Current IntelPower LibraryShop main store

Explainer

Why a motor-side braking resistor works on a PM servo

Variable frequency drives Published 8 min read

Short answer

Because your motor has a permanent-magnet rotor, it becomes a generator the moment the shaft keeps turning with the drive disconnected: close a three-phase resistor bank across the motor terminals and the generated current produces torque that opposes rotation. An induction rotor loses its field in a fraction of a second, so this is a PM-servo arrangement, built as a fail-safe path that brakes even when the inverter is dead.

On this page
  1. What the spinning PM rotor does once the drive lets go
  2. Why the same bank is nearly useless on an induction motor
  3. Motor-side bank versus the drive's DC-link brake
  4. The fail-safe switching arrangement
  5. Energy per stop for 0.02 kg·m² at 3,000 rpm
  6. Setting the resistance
  7. Proving the stop, and opening the panel only dead
  8. The decision, case by case
  9. Questions asked

The vendor's switch is a motor-side dynamic brake, and it works for exactly one rotor type: a permanent magnet. A PM synchronous motor generates stator voltage whenever the shaft turns, drive connected or not, so once the switch isolates the inverter and closes the motor onto a three-phase resistor bank, the machine loads itself as a generator and its torque opposes rotation until the load stops. An induction motor fed the same way gives you a fraction of a second of braking and then coasts, because the rotor field that produces the voltage collapses once the drive stops supplying magnetizing current. The arrangement exists for the emergency stop that must still brake when the inverter itself is dead.

What the spinning PM rotor does once the drive lets go #

A permanent-magnet rotor carries its own flux. Move that flux past the stator and you get terminal voltage with no excitation from anywhere else, proportional to speed and set by the motor's magnets and windings. That is why the machine keeps acting as a generator after the output switch opens: the voltage is still on the terminals, and it rises with rpm.

Close the motor onto the resistor bank and current flows. Generator action makes the electromagnetic torque oppose the shaft, and the rotating system's kinetic energy converts to heat in the bank and in the motor windings. The braking lasts as long as the shaft turns; nothing is consumed but the motion. Torque is strongest at high speed, where the generated voltage drives the most current, and it tapers as the machine slows, reaching zero at standstill — no generated voltage, no holding torque at zero speed. Lower bank resistance draws more current and more braking torque, up to the currents the motor is built to take.

Why the same bank is nearly useless on an induction motor #

An induction machine has no magnets. Its rotor field is induced by the magnetizing current the drive supplies, so when the output opens, the only flux left is what is trapped in the rotor circuit, and it decays with that circuit's time constant — fractions of a second, with no motor-independent number; the exact duration is a property of your specific machine. After that the terminals are dead and the load coasts on friction and windage.

A resistor bank cannot fix this, because keeping the field alive takes reactive current, which resistors never supply. Only capacitance self-excites an induction machine — the same physics behind the self-excitation overvoltage concern when power-factor-correction capacitors sit across induction motor terminals. So on an induction motor the bank buys a fraction of a second of weak braking and a long coast after it. If the proposal reaches you with an induction motor on it, decline it.

Confirm the rotor type from the motor documentation before leaning on any of this. The word servo on the order is not evidence: machines assumed to be induction have turned out to be PM once someone opened the datasheet.

A drive's normal dynamic brake switches a resistor across the DC link while the inverter keeps switching, bleeding the regenerated energy off the bus; a regenerative front end sends it back to the line. Both paths run through the drive's power electronics and control, which is precisely their limit. Trip an emergency stop with shorted IGBTs or a dead control board and neither path gives you any braking at all. The motor-side bank is the only electrical brake left standing in that failure, and that is the reason the vendor asks for it.

The drive's electronic inhibit is also faster and cleaner than any contactor sequence, and the contactor adds a failure point with downtime attached. Accept that cost only for the stop that genuinely needs it, the final emergency stop; normal deceleration stays with the drive.

DC-link brake chopper with resistor Motor-side resistor bank
Connects Across the drive's DC bus Across the motor terminals, behind an output switch
Needs working Inverter, chopper transistor, drive control Contactor logic and the rotor's magnets
Energy path Through the inverter onto the DC bus Motor generates straight into the resistors
Covers Controlled deceleration while the electronics live The stop after inverter failure or power removal
Sized from Drive braking data and duty Motor generated voltage, ½Jω² per stop, duty

The fail-safe switching arrangement #

The switch the vendor sketched is usually two contactors with opposed states. The drive-to-motor contactor is normally open, its coil energized to run. The motor-to-bank contactor is normally closed, its coil energized during running to hold the braking contacts open. The emergency-stop chain drops both coils at once: the drive contactor opens, and the brake contactor's springs close the motor onto the resistors. Losing coil power alone does the same thing, which is what makes the brake fail-safe — a dead control supply still leaves braking connected.

Two details keep the sequence honest. A mechanical and electrical interlock between the two contactors stops both being closed at once, so the inverter never drives into the resistor bank. And the brake contactor's auxiliary contact belongs in the drive's enable circuit, so any closure of the braking contactor inhibits the inverter output first — that covers the failure where its coil dies while the machine is running. The chain reaches back to the infeed too, and protection on that side is its own subject: using a motor circuit breaker on a servo drive infeed.

On the standards side, IEC 60204-1, 2016 edition, covers the electrical equipment of machines and defines stop functions by category: category 0 removes power immediately and lets the machine coast, category 1 is a controlled stop followed by power removal, and category 2 is a controlled stop with power kept. This resistor path is a braking means that keeps working after power removal, so it turns a category 0 coast into a braked stop, and its stopping time becomes part of the stop function's validated performance.

IEC 61800-5-2, 2021 edition, covers safe-stop functions integrated into drives. A drive's safe torque off removes torque but brakes nothing — a coasting PM load keeps spinning — which is exactly the gap the bank fills. Confirm the classification and validation your installation answers to with the governing edition of the machine-safety standard, the authority having jurisdiction, and the drive and motor documentation.

It remains a coarse stop: speed falls along a resistor-shaped curve, with no current control and no position authority. Right for a final emergency stop; wrong for positioning.

Energy per stop for 0.02 kg·m² at 3,000 rpm #

Inputs, illustrative and labeled as such — put your own in their place: total inertia referred to the motor shaft J = 0.02 kg·m², motor plus load through the gearbox; speed at the moment of the stop n = 3,000 rpm; target stop time t = 1 s; duty assumed at six emergency stops per hour. The rule in words: a rigid rotating system stores kinetic energy equal to one half the inertia times the square of angular speed, E = ½Jω², with ω = 2πn/60 in radians per second, and the bank must absorb that energy as heat during the stop.

The arithmetic, carried with units: ω = 3,000 rev/min × 2π ÷ 60 s/min = 314 rad/s. E = 0.5 × 0.02 kg·m² × (314 rad/s)² = 0.5 × 0.02 × 98,700 kg·m²/s² ≈ 987 J. Average power over the one-second stop: 987 J ÷ 1 s ≈ 987 W. Spread over a three-phase bank, each resistor absorbs about 330 J. From 3,600 rpm instead, ω = 377 rad/s and E = 0.5 × 0.02 × 142,100 ≈ 1,421 J — 20 percent more speed is 44 percent more energy, because 1.2² = 1.44. The duty load: 6 × 987 J = 5,922 J per hour ÷ 3,600 s ≈ 1.6 W continuous, which is negligible.

Decision: if the machine can reach 3,600 rpm, the bank's rated pulse energy per stop must be at least about 1.42 kJ; a smaller bank overheats on the first stop from speed. At emergency-stop duty the per-stop pulse rating governs and continuous wattage barely matters; if the scheme is used for routine stops, redo the duty arithmetic at the real stops per hour.

Setting the resistance #

The ohms come from one number only the motor datasheet supplies: the line-to-line generated voltage, the back-EMF, at braking speed. A workable starting point is to pick the per-phase resistance so the generated voltage at rated speed drives roughly the motor's rated current through the bank, which puts braking torque in the region of rated torque. Lower resistance buys more torque and more heat in the same step, and both motor and bank must be built for repeated abrupt stops — the motor documentation has to say so. The stop test settles the value; the calculation only starts it.

Proving the stop, and opening the panel only dead #

Verification is a shaft speed versus time trace taken during a controlled test; the stopping time it shows is the acceptance number for the stop function. If you clamp a meter on the braking current, the waveform cautions that govern drive outputs govern here too — see measuring VFD and soft starter current with the right meter. And before anyone opens the contactor cabinet, a motor terminal box or the resistor enclosure to inspect the wiring, lock out, de-energize and test for absence of voltage under the NFPA 70E, 2024 edition, work practices where they apply; the bank runs hot after stops, and the drive's DC-link capacitors hold charge for the discharge time its documentation states.

The decision, case by case #

  • PM rotor, emergency stop that must brake through an inverter failure: fit the bank, with a normally closed fail-safe braking contactor, an interlock against the drive contactor, inverter inhibit on any bank closure, and a bank pulse-rated for the highest speed the machine can be stopped from — 1.42 kJ in the worked case.
  • Induction rotor: do not fit it. It brakes for a fraction of a second and then the load coasts; the dead-drive stop needs a mechanical brake instead.
  • Ordinary deceleration and controlled stops: leave them to the drive's ramp with its DC-link brake or regenerative unit — faster, controlled, and free of contactor wear.
  • Holding at standstill: the bank gives nothing at zero speed. A spring-applied brake holds what the resistor bank stops.

Questions asked

Will the resistor bank brake an induction motor fed from a VFD?

Only for a fraction of a second. An induction motor needs magnetizing current to generate voltage, and once the drive output opens, only the flux trapped in the rotor circuit remains, decaying with its time constant. A resistor bank never supplies the reactive current that would keep the field alive — only capacitance does that, which is why power-factor capacitors raise a different self-excitation problem. Treat the arrangement as PM-only, and plan a dead-drive induction motor stop around a mechanical brake.

Why is the braking contactor normally closed?

For fail-safe behavior. During normal running the coil is energized to hold the resistor contacts open; when the emergency-stop chain drops coil power, springs close the motor onto the bank. A plain loss of control supply does the same thing, so braking survives dead controls. Wire the auxiliary contact into the drive enable and to an alarm, so you learn immediately if the brake path changes state while running.

Does the motor-side bank replace the drive's DC-link braking resistor?

No. The DC-link chopper handles normal controlled deceleration through the inverter and needs working electronics; the motor-side bank exists for the stop after inverter failure or power removal. Size them separately — drive braking data for the chopper, the motor's generated voltage and one half J omega squared for the bank — and keep both when the machine needs both stops.

How much energy must the bank absorb per stop?

The stored kinetic energy, E = 0.5 times J times omega squared, with J the total inertia referred to the motor shaft. At 0.02 kg·m² and 3,000 rpm that is about 987 J, roughly 330 J per resistor in a three-phase bank. Energy rises with the square of speed, so a stop from 3,600 rpm needs about 1.42 kJ. Rate the bank at the highest speed it can be called on to stop from.

Will the bank hold the load at standstill?

No. The braking torque comes from the voltage the spinning magnets generate, and that voltage falls to zero as the shaft stops, so torque tapers away through the stop and disappears at standstill. A raised axis or an overhauling load that must be held in place needs a spring-applied mechanical brake; the resistor bank stops the load, the brake keeps it there.

Keep reading

  • Explainer

    Why a capacitor-run motor needs a special VFD

    A standard three-phase VFD will not run a single-phase capacitor motor usefully: the fixed run capacitor's reactance rises as output frequency falls, so the auxiliary winding loses its phase-shifted current and low-speed torque collapses. Use a drive documented for PSC or shaded-pole motors, or change to a three-phase motor.

    Variable frequency drives

  • Selection guide

    Measuring VFD and soft starter current with the right meter

    Use a true-RMS clamp inside its stated AC-current band for VFD input current and for soft-starter current, where line and load are one series path. On the PWM drive output, trust only a clamp its maker rates for drive output, a current probe with an oscilloscope, or the drive's own current display. A frequency-counter range like the Fluke 325's 5–500 Hz says nothing about its 45–400 Hz current accuracy.

    Variable frequency drives

  • Troubleshooting

    Why a VFD reports a motor overload fault

    A motor overload fault on a VFD means the drive's electronic thermal model accumulated heat from current above the motor's entered rated current. Compare measured current with both the nameplate full-load current and the drive's entered value before changing any setting: the fix is the load, supply, cooling, or the typed-in number, almost never a raised limit.

    Variable frequency drives