the display reads E0u3, which the manual describes as a protective stop when regenerative energy pushes the main-circuit DC voltage to its specified level, with a surge from the power supply system listed as another trigger. With the motor leads off, only the supply-side triggers remain. Measure, in this order: the three line-to-line voltages, the DC-link voltage against the 1.35 × line rule, and the trip timestamps against upstream capacitor switching. Each result commits you to one fix.

Why deceleration settings and braking resistors cannot fix it #

Lengthening the deceleration ramp and fitting a braking resistor both act on energy that a connected, spinning load returns through the inverter. With the motor disconnected, that energy is zero, so a longer ramp, a shorter ramp, and a braking unit are all adjustments to a quantity that does not exist. Every reset-and-retry cycle also overwrites the timing evidence in the fault history, which is the one clue that separates a supply problem from a drive problem.

A braking resistor is not a clamp you can wire across the DC link, either. Inside the drive, or in an external braking unit, a transistor switches the resistor in only above a set DC threshold. A resistor permanently connected across the link draws continuous current it was never sized for and burns. Braking becomes a real design problem only when a motor is connected and overhauls the drive, which is the case why a motor-side braking resistor works on a PM servo covers, and its placement is decided by the drive's braking-unit terminals, never improvised.

The input stage is a six-pulse rectifier charging a capacitor bank. At no load the capacitors charge to the line-to-line peaks and hold most of the way between them:

  • Average DC-link voltage ≈ 1.35 × line-to-line RMS voltage
  • Peak DC-link voltage ≈ √2 × line-to-line RMS voltage
Line-to-line supply Average DC link (1.35 ×) Peak (√2 ×)
200 V 270 V 283 V
220 V 297 V 311 V
240 V 324 V 339 V
480 V 648 V 679 V

The FR-F720 nameplate in question lists a three-phase input of 200–220 V at 50 Hz and 200–240 V at 60 Hz, 48.8 A. A supply anywhere in the 60 Hz band therefore holds an unloaded, healthy link between about 270 V and 339 V. The trip level is none of these numbers: it is a protection threshold set by design and printed in the manual's protective-function table for the exact model, and that table is what the drive is actually defending.

That gives the diagnostic rule. Measure the supply, multiply by 1.35, and compare with the bus the drive reports. If the bus tracks the line, the power section and its sensing agree and the energy is genuinely arriving from outside. If the bus reads far above what the measured line can produce, the sensing or protection circuit is reporting fiction, and the drive itself is the fault.

The three causes that remain #

  • Sustained high input voltage. Any line-to-line pair above the nameplate input range charges the link in proportion; the 1.35 multiplier does not soften it. Judge the supply against the input rating, not against the output specification printed beside it.
  • A switching transient on the feeder. The classic source is power-factor-correction capacitor switching, which excites an oscillatory ringwave on the distribution system. These transients typically last only a few cycles and peak on the order of 30% above the nominal line-voltage peak — enough to charge the link past its trip level, and invisible to a handheld RMS meter sampled afterwards. Trips that cluster at fixed clock times, such as morning pickup and afternoon peak, carry this signature.
  • A fault inside the drive. If every phase pair measures inside the input range, no transient lines up with the trips, and the fault still appears with no motor attached, the DC-voltage sensing or the protection board is the remaining cause. That drive goes to service or replacement; no supply-side change will fix it.

Work safely before the measurements #

NFPA 70E, 2024 edition sets the work practices for electrical maintenance: de-energize, lock out, and verify absence of voltage before opening equipment, unless a documented energized-work procedure justifies otherwise; confirm the requirement with your authority having jurisdiction and the drive documentation. The DC-link capacitors hold a lethal charge after the input breaker opens, so honor the discharge wait time the manual states for the model and verify the bus is down before reaching inside. Take every reading with a meter rated for the panel's measurement category.

The measurement sequence that decides it #

  1. Record the fault exactly as displayed, E0u3 on this model, plus the fault history and the operating state at each trip: power-up, idle, run command, deceleration. Do not clear history before capturing it.
  2. Isolate, lock out, and verify absence of voltage, then confirm the motor leads really are disconnected, insulated, and clear of the terminals.
  3. Energize and measure all three line-to-line pairs and the frequency. Judge them against the input rating, 200–220 V at 50 Hz or 200–240 V at 60 Hz on this nameplate, not against the output rating.
  4. Read the DC-link voltage from the drive's monitor display where the model provides one; a direct measurement at the link is for qualified personnel following the manufacturer's service procedure with rated instruments. Compare it with 1.35 × your measured line voltage.
  5. Put a power-quality recorder on the drive input, set to capture transients, and log across at least one full day of upstream switching: capacitor banks, transformer tap changes, large across-the-line starts.
  6. If the numbers are borderline, run the same configuration from a known-good feeder. If the drive runs clean there, the first feeder owns the fault; if it trips there too, the drive does.

Worked example: 236 V feeder, trips at 07:02 and 15:01 #

Inputs: FR-F720 on a 60 Hz system, motor disconnected, measured at the drive terminals 236 V, 236 V and 235 V line-to-line at 59.9 Hz, inside the 200–240 V input rating. The drive's monitor shows 319 V DC at idle.

Check the link against the line: 1.35 × 236 V = 318.6 V, so the displayed 319 V is exactly what this supply should produce. The power section and the DC sensing agree with the incoming line, so the drive is not inventing the voltage.

Now the trip pattern: the fault history shows trips at 07:02 and 15:01, and the plant's power-factor-correction bank switches at 07:00 and 15:00. The line peak the rectifier can reach is √2 × 236 V = 333.8 V. A capacitor-switching ringwave peaking 30% above nominal reaches 333.8 V × 1.30 = 434 V, and for the few cycles the ringwave lasts, the diodes charge the link toward that value until the protection circuit acts.

Decision: this drive is healthy; the feeder transient is the cause. Fit a line reactor, 3% or 5% impedance rated for the 48.8 A input, where the trade-offs are what choosing a line reactor or motor reactor for a VFD works through, and ask the utility about controlled capacitor switching. Prove the fix by capturing the next 07:00 switching event with the reactor installed and confirming no trip.

The fix for each finding #

Finding Commit to Proof
Any line-to-line pair above the input range, above 240 V at 60 Hz on this nameplate The supply is the fault: correct it with the electrical-system owner, by transformer tap, regulator setting, or the feeder itself All three pairs inside the input range under all plant load conditions, and no trips
Supply in range, bus tracks 1.35 × line, trips cluster at switching times The transient is the fault: line reactor at the drive, switching controls at the capacitors Event capture through a full switching cycle with no trip
Supply in range, no transient correlation, bus reads implausibly high or trips at power-up with no motor The drive is the fault: send it for repair or replace it Post-repair idle operation with no motor and no trip
Overvoltage only with the motor connected and decelerating The stop is the fault: lengthen the decel ramp, then size braking from the manual's resistor and chopper tables for the model Stops complete with no trip inside the drive's thermal limits

One rule holds across all four rows: with no motor connected, every overvoltage trip is either real energy arriving from the supply or a false report from the drive, and the two measurements above tell you which.

Questions asked

Can a braking resistor clear this fault with the motor still disconnected?

No. The braking resistor is switched by the drive's braking transistor and only conducts when the DC link exceeds its threshold while a connected load regenerates. With the motor off the terminals there is no regenerative energy, so the resistor never carries current. Whatever lifts the link comes through the input rectifier: high line voltage, a supply transient, or a faulty sensing board.

What DC-link voltage is normal on a 240 V three-phase input?

At no load the capacitors hold near the line-to-line peaks: about 1.35 × 240 V = 324 V average, 339 V peak. On 220 V that is 297 V, and on 480 V about 648 V. If the bus you read tracks 1.35 times your measured line voltage, the drive's power section and sensing agree with the supply.

Why does the drive trip at times other than deceleration?

The fault name describes the usual trigger, not the only one. The same DC threshold is reached by a surge on the supply system, which can arrive at power-up, at idle, or at a fixed clock time. Trips that cluster at specific times point to scheduled capacitor switching upstream, so compare the trip log against the switching schedule before touching the drive.

Can I raise the overvoltage trip level to stop the nuisance trips?

Not as a tuning parameter. The trip level is a protection threshold fixed by the drive's design and listed in the protective-function table of its manual; raising it would expose the DC-link capacitors and switching devices to voltage they are not rated for. Some drives offer an input-voltage selection, so check the manual for the exact model before assuming one exists.

How do I know the drive itself is bad?

When all three line-to-line pairs measure inside the nameplate input range, no captured transient lines up with the trips, and the fault still appears with no motor connected, the DC-voltage sensing or protection circuit is the remaining cause. That drive goes to repair or replacement, because no supply-side change will clear it.

Keep reading

  • Troubleshooting

    Why a grounded motor trips the VFD line breaker at power-up

    It happens for a reason: safe torque off only stops output switching, so at power-up the DC bus still charges and feeds the grounded motor lead through the drive's output diodes, tripping the line breaker before the control boots. Disconnect and test the cable off the drive, then recheck the breaker against the installed nameplate — a 5 hp drive on a 3 hp breaker selection nuisance-trips.

    Variable frequency drives

  • Troubleshooting

    Why a VFD reports a motor overload fault

    A motor overload fault on a VFD means the drive's electronic thermal model accumulated heat from current above the motor's entered rated current. Compare measured current with both the nameplate full-load current and the drive's entered value before changing any setting: the fix is the load, supply, cooling, or the typed-in number, almost never a raised limit.

    Variable frequency drives

  • Troubleshooting

    Why a VFD trips a GFCI and what to do about it

    A GFCI or RCD trips on a VFD because the inverter's PWM output drives capacitive leakage current through the motor cable and winding capacitance to the equipment grounding conductor — commonly tens of milliamps against a Class A or 30 mA threshold, and only once the motor runs. Test the insulation first, then either supply the drive from a circuit not required to carry GFCI protection or fit a Type B residual-current device the drive documentation accepts.

    Variable frequency drives