How-to
Wiring a three-pole contactor for a single-phase motor
Short answer
Run the single-phase current through two poles in series per the overload maker's diagram — supply to terminals 1 and 5, a link between 3 and 6, motor leads at 2 and 4 — and never parallel all three poles. Set the overload at 125% of the 6 A nameplate full-load current (7.5 A) when the service factor is 1.15 or higher or the temperature rise is 40 °C or less, otherwise 115% (6.9 A), per NFPA 70 (NEC) 430.32.
On this page
Run the motor current through two poles in series with the overload relay: supply on terminals 1 and 5, a link between 3 and 6, motor leads on 2 and 4. That is the connection the overload makers print for single-phase current through a three-element relay, and it keeps the trip mechanism calibrated the way it expects. If the nameplate says thermally protected or impedance protected, no separate overload is needed: switch the ungrounded conductor through one pole and leave the other two unconnected. Never jumper all three poles in parallel. For a 6 A motor the setting is 7.5 A or 6.9 A, decided by the service factor and temperature-rise markings under NFPA 70, National Electrical Code, 2023 edition, Article 430.
Run two poles in series with the overload #
A contactor pole only makes and breaks current. The overload relay measures it and drops the coil when its thermal or electronic model says the winding is in trouble — the split in duties is the difference between a motor starter and a contactor, and it is why the wiring answer depends on whether a relay is in the assembly.
A three-element overload is calibrated with current in all three sensing elements. Feed a single-phase motor through one element and two sit cold; on some trip mechanisms the drop-out point then shifts from the calibrated current. The manufacturer's single-phase diagram fixes that by sending the motor current through two poles and their elements in series, so the heat and the force on the trip bar land where the calibration expects them.
On the common numbering — line side 1, 3, 5, load side 2, 4, 6, with the overload elements between — the documented connection is:
- One supply conductor to terminal 1, motor lead off terminal 2.
- The other supply conductor to terminal 5.
- A link from terminal 6 to terminal 3, sized like the branch-circuit conductor.
- The second motor lead off terminal 4.
One conductor passes through a single pole; the other passes through two poles in series by way of the link, and both open together when the coil drops out. Use the exact diagram in the relay's own instructions, not the terminal numbers alone: numbering tells you pole order, not the sensing arrangement inside.
When one pole is the whole job #
A 6 A, 120 V motor draws 120 V × 6 A = 720 VA, well under 1 hp, and motors this small can carry their own protection. If the nameplate is marked thermally protected or impedance protected, the separate overload relay comes out of the design: run the ungrounded conductor through one pole (1 in, 2 out), leave the other poles empty and unjumped, and let the grounded conductor run continuous. Never break the grounded conductor alone — in the series arrangement the two conductors open together, which a controller may do.
The contactor still has to come from the maker's single-phase application table for the actual duty: the single-phase motor rating, not the three-phase AC-3 figure printed largest. The control side does not change with the motor's phase count — coil, stop-start station and trip contact wire the same way as in wiring a three-phase coolant pump starter from a 120 V signal.
Why the parallel jumper stays out #
Paralleling all three poles looks like free contact life; it is an unrated connection instead:
- The poles do not close and open on the same microsecond, so during make and bounce one pole carries the whole locked-rotor inrush, and during break one pole takes the full arc.
- Contact resistance differs pole to pole, so steady-state sharing is never even either.
The single-phase rating in the application table is stated for the documented connections and already covers this motor. On this style of contactor the single-phase data shows the series and single-pole connections, not a parallel one, so treat parallel as unrated unless the documentation for your exact device shows the connection and states a rating for it. Decision: two poles in series with a relay, one pole without, and nothing else.
Set the overload from the nameplate, not the contactor #
NFPA 70, National Electrical Code, 2023 edition, Article 430 covers motor circuits and controllers in the United States; overload protection sits in Part III, and for a continuous-duty motor of this size started automatically the requirement is in 430.32(C). Confirm the section and any local amendments with the authority having jurisdiction and the equipment documentation — editions and jurisdictions differ. In plain words, a separately installed overload device for this motor may be set no higher than:
| Nameplate marking | Code ceiling | Setting for 6.0 A full-load current |
|---|---|---|
| Service factor 1.15 or higher, or temperature rise marked 40 °C or less | 125% | 6.0 A × 1.25 = 7.5 A |
| Neither marking present | 115% | 6.0 A × 1.15 = 6.9 A |
Worked example with every input stated: 120 V single phase, 6.0 A nameplate full-load current, service factor 1.15, continuous duty, automatically started. The qualifying marking is present, so the 125% ceiling applies: 6.0 A × 1.25 = 7.5 A, and the relay you pick needs an adjustable range that spans that setting. The same motor without the service factor or the 40 °C rise marking falls to 115%: 6.0 A × 1.15 = 6.9 A. Choosing the relay class and range is its own step, covered in selecting overload and jam protection.
Both percentages are ceilings, not targets. Setting below the ceiling is permitted and kinder to the winding; configuring motor overload settings at 90% FLA versus the NEC 430-32 limits is exactly that trade-off, and the code leaves the choice to you.
Wire it, step by step #
Lock out the branch circuit and test for absence of voltage at the contactor line terminals with a properly rated tester before any conductor goes on a lug — this procedure has no energized step.
- Record the nameplate: voltage, full-load current, service factor, temperature rise, duty, and any thermal- or impedance-protection marking.
- Confirm in the manufacturer's single-phase table that the contactor frame is rated for this motor at 120 V.
- Confirm the coil voltage marking against the control supply; the coil follows the control circuit, not the motor voltage.
- With the circuit dead, land the two supply conductors on terminals 1 and 5.
- Install the 3-to-6 link with branch-circuit conductor, torqued to the value marked at the terminal.
- Land the motor leads on terminals 2 and 4.
- Set the overload dial to the value the nameplate earns in the table above.
- Wire the relay's normally closed trip contact in series with the coil, and the stop-start station to the control drawing.
- Leave the disconnecting means and the branch short-circuit device as separate functions: a contactor is a controller, not a disconnect, and the breaker above it clears faults; neither replaces the overload relay.
Prove it before you call it done #
Dead first: continuity from 1 to 2 and from 5 through 6, the link and 3 to 4; no continuity between line terminals or to ground that the diagram does not show; every lug torqued and the dial where you set it.
Then energize the control circuit. The contactor must pull in cleanly, drop out on stop, and stop the motor. Measure running current at normal mechanical load against the nameplate value, not against the contactor's rating: a motor above nameplate current is a load or supply problem, not a case for bigger hardware. Operate the overload's test function and confirm the coil drops out, reset it, and verify the restart behaviour. After the first loaded run, check the terminals with an infrared camera or temperature probe — a hot lug is a torque problem, and a nuisance trip at a correct setting has its cause elsewhere.
Two cases, two decisions: with a separate overload relay, the series connection and the ceiling the nameplate earns; on a thermally or impedance protected motor, one pole on the ungrounded conductor and no relay to set.
Questions asked
Does the contactor coil have to be 120 V because the motor is 120 V?
No. The coil voltage follows the control circuit that feeds it, so a 24 V DC, 120 V AC or 240 V AC coil can all switch the same power poles on a 120 V motor. Check the marking on the coil against your control supply before wiring anything, and fit a different coil if they disagree.
Does a service factor of 1.15 mean the motor can draw 15% more amps?
No. Service factor is a margin on horsepower under the conditions stated on the nameplate, not a current allowance. A separate marking, service factor amperes, is the current the motor draws at service-factor load. The overload calculation uses the full-load current marking; the service factor only decides which percentage ceiling applies.
Isn't the branch breaker enough protection for a small motor?
No. The branch breaker is sized for starting current and fault clearing, so it sits well above full-load current and will not trip while a 6 A motor winding carries 8 or 9 A continuously. The overload relay is the device that models winding heating and drops the motor out; without internal motor protection marking, leaving the relay out removes the only overload protection the motor has.
Can I set the overload between the two percentages, say 7 A?
Yes, provided the relay's adjustable range covers the value and it stays at or below the code ceiling for your nameplate. The percentages are maxima, not the only legal points. A motor manufacturer's recommended setting, or a practice such as 90% of full-load current, lands below the ceiling and is the safer choice for winding life.
The overload trips on start-up at the right setting. Can I raise it?
Not past the code ceiling. A trip at a correct setting points to the cause, not the relay: mechanical load above the motor rating, low supply voltage, a long acceleration, or a loose lug in the power path. Fix the cause; a setting above the maximum leaves the winding unprotected and is the one adjustment this code section does not permit.