How-to
Setting overload relays from motor nameplate full-load current
Short answer
Set the overload dial — or select heater elements — to the motor's nameplate full-load current for the connected voltage, with no multiplier. NFPA 70 NEC Article 430.32 limits (125% with service factor 1.15 or 40 °C rise, else 115%) are ceilings on the trip rating, not percentages to add to a dial already calibrated in motor amps.
On this page
- What number do I set the overload relay to?
- Where do I find the full-load current on the motor nameplate?
- How do the NEC 430.32 percentages apply to the dial?
- How do I pick the relay range or the heater elements?
- How do I set and check the overload in the starter?
- Does the starter size or the control transformer change the setting?
- What if the relay trips on start, or the motor still runs hot?
- Questions asked
Set the overload relay dial — or choose the heater elements — to the motor's nameplate full-load current for the connection you wired, with no multiplier applied. For your 3 HP three-phase motor on a 480 V system, that is the amperage printed beside the 460 V rating on the plate. The percentages in NEC 430.32 — 125% or 115% of nameplate current — are ceilings on the overload device's trip rating, not numbers to add to a dial already marked in motor amps.
What number do I set the overload relay to? #
Set the dial to the motor's nameplate full-load current — nothing higher, nothing multiplied — because a dial marked in motor amperes is calibrated to the relay's trip characteristic around that entry, and the manufacturers' instruction is to enter nameplate current directly. Winding heating rises roughly with current squared times time, so the relay carries a time-current curve: it rides out the few seconds of inrush at start and accumulates the heat of a sustained overload until it trips. The dial entry tells that curve where this motor's normal running point sits. Set too high and the motor cooks with no trip; set too low and every start nuisance-trips. Nameplate current is the point between those failures, which is why relay makers publish no factor for you to apply on top of it.
If the relay is the adjustable type with a range such as 3.2 A to 7.6 A, the size that brackets your motor's current is the right one, and the dial still stops at the nameplate value.
Where do I find the full-load current on the motor nameplate? #
Use the current printed beside the connection you actually wired — on a dual-voltage nameplate, the 460 V entry for a 480 V system — and write down the service factor and temperature rise at the same time, because they decide which code percentage governs. Horsepower, voltage and phase identify the machine; they do not produce the setting. Two 3 HP motors can carry different nameplate currents because motor full-load amps depend on efficiency and power factor, so read the plate rather than a horsepower table. On a dual-voltage machine the full-load current changes with the connection, so the entry you use must match the leads actually joined per the diagram on the nameplate or the terminal-box cover.
How do the NEC 430.32 percentages apply to the dial? #
NEC 430.32 sets a ceiling on the trip rating, not the dial entry: 125% of nameplate full-load current for motors marked with a service factor of 1.15 or higher or a temperature rise of 40 °C or less, and 115% for all others. A dial set to nameplate current already sits under that ceiling. Article 430.32 of NFPA 70, the National Electrical Code (2023 edition), governs overload protection for continuous-duty motors and requires a current-responsive device selected to trip, or rated, at no more than those percentages of nameplate full-load current. Confirm the adopted edition and any local amendment with the authority having jurisdiction, and the setting instruction with the relay documentation.
Worked example, from a documented sizing problem: a 20 HP, 230 V three-phase motor with a nameplate full-load current of 49.3 A and a service factor of 1.15 has a ceiling of 49.3 A × 1.25 = 61.6 A. The dial still goes to 49.3 A; 61.6 A is the most the protection may be rated to trip at, not the setting.
Worked example with illustrative inputs: say your 3 HP nameplate reads 4.8 A at 460 V with a 1.15 service factor. The dial goes to 4.8 A, and the ceiling is 4.8 A × 1.25 = 6.0 A. Setting the dial to 6.0 A because the code allows 125% lifts the whole trip curve by 25% — the double-percentage mistake. Many relays already build the allowance into their calibration, and some electronic relays apply their own service-factor multiplier internally, which is exactly why the relay manufacturer's setting instruction outranks any percentage you might add in the field. Heater-element tables fold the same relationship into the element number listed for a given current.
How do I pick the relay range or the heater elements? #
Pick a relay whose adjustment range brackets the nameplate current — a 3.2 A to 7.6 A dial, for instance, brackets typical 3 HP currents — and with heater elements, order from the exact assembly's published table, never by starter size alone.
| Overload type | Selection basis | Setting action | Error to avoid |
|---|---|---|---|
| Adjustable dial, thermal or electronic | A range that brackets nameplate current | Set the dial to nameplate amperes per the relay instructions | Adding a code percentage to a dial already calibrated in motor amps |
| Replaceable heater elements | The manufacturer's table for your exact overload assembly | Install the element listed for your current and conditions | Choosing by starter size, or mixing heater families between assemblies |
| Electronic relay with functions | Current range plus the protection functions you need | Enter motor current and trip class per the device manual | Treating extra adjustability as permission to raise thresholds |
The starter's construction decides what fits: identify the starter and its overload assembly before ordering, because an amperage match alone does not make a relay or heater family mechanically and electrically compatible with your device.
How do I set and check the overload in the starter? #
De-energize the circuit, lock it out and test for absence of voltage before opening anything; the rest of the job is five steps — record, choose, set, wire, verify.
- Record the nameplate full-load current at the connected voltage, plus the service factor and temperature rise.
- Confirm the relay's range brackets that current, or pull the heater element number from the exact assembly's table.
- Set the dial to the nameplate amperes and lock the adjustment; with heaters, install the elements and torque the terminals to the assembly's specification.
- Wire the overload contact so the contactor drops out and the controller sees the trip; wiring overload relay contacts to the coil and the PLC shows the standard patterns.
- With the motor at normal load, clamp each phase and compare the reading to the nameplate; if that current belongs in a monitoring system permanently, measuring three-phase motor current for a PLC alarm input covers the transducer route.
Does the starter size or the control transformer change the setting? #
Neither one moves the overload: the size 0 label designates the starter's frame and horsepower class — confirm its three-phase rating at 480 V against 3 HP in the manufacturer's data — and the 75 VA transformer feeds only the control circuit. The arithmetic for the control side: 75 VA ÷ 120 V = 0.625 A available at the secondary, and about 75 VA ÷ 480 V = 0.16 A on the primary. Motor current never flows through it. In the power circuit the contactor switches, the overload protects the motor against sustained overcurrent, and the branch breaker or fuse handles short circuits and ground faults; conductor sizing follows its own rules, as in sizing a motor branch circuit with #14 AWG and a 20 A breaker. The size 0 designation alone does not complete the design — the manufacturer's data ties it to horsepower, voltage and duty, and the overload assembly must be the one listed for that starter.
What if the relay trips on start, or the motor still runs hot? #
A trip on a healthy motor means the start outlasts the relay's trip class or the running current is genuinely above nameplate — fix the cause rather than raise the dial, because an over-set relay is how motors burn with no trip ever operating. Work through it in order. If the current settles at or below nameplate after a long acceleration — a fan or high-inertia load taking tens of seconds — the fix is a slower trip class, Class 20 or Class 30 instead of Class 10, selected against the manufacturer's trip curves; setting overload relays for high-inertia motor starts works that case. If the running current stays above nameplate with the dial set right, the cause is on the load or supply side — mechanical overload, voltage out of range, phase imbalance — and raising the setting only hides it. That sustained-overload-with-no-trip pattern is the failure behind why motors burn up with no overload trips on 480 V.
Questions asked
Do I size the overload from the breaker size or the wire size?
No. The overload tracks the motor: it is set to the nameplate full-load current. The breaker or fuse provides short-circuit and ground-fault protection, and the conductors follow their own sizing rules, so a 20 A breaker or #14 AWG wire on a motor circuit does not move the overload setting. Each device protects a different thing, and only the overload follows the motor.
Does a 1.15 service factor mean I can set the dial higher?
No. The service factor is the motor's ability to carry a continuous overload at rated voltage and ambient under stated conditions, not permission to weaken protection. NEC 430.32 treats a marked service factor of 1.15 as justification for a higher trip ceiling, 125% instead of 115%, and a dial set to nameplate current already sits inside that ceiling. Running habitually into the service factor still shortens insulation life.
Can I use a 10% alarm and 20% shutdown in the controller instead of an overload relay?
Not as motor thermal protection. Those thresholds carry no time characteristic, so they cannot reproduce a trip curve: a motor drawing 15% over nameplate for two minutes needs a timed response, and the inrush at start would trip an instantaneous 20% threshold every time. Use such thresholds as process monitoring layered on top of a properly set overload relay, never instead of one.
The relay trips during a long start. Can I raise the dial?
Not first. Clamp all three phases once the motor is up to speed; if the current settles at or below nameplate, the problem is start duration, and the fix is a relay with a slower trip class, Class 20 or Class 30 instead of Class 10, selected against the manufacturer's data. Raising the dial takes protection away from the running motor to excuse a long acceleration.