Troubleshooting
Why a VFD reports a motor overload fault
Short answer
A motor overload fault on a VFD means the drive's electronic thermal model accumulated heat from current above the motor's entered rated current. Compare measured current with both the nameplate full-load current and the drive's entered value before changing any setting: the fix is the load, supply, cooling, or the typed-in number, almost never a raised limit.
On this page
A motor overload fault on a VFD is a heat calculation, not a wiring diagnosis. The drive's electronic thermal model has watched output current run above the rated current entered in its motor data, accumulated the excess as winding heat, and reached the trip level. Three numbers decide the case: the motor's nameplate full-load current, the current entered in the drive, and the current you actually measure. In most trips the fix is a mechanical load, an unbalanced supply, blocked cooling, or a mistyped rated current — not a raised limit, because the motor's thermal limit does not move when a parameter does.
What the drive is protecting #
An electronic thermal overload is a calculation, not a heater element. The drive compares measured output current with the entered motor rated current, squares the ratio because winding loss rises with current squared, and accumulates the excess against a thermal capacity. When the accumulator fills, the drive reports the motor overload fault and removes output. A small excess fills it in minutes, a large one in seconds — inverse-time behaviour whose speed is set by the overload trip class: a lower class trips faster, a higher class tolerates longer overloads such as high-inertia starts.
The model believes whatever was typed into it. Enter rated current 10% high and the drive tolerates 10% more current than the motor should ever carry; enter it 10% low and the drive faults at 90% of true full-load current with a perfectly healthy motor. The entry must be the nameplate full-load current of the specific motor connected — the same discipline as setting an overload relay from nameplate full-load current.
Two standards give the function its standing. UL 61800-5-1, the US adoption of IEC 61800-5-1, evaluates a drive's protective functions — including solid-state motor overload protection — as part of the drive's certification, which is what lets the drive act as the motor's overload protection when it runs a single motor. NFPA 70, the National Electrical Code (2023 edition), withdraws that for multi-motor installations: when one drive feeds more than one motor, each motor needs its own overload protection on the load side of the drive. Confirm both points with your authority having jurisdiction and the drive's installation manual.
Separate this fault from an instantaneous overcurrent trip, which is an output-stage current limit measured in the drive's semiconductors. A drive that faults the instant the motor moves is on the overcurrent path — why a VFD trips overcurrent the instant the motor moves. Overload trips happen after the motor has been running and heating.
Read the fault data before you reset #
The fault history in the drive logs the output current and frequency at the trip, and the thermal accumulator usually decays only as the model simulates the motor cooling down — so an immediate reset and restart can re-trip before the shaft turns. That is the model working, not a new fault. Record the current, the output frequency, and the point in the machine cycle before you clear anything.
Fault names and numbers differ by manufacturer and series: one drive series labels the condition "Motor Thermal Overload" with fault code 78, another uses a different short code. Read the fault table for your exact model in the manufacturer's documentation before assigning a cause; the code tells you which protection actually operated.
The checks, in order #
- Lock out and verify absence of voltage before opening the drive, a terminal box, or the motor. Every step below that opens equipment follows this one.
- Compare three currents. Write down the motor rated current entered in the drive's motor data group, the nameplate full-load current, and the measured output current during the duty that trips. Measure the output with the drive's own current display or an instrument built for drive output, as covered in measuring VFD and soft starter current with the right meter — pulse-width-modulated output gives false readings on the wrong clamp meter.
- Inspect the mechanical train. With the machine isolated, turn the driven equipment by hand where practical: jams, product blockage, binding, misalignment, and rough bearings all add torque, and torque is current.
- Measure the supply under load. Compare all three phase-to-phase voltages at the drive input while the machine works. Low or unbalanced input voltage raises motor current for the same shaft load.
- Check cooling and duty. Ambient temperature above the motor's rating, a clogged fan cover or fin pack, and long runs at low output frequency on a shaft-cooled motor all raise winding temperature even when the current reading looks normal.
- Suspect the motor last, and isolate it first. Disconnect the motor leads from the drive output before any insulation-resistance test: the test voltage applied through the drive's output semiconductors can destroy the drive. Judge the reading against the motor manufacturer's test method and limits.
Checking a trip on a 10 HP, 460 V fan at 93% of nameplate current #
Inputs for this illustrative case, each one you can read in the field:
- Motor nameplate: 10 HP, 460 V, three-phase, 60 Hz, full-load current 14.0 A.
- Drive's entered motor rated current: 10.5 A, left over from a smaller motor when the drive was reused.
- Measured output current during the duty that trips: 13.0 A steady at 60 Hz, read with a true-RMS clamp meter rated for drive output.
- Ambient 30 °C, fan cover clean.
The rule in words: the motor's real heating follows the square of measured current divided by nameplate full-load current, and the drive's model applies the same square law to measured current divided by the entered value. The decision threshold is 100% of nameplate full-load current, sustained.
The arithmetic:
- Real load: 13.0 A ÷ 14.0 A = 0.93, so the motor runs at 93% of full-load current. Heating: 0.93² = 0.86, about 14% less heat than at rated load. The motor is not overloaded.
- What the drive models: 13.0 A ÷ 10.5 A = 1.24, and 1.24² = 1.54. The model accumulates a 54% excess until the thermal capacity fills and the fault fires. The entered value sits at 10.5 A ÷ 14.0 A = 0.75 — 25% below the nameplate.
Decision: measured current is below nameplate full-load current while the entered current is 25% low, so the fault is in the data. Correct the entered motor rated current to 14.0 A and re-run the duty — expect no trip. The branch runs the other way too: had the meter read 16.8 A against a correctly entered 14.0 A, then 16.8 ÷ 14.0 = 1.20 and heating 1.20² = 1.44, a real 44% overheat — clear the mechanical cause, correct the supply or cooling, and if the process genuinely needs that torque, size the replacement motor from the measured load with a documented sizing method rather than by trial.
Settings you may change, and settings you must not #
- Correct the entered motor rated current to the nameplate value whenever they differ. This single edit clears a large share of overload trips on healthy machines.
- Set the trip class to the duty. A higher overload trip class tolerates longer overloads during acceleration; a lower class trips faster. Choose the class that covers the longest measured start without covering sustained running overload — the same trade-off as setting overload relays for high-inertia motor starts.
- Address low-speed duty explicitly. The thermal model assumes the motor turns at full speed with its shaft fan; long runs at reduced frequency on a self-cooled motor need either the drive's documented low-speed derating or a separately ventilated motor.
- Use the motor's own sensor where available: many smaller drives accept a motor thermistor input from the winding, which protects the actual winding temperature regardless of the model's assumptions.
- Never raise the entered current above the nameplate value to stop trips. The parameter moves the model, not the winding.
Proving the fix #
Run the machine through the exact duty that tripped it — acceleration, peak process load, and the longest cycle — and watch the current trend rather than only the run status. Current should stay at or below nameplate full-load current through the whole duty, and the drive's thermal or overload-utilization display should settle well below its trip level. Re-check the three input phase-to-phase voltages under the same load, and file the measured currents with the maintenance record so the next trip diagnosis starts from data.
Questions asked
Can I stop the trips by raising the motor overload setting?
Only when the entered current was simply wrong. If the entered value already matches the nameplate, raising it teaches the model to accept current the motor was not built to carry, and the winding pays for it. Correct the entered current, the load, the supply, or the cooling; if production truly needs more torque, size the motor up from the measured load.
Why does the drive trip on overload at low speed when current is below nameplate?
A self-cooled motor's shaft fan moves less air as frequency drops, so the same current produces a hotter winding. Some drives compensate for this in the thermal model below a set speed; confirm the low-speed continuous rating in the drive and motor documentation. Sustained low-speed duty under load usually calls for a separately ventilated motor.
Can one drive's overload function protect several motors?
No. When one drive feeds more than one motor, NFPA 70, the National Electrical Code (2023 edition), requires each motor to have its own overload protection on the load side of the drive, because the drive's model tracks one entered current and cannot see individual motors. Confirm the installation detail with your authority having jurisdiction.
How do I insulation-test the motor without damaging the drive?
Disconnect the motor leads from the drive output terminals first, then test at the motor with the circuit locked out and absence of voltage verified. Test voltage driven through the drive's output semiconductors can destroy the drive. Follow the motor manufacturer's documented test procedure and limits.